ABERDEEN CHEMICAL PLANT ROUTINE CHEMICAL DOSIMETRY SUMMARY
MONTH OF: October 1982
DATE OF REPORT:
c: JF, CRM, PEM, PJK, RDJ, WFH,CRS, RAF, RAM, AHS T. G. Grumbles - Houston, L. A. Legendre- Ponca City
ALL SAMPLE RESULTS:
November 4, 1982
Chemical
VCM Lead Antimony Total Particulates
OVEREXPOSURES:
Job Class
< PEL No7"
%
79 86.8 10 100
0 0
Exposure
PEL OVEREXPOSURES No. %
12 13.2
00 0 0
Source
Dryer Utility General Helper
1.0 ppm, VCM 1.1 ppm, VCM
Vinyl Shift Supervisor
4
Dryer Operator
yj 1.6 ppm, VCM
Employee present when a VCM filter pack gasket blew out in the new. unit recovery area on 10/4/82. Employee assisting with maintenance work at the time.
w*
Employee helped insulate lines in the new unit recovery area. During that time, a union on the east RVCM charge pump nearby was found to be leaking (and was immediately repaired).
4-
Employee present in old unit re covery area when a contractor doing demolition work removed a valve from a knockout tank recirculation line. The old unit was being started up at the time and VCM was released as a result.
Helped clean out fluid bed dryer during a shutdown.
VAB.0001040259
OVEREXPOSURES - (Continued)
Job Class Lead Operator
Exposure V 1.8*; ppm,rVCM
Reactor Operator
n/ 1.9 ppm* VCM
*
Dryer Utility
V 2.6 ppm* VCM
Reactor Operator
* 3.0* ppm, VCM
Painter/Insulator/ Carpenter
6.4 ppm, VCM
Chief Operator
^ 10.3* ppm, VCM
General Mechanic General Mechanic
10.4* ppm, VCM 35.5* ppm, VCM
*Respiratory protection worn.
Jerald Uptain
Source
Employee helped correct problem following filter pack gasket blowout of 10/4/82 mentioned above.
Installed filters in old unit recovered VCM vilter pack. The pack had been opened and valved off prior to this time. The employee opened the pack, drained water from it and in stalled the new filters, noting a scent of VCM.
Employee acting as firewatch for demolition work in old unit when a valve was erroneously removed from a knockout tank recircula tion line (same incident as Vinyl Shift Supervisor overexposure of 1-4 ppm mentioned above).
Employee overexposed while sampling 741 and 743 reactors.
Employee worked near the new unit knockout tanks preparing for in sulation work. He recalls smelling VCM at one point.
v
Employee helped correct problem, following filter pack gasket blowout of 10/4/82 mentioned above.
Employee blanked out 9Q1 vacuum pump.
Employee changed agitator seal on 741 reactor.
VAB.0001040260
A
4
ABERDEEN CHEMICAL PLANT ROUTINE CHEMICAL DOSIMETRY SUMMARY
MONTH OF: November 1982
DATE OF REPORT:
c: JF, CRM, PEM, PJK, RDJ, WFH,CRS, RAF, RAM, AHS T. G. Grumbles * Houston, L. A. Legendre-- Ponca City
December 3, 1982
ALL SAMPLE RESULTS:
Chemical
VCM Lead Antimony Total Particulates
OVEREXPOSURES:
^ PEL
NoT~
~~ t
78 92.9 23 95.8
0
3 100.0
^ PEL OVEREXPOSURES No. %
6 7.1 1 4.2
0 00
Job Class
*
Compounder
Expos u re
63.T* mierograms
lead/m^
Chief Operator
\J 1.5 ppm, VCM
Reactor Operator
V T.8 ppm, VCM
%
Shift Supervisor
V 6.7 ppm, VCM
Source
Employee did regular job of charging blenders on Line III, No specific cause for the overexposure has been found. However, a suspicion exists that it may have occurred when the employee removed his coveralls caus ing dusting.
Employee worked in vicinity of new unit blow tank during preparation for install tag a sparge pipe. A leaking valve in the system gave trouble.during the time.
Employee worked in old unit entire shift. No cause has been found for the overexposure. The employee and his fellow workers and supervisor have no recollection of anything that may have produced the over exposure.
Same as Chief Operator having 1.5 ppm, VCM overexposure.
im
VAB.0001040261
QVEREXPOSURES - (Continued)
Job Class Reactor Operator
Exposure v/ 7.9* ppm, VCM
General Mechanic
1.3* ppm, VCM
General Mechanic
14.5* ppm, VCM
*Respiratory protection worn.
A
Source Employee changed VCM filter pack filters in the old unit. Employee installed blanks in a recovery line in the old unit. Same as General Mechanic over exposure of 1,3 ppm, VCM.
rah
VAB.0001040262
-,,
-/ V::w^,,- ;0'/- *r- v
1 ^ .1
r-.' f.
v,v <*.%
Vfc, -H"
'J
4 -p
ABERDEEN CHEMICAL PLANT ROUTINE CHEMICAL DOSIMETRY SUMMARY
MONTH OF; December, 1982
DATE OF REPORT: January 10, 1983
c; JF, CRM, PEM, PJK, RDJ, WFH,CRSV RAF, RAM, AHS T. G. Grumbles - Houston, L. A. Legendre- Ponca City
ALL SAMPLE RESULTS;
Chemical
VCM Lead Antimony Total Particulates
OVEREXPOSURES:
< PEL No,
%_
65 91,5 16 88t9
2 100
*
PEL OVEREXPOSURES
%
6 8.5 2 11.1
Job Class
Exposure
Source
Color Weigh Compounder
721,0* micrograms 1ead/m3
Color Weigh Compounder
Reactor Operator
\/
120,8*, micrograms lead/m3
4.1 ppm, VCM
Employee did regular job of color weighup, No specific cause has been made certain, although a shift in work habits is most
suspect, Improved housekeeping and work practices are being re-emphasized at waiting.
Same as exposure of 721,0 micro grams lead/m3 above.
Employee checked for VCM leak in the new unit (recovery system diverter valve found to be culprit)
Reactor Operator
v 6,2* ppm, VCM
Same as exposure of 4.1 ppm, VCM above.
General Mechanic
1.3 ppm, VCM ~
Employee overexposed while un plugging steam lines feeding
steam tracers in the new unit
recovery area.
VAB.0001040263
OVEREXPOSURES - (CONTINUED)
Job Class Maintenance Helper
Exposure 1.4* ppm, VCM
Maint. Supt. (I&E)
2.3 ppm, VCM
General Mechanic
1.5 ppm, VCM
*Respiratory protection worn.
Source
Employee blanked out D-4QQ reactor in preparation for a seal change.
Employee supervised inspection of recovery compressor instru mentation during an intermittent VCM leak in the new unit.
Employee pulled blanks in VCM lines and recovery lines in the old unit.
VAB.0001040264