Document wrExMmadpD6gM5Egv6JxZNzk3
MONSANTO COMPANY ORGANIC DIVISION W. G. KRUMMRICH PLANT
PROCESS SAFETY AUDIT Department 246 Aroclors, Pyranols, Pydrauls, Inerteens
Supervisor
D. E. Harris
Supt. __________ P. E. Helsler
Written by:
Q. L. Judy D. H. Sartor
August - 1966
MONS 0A9290
PROCESS SAFETY AUDIT
Dept 246
Aroclors, Pyranols, Pydrauls, Inerteens
Raw Materials
The following toxic rating code will be used in describing the toxicity of these materials:
0 - none 1 - slight 2 - moderate 3 - high U - Unknown
A. Biphenyl (Code 82601)
1. Synonyms: Diphenyl 2. description: White flakes or solid off white mass;
somewhat pleasant odor. 3. Constants: Mol Wt. 154.2; M.P. 70C; B.P. 255* C.:
Density .9910 0 75A C. 4.* Flash Point: 235 F. (C.C.) 5.* Auto Ignition Temperature: 1004 F. 6. Toxic Hazard Ratine: , Acute Local: U
Acute Systemic: Ingestion 3, Inhalation 3, Chronic Local: U
* See Appendix for definition of these terms
7. Fire Hazard: Definitely when exposed to heat or flame; can react with oxidizing materials.
8. Fire fighting: CO2 or dry chemical
Biphenyl is received In 10,000 or 20,000 gallon tank cars from Anniston and in 4,000 gallon trailers from Associated Sales. The crystallized biphenyl Is melted with 80 lb. steam using the coils In the cars and additional hairpin coils if necessary. There is no temperature recorder or controller used during the biphenyl heatup. The pumping of the biphenyl to storage begins after the operator has visually Inspected the car and has determined that all of the biphenyl has melted. The full 80 lb, steam is left on the colls unless there is a danger of overflowing the car. Since saturated 80 lb. steam is 324 F. (162 C.) It is possible to raise the biphenyl temperature above Its flash point - 235 F. (113 C.). Since its melting point is 158 F. (70 C.) there is no need to heat this material to 324 F. It Is recommended that either 1. A temperature recorder, controller and alarm be put on the tanE
car when melting and unloading biphenyl and the temperature main tained at or below 26011 F. (93* C. ) maximum or 2. the tank car & unloading system be properly equipped to handle a flammable liquid (grounding, flame arrestor, etc.)
The molten biphenyl Is then transferred to the 25,000 gal. biphenyl storage tank where It is stored at 212 - 250 F. (100 - 120 C.) per operating instructions. There is a temperature recorder to Indicate the biphenyl temperature but no alarm or control system. Since the
HONS 049291
2
A. Biphenyl (continued)
biphenyl is being stored at and above its flash point it must be
treated as a flammable liquid. It is recommended that either the storage temperature be controlled at or below 200" F. I93C) or
1. A3" breather vent with a traced flame arrestor having removable
trays be installed. This will replace the undersized 2" vent now on
the tanltT
~'
3. The~Tank be properly grounded per Standard E2.
T A dip pipe be installed to Introduce biphenyl into the tank per
...'SUnfera DV2 Std. 3TT-------- ------------- --------------------------------
ID A sign be placed on the biphenyl storage tank labeling it "BIPHENYL --wjufair.*--------------------------- ^------------ ---------------------------- --------------------------
5. installation of a fire protection system adequate for fire control at the biphenyl storage tank be investigated. Use of water will
create no problems.
The biphenyl in the storage tank is pumped up to a 700 gal. measuring tank on the fifth level. There is a 1$TM traced and insulated overflow back to the biphenyl storage tank to maintain a constant charge size to the chlorinators. The biphenyl is kept molten with 80 lb. steam reduced to 4o lb. A 6o lb. relief valve protects the Jacket. Forty lb. steam at 286 F. (142 C.) keeps the head tank temperature above
the flash point of biphenyl. There is no temperature recorder, con troller or alarm on this system. '
It is recommended that either 1. The biphenyl temperature be kept at
or below 366* F. (93* C.) or 2. The biphenyl head tank be properly
equipped to handle s flammable liquid.' B
Ki
B. Chlorine (Code 81059)
1. Description: Greenish yellow gas 2. formulaiJTg 3. Constants: Mol. Wt. 70.914; M.P. = 101 C.; B.P. - 34.5 C.;
Density 1.47 9 0C. 4. Toxic Hazard Rating;
Acute local: Irritant 3; Inhalation 3 Acute systemic: 0 Chronic local: U Chronic systemic: U M.A.C. - 1 PPM in air per 8 hour day.
5. Toxicology: Chlorine is extremely irritating to the mucous membranes of the eyes and respiratory tract. It combines with moisture to liberate nascent oxygen and from hydrochloric acid. Both of these substances, if present in quantity, cause inflamma tion of the tissues with which they come in contact. If the lung tissues are attacked. Pulmonary edema may result. A con centration of 3*5 ppm produces a detectable odor; 15 PPM causes immediate irritation of the throat. Concentrations of 50 PPM are dangerous for even short exposures. 1000 PPM may be fatal even when the exposure is brief.
HONS 049292
-35. Toxicology: (continued)
Because of its intensely irritating properties, severe industrial exposure seldom occurs, as the workman is forced to leave the area before he can be seriously affected. In cases where this is im
possible, the initial irritation of the eyes and mucous membranes of the nose and throat is followed by cough; a feeling of suffoca
tion and later pain and a feeling of constriction in the chest. If
exposure has been severe, pulmonary edema may follow with rSles being heard over the chest.
6. Fire Hazard: Moderate - can react to cause fire or explosion upon contact with turpentine, ether,ammonia gas, illuminating gas, hydrocarbons, hydrogen and powdered metals.
7. Explosion Hazard: Present by reaction with reducing agents.
8. Disaster Control; Dangerous; emits highly toxic fumes; will
react with water to form toxic and corrosive fumes of HC1; Is heavier than air - gas will hug the ground. People without
adequate protection should go across wind until out of the affected area.
Chlorine is transferred by a 4" pipe line from the Chlorine Department. As it enters the department it passes through a
Brink Demister which removes any entrained liquids. Prom there it passes through a chlorine vaporizer which adds enough heat to prevent any liquid chlorine from entering the system.
The vaporizer uses regulated 80# steam to heat up the incoming
chlorine. If the Clp pressure reaches 50 lbs., the steam is automatically shut off thus preventing further pressure buildup.
However, if due to a plug in the Clp line past the vaporizer, the chlorine pressure builds up to 50 Ids ., and if the ambient temperature
is below 30" F.-(the liquifying temperature of chlorine at 50 lbs. pressure) there is a possibility that when the steam is automatically shut off liquid chlorine will be formed and sent on to the chlorinators. The immediate flash vaporization of the chlorine as it enters the hot chlorinator presents a potential hazard.
It la recommended that
1. A temperature controller be put on the vaporizer to maintain
a chlorine temperature of ^0-50"
(5 - 10" C.), this would
eliminate the possibility of liquid chlorine entering the chlorlnators.
2. A pressure alarm be put on the vaporizer in case the steam valve falls to shut off when the C12 pressure reaches 50 lbs.
HONS 04993
-4-
C. Nitrogen (Code 43099)
1. Description: Colorless gas 2. Formula: Np 3. Constants: Mol. Wt. 28.02; M.P. - 210 C: B.P. - 195.8" C.;
Density 1.2506 gr/liter at 0s C. 4. Toxicity: None. In high concentrations it Is an asphyxiant.
Nitrogen is used as a purge on the electrical grade Aroclor tanks
and on the #1 blend tank system before making a 1254 and 105t Xylene mix. It is handled properly.
D. Xylene (Code 64005)
2096 Ortho 36% Meta
15J< Para 2fl$< Ethyl benzene Purchased from Shell Petroleum Co.
1. Description: Colorless liquid. 2. formula;' CfiHk (CHo)2
3. Plash W, 85 F. to 100 F. depending on composition of Isomers.
4. Density: .864 @ 20/4 C.
5. Explosive Range: 1.1 to 7.0j< in air.
6. Toxic Hazard Railing:
Acute Local: irritant 1 Acute Systemic: Inhalation 1
Chronic local: Irritant 1 Chronic Systemic: Inhalation 1
Skin Absorption 1
7. M.A.C.: 200 PPM in air.
0. Fire hazard: Dangerous when exposed to heat or flame; can react with oxidizing materials.
9- Fire fighting; Foam, COg, or dry chemical. 10. Explosion riazard: Moderate in vapor form.
Xylene is used only to make an Aroclor 1254 and I0j( Xylene mix. It is received in 50 gallon steel drums and stored on pallets on the east side of the department. Xylene is extremely flammab
and should be handled and labeled as such. It is recommended that the Xylene storage area be laid off and a sign "Xylene Flammable" erected.
E. Trichlorobenzene (Code 60200)
1. Description: Colorless liquid as received in Aroclor Department
It is a mixture of 1,2,3 and 1,^4 TCB and possibly oiler Isomers
2. Formula: C6H5CI3
3. Constants: Mol. Wt. 181.5: M.P. approx. 10 C.. B.P. 213 C. 4. Plash Pfc."about 230 F. (C.C.)
5. --foxlcffcH5taizrai6rd~Rara;tin~gt:r
mums 049294
Acute Systemic: Ingestion 2; Inhalation 2
Chronic local; causes loss of hair of experimental animals.
Chronic Systemic: Ingestion 2; Inhalation 2
-5E, Trichlorobenzene (Code 60200) (continued)
6. Fire Hazard: Moderate when exposed to heat or flame. When
heated to decomposition (300 C.+) it emits highly toxic fumes of chlorides. Can react with oxidizing materials.
7. Fire fighting: Water, foam, C0? or dry Chemical. TCB is used as a blending agent in the production of Pyranols. It is handled and stored safely in underground storage tank #6.
F. Tri Cresyl Phosphate (Code 80180)
1. Synonym
O-Tolyl phosphate
2. Description Colorless liq.uid
formula:' (EhaC6H4)q PO4
Constant's; Mol. wt; 368.36; M.P. -25 to -30 C. BP. 410C.
5. Flash Point: 460 F. (c.c.
6. Toxic Hazard Rating: Acute Local: u Acute Systemic: Ingestion 3; Inhalation 2; Skin Absorption 2. Chronic Local: U
Chronic Systemic: Ingestion 2, Inhalation 2; Skin Absorption 2.
7. Fire Hazard: slight when exposed to heat or flame. When heated to decomposition it emits highly toxic fumes of oxides of phosphorus; can react with oxidizing agents.
8. Fire fighting: Water, foam, CO* or dry chemical. It is used in the production of Pydraul 280.
0. Qlycldyl Phenyl Ether (PPO) (Code 36100)
1. Description: Liquid 2. Formula: CgHi, CHo CHOCHo 3. Constants: M.P. 3.5* C.s B.P. 245 C. 4. Flash"PoTnt: 175* F. (O.C.) 5. foxlc Hazard Rating;
Acute local: U
Acute Systemic: Ingestion 3; Inhalation 3. Chronic local: U Chronic Systemic: U
6. Fire Hazard: Moderate; when exposed to heat or flame. Can react with oxidizing materials; The vapors of glycidyl phenyl ether normally will not present a hazard at room temperature. Inhalation of vapora above 60 C. should be avoided. Material should be kept from eyes or skin.
7- Fire fighting; Water, foam, COo or dry chemical. When heated to decomposition It emits toxic fumea.
8. Handling: Avoid contact with eyes or skin. Wash off with water IF any Is spilled on the skin.
Qlycldal Phenyl Ether is used as a chlorine scavenger In producl: Inerteen PPO ft 54201KA a mixture of Aroclor 1260 and TCB. It is stored safely In drums.
MONS 049295
-6-
H. Lime (Code 38800) (Calcium oxide)
1. Description: Fine white or slightly gray powder, Rhomeric Trigonal crystals.
2. Formula: CaO
3. Toxic Hazard Rating:
Acute local: Irritant 3; Ingestion 1; Inhalation 3. Acute Systemic: Ingestion 2; Inhalation 3;
Skin Absorption 0
Chronic local: Irritant 3, Inhalation 2 Chronic Systemic: Ingestion 2, Inhalation 3;
Skin Absorption 0.
k. Toxicology: Has a caustic reaction and therefore is irritating to the skin. As a dust it can cause dermatitis and irritation of the eyes and mucous membranes. It is a general nuisance type of dust.
5. Fire Hazard: None 6. Explosion Hazard: Virtually none 7. Handling? Bust respirator, adequate protective clothing, in
cluding rubber coated gloves, optional rubber full cover apron, and full cover plastic goggles should be used when handling lime
(dust). Adequate ventilation and dust removal equipment should be used in the handling area.
Lime is added to the still to neutralize any liberated HC1 and prevent sublimation of the FeClj catalyst.
I. Attapulgus Earth (Code 19^00)
Attapulgus earth Is an inert material and is handled in bags, drums
or buckets. There should be no toxicity, involved Sin handling this material, but as a matter of personal cleanliness, it should be washed from the skin or brushed from the clothing after handling it. It should not be blown from the clothing or skin with an air hose
as this is an unsafe practice.
J. Trl-Tetra Chlorobenzene Mix (Code 58500)
Received in tank cars. This is a mixture of trichlorobenzene and tetra chlorobenzene. It is similar in properties to TCB and should
be handled in the same way.
, ,, K. llnox Epoxide (Code 613201
HONS 049296
Handled in drums and used in production of Pyranol A13B3B. Purchased from Union Carbide; This material is didyclo diepoxy carboxylate. Prolonged and repeated contact of liquid or breathing of vapors or mists may cause delayed and serious injury.
Operators should avoid contact of this material with skin or clothln and should avoid inhalation of vapors or mists. In case of contact the skin should be washed thoroughly with plenty of soap and water and contaminated clothing and shoes should be removed.
7 L. Dow Corning Fluid (Code 31100)
A defoamer used in Pydraul blends. It has a flash point in the order of 600 F. and should present no particular hazard in handlim In the Interest of personal cleanliness it should be washed off if it comes in contact with the skin or clothing. M. Santolube 70 (Code 81787) Used in Pydraul A-200. Purchased from our Nltro Plant. This material chemically is the product of Oleic Acid and Triethylene tetramine reacted in Benzene with Tetra-prophenyl succinic anhydride and #5 oil. Its exact structure is unknown. Handled in drums should present no hazard as long as it is not over heated to de composition. Should not breathe fumes. Should be washed off if it comes in contact with the skin. O. Blue A Dye and AZO Oil Black Dye Used only in small quantities in Pydraul A-200 and Pydraul 200. Should present no particular safety hazard. Should be washed off If in Contact with the skin. P. General Comments 1. All raw materials used are stable under the present operating
conditions and would remain stable using any imaginable equip ment failure. 2. Biphenyl, Xylene and glycidal phenyl ether must be handled as flammable liquids under present operating conditions. 3. None of the operating areas is enclosed in such a way as to permit exposure to toxic materials. 4. The operators are knowledgable and trained to carry out the available emergency procedure in the event of a spill. 5. Adequate fire control is available in storage areas with the exception of biphenyl.
MONS 04929 7
-8-
XI. Process
A. Chlorination
Aroclor 13 produced by the batchwlse chlorination of biphenyl (from the biphenyl head tank) with snift gas chlorine (delivery pressure SO to 25 pslg) at a pressure of 2 - 4 pslg. Normal operating temperatures are between 120 and 170 C. Hydrogen chloride gas Is liberated during the reaction and Is piped to the muriatic acid department.
The chlorination reaction Is exothermic (510 BTU/Lb. of chlorine) and is stable. Biphenyl can be chlorinated as fast as the exothermic heat can be removed from the batch and still maintain a batch tempers ture of 150 0. In order to remove this heat, the reaction mass Is continuously circulated at an average flow rate of 200 - 220 gpm
from the bottom of the chlorlnator up through an air-cooled heat exchanger (capacity 1,200,000 BTU/hr.) and back into the top of the
chlorlnator over the catalyst bed. Maximum chlorine flow rate Is
1500 lbs/hr. (pipe size and supply pressure limiting). At 510 BTU/lb. this rate of chlorine flow produces 765.000 BTU/hr. which can be safely removed by the heat exchanger.
The temperature of the batch Is recorded at four different points:
1. In the center of the chlorlnator
2. Just below the chlorine sparger in the chlorlnator.
3. At the discharge of the chlorlnator pump.
4. At the discharge of the air-cooled heat exchanger.
Point 1 is alarmed for high temperatures (170* C.+) and point 4 Is alarmed for low temperatures. As a safety device, a high temperature sensing element Is positioned at point 2 to shut off the chlorine gas flow If the reaction temperature exceeds 190 C.
Each chlorlnator Is protected by a 8" - 20 lb. carbon rupture disc with a 3" discharge to the roof. Should a chlorlnator rupture disc
break any discharged liquids would be blown down through the grating onto anyone below. It Is recommended that either:
1. flooring be put on the level of the discharge piping from the
chlorinators or
2. fhe discharge lines be directed away from the working area and
a blown seal warning device (pressure) be Installed,
3. The siting ok the rupture disc and discharge line be Invest1-
fated. unless the oT' disc broke uu Into small nieces it mTSKt e~possioie to clog the 3" discharge lire with large pieces oT~
carbon.
^
In addition to the rupture system, the chlorinators can be manually vented. All of the manual vents are tied Into a central header system which Is vented to #1 blow tank. This vent system Is adequate.
MONS 049298
-9-
The chlorination system is well controlled. However, it is
recommended that all temperature alarms and automatic cut-offs
be checked. It does not require shut down and has not been
done since November, 19bj.
"'
Contamination of reactants with water of sulfuric acid will slow
down if not completely stop the reaction, The same hazard exists here as it does when the chlorinators are short charged or not
charged at all and chlorine flow continues. Because there is no means to detect chlorine in the off-gas (HC1), it is possible to chlorinate in the Brinlc demister or HC1 transfer piping. When
the heat from this exothermic reaction raises the temperature to 250" C., the chlorine will ignite the iron pipe. It is recommended
that some means of chlorine detection be provided In the off-gas system to prevent such an occurrence?
General Comments on Chlorination
1. Safe handling limits have been established and are observed.
2. There Is no provision for disposing of reactants in an emergency.
3. All Instruments fail safe.
. B. Aeration
The crude Aroclor is transferred from the chlorinators to #2 blow tank. This is a 2000 gal. steel tank with coils, an air sparger, and an 18" vent line. Here the Aroclor is air blown for 2 hours to remove any HC1 remaining in the crude.
There are no controls on this tank. 80 lb. steam is used on the colls for all Aroclors except 12k2, There is no danger of opera
ting within the Aroclor flash points as long as this procedure is followed. It is possible, however, that the operator could drop the wrong batch from the chlorinator (l.e. one Just charged).
This would mean that essentially biphenyl was being heated with 200# steam (388 P * 200 C.). Since biphenyl's flash point is 235 F., it is recommended that either:
1. A procedure be adopted to prevent dropping the wrong chlorinator 2. #2 Blow tank be properly equipped to handle a flammable liquid
Since there is no level recorder or controller on the tank, it is possible to overflow the tank and its hot contents on those below.
It is recommended that:
1. A level recorder be put on #2 blow tank.
2. Procedures be Included in the Operating Instruction to check this tank level before dropping a chlorinator.
After air blowing, the contents of #2 blow tank are transferred to #] blow tank where it is continuously fed to the distillation system.
There is a level indicator but no steam pressure regulator on #1 blow tank.
MONS 099299
10
C. Distillation
The straight take-over vacuum distillation is carried out in a 1100 gal.
and a 2200 gal. steel still. Feed is continuous to each still from #1 blow tank and feed rate is controlled automatically to maintain a set level in the still pots, The still contents are circulated continuously through a gas fired furnace (1 for each still). These furnaces are un
insulated and are in a position where personnel contact is possible. It is recommended that:
1. The still furnaces be Insulated and properly guarded.
2. A warning sign be placed on the furnaces.
Vacuum (30 - 50 mm Hg abs.) is maintained by two - 2 stage Worthington Jets and one - 2 stage Kulatl porcelain Jet with condenser. The porcelain Jet is always in operation whereas use of the Worthington
Jets is alternated. The porcelain Jet is grounded but the grounds are weather worn and most likely have a greater than 1 ohm resistance
(Monsanto standard). The Jet is not guarded. It is recommended that:
1. The adequacy of the grounding on the porcelain .let be checked and
the Indicated repairs made.
1
2. A guard be Installed around the .lets in case an explosion occurs.
Each still is equipped with a 30 lb. rupture disc and 4" discharge line. There are sufficient temperature recorders on the still system to Insure safe operation. Overheating of the still contents causes formation of a tar-like substance but presents no safety hazard.
D. Earth Treating
The distilled Aroclor is transferred from the 2 product receivers to
blend tanks #1 and #2 for earth treating. Attapulgus earth is added
to the distilled Aroclor (0.1 - 0.3% by weight) to absorb moisture and improve electrical properties. The mixture is agitated for 1 hour and transferred to a 33" Sparkler filter. The earth is removed by the filter and the processed Aroclor transferred to the finished product tanks (2 - 2000 gal. tanks). The Jacketed filter is heated with 8o#
steam. The Jacket has a relief but the filter doesn't. It is possible to overheat the material in the filter. It is recommended that:
1. A rupture system be installed on the filter to release any excess pressure buildup?
2. The Jacket relief be tested. Specs, for this filter show a 30 lbtested jacket. It is important that this maximum not be exceedecTT
Oeneral Comments on the Process
1. Accidental contamination of reactants will not form undesirable side products.
2. Process piping and controls are installed so as to prevent improper mixing of chemicals.
HONS 049300
General Comments on the Process (continued)
3. Sewering of materials would result In no hazards. If biphenyl, xylene, or glycldyl phenyl ether is sewered precautions must be taken to prevent ignition of the flammable liquids.
4. Department guarding conforms to the Illinois Health and Safety Code.
5. Ventilation is adequate to avoid exposure to toxic materials during all routine operations.
III. Finished Poods
A. Blending and Finished Product Handling
Aroclors are produced in a variety of grades and blends for use in capacitors, transformers, heat transfer fluids and plasti cizers. See Appendix II for a complete list of the Aroclors produced and their blends.
After the Aroclor has been earth treated in the blend tanks and transferred to the finished product tanks, it is transferred to an appropriate storage tank.
1. Aroclor for Sales
Aroclor that is to be sold without an additive is stored as follows:
a. Aroclor 1242 - Underground storage tank #3 (15,000 gal.), tanks #9 and 11 (20,000).
b. Aroclor 1248 - Storage tank #7 (20,000 gal.)
c. Aroclor 1254 - Underground storage tank #5 (15.000 gal.) and #10 stg. (20,000 gal.)
d. Aroclor 1260 - Storage tank #8 (20,000 gal.)
All storage tanks are equipped with the proper breather or con servation vents. Storage temperatures are not such that grounding or flame arrestors be required.
2 Pyranols
Pyranols are used mostly in transformer applications and are made by blending Aroclors with chlorinated benzenes and other additives. These materials are mixed in #2 mix tank (14,500 gal. and then transferred to finished product containers. This systea is adequately protected.
MONS 049301
i2
III. Finished 0ood3 (continued)
Two pyranols - Inerteen PPO and 5^201 KA - use 0.20% Glycidyl Phenyl Ether as an additive. This material has a flash point of 175" F. (80" C.). rt is added to the Pyranol - Trichlorobenzene mix through the suction side of the circulating pump after laboratory analysis is completed. Storage temperature of the contents in #2 mix tank is
between 90 and 100 C. This is above the flash point of the Glycidyl Phenyl Ether but may not be above flash point of the mix. It is
recommended that a sample of Inerteen PPO and 54201KA be taken after
the Ether has been added and a flash point determined. If storage temperatures are within lb* of the flash point either:
1. The tank must be properly equipped to handle a flammable liquid or
2. The storage temperature must be lowered.
These materials are circulated through a 18" filter before transferring to the finished product containers. This filter Is not protected with a rupture disc or relief system. It Is recommended that an appropriate relief system be Installed on the filter,
3. Pydrauls
Pydrauls are used mostly as heat transfer mediums. They are made by blending various Aroclor grades with additives. They are mixed
In #1 blend tank and stored under proper conditions.
4. Aroclor 1254 and 10% Xylene Mix
Xylene has a flash point of 85 - 100' F. which classifies it very
definitely as a flammable liquid. This mix Is made In #1 blend
tank. The xylene is stored In drums and unloaded by use of a dip
pipe put Into the drums. The drums are grounded but not adequately.
I,t Is recommended that this grounding system be checked and a proper
one Installed.
~
During preparation of a xylene mix all smoking In the department Is stopped and signs are put up in the department to that effect. Electrical cigarette lighters are removed from their receptacles.
#1 still Is allowed to run as usual by permission of the fire
Insurance inspector but #2 still furnace is shut off and kept off until the batch Is complete, any spills cleaned up, the tank closed off and a gas test of the area made. These provisions are a must.
The tank Itself Is Inadequately equipped to handle this liquid,
however. There Is a 2" vent line that follows an adjacent building and then discharges at the northeast corner about 3 feet from the
ground. The vent from #2 blend tank Is also tied Into this line.
This system Is unsafe and reflects Improper design. It Is recommended that:
HUNS 049302
- 13
III. Finished Good3 (continued)
1. A proper vent and flame arrestor be put on #1 blend tank.
2. The tanlc be grounded.
3. A separate vent be provided for #2 blend tank..
4. The flash point of the Aroclor 1254 and Xylene Mix be determined.
5. Storage temperature be kept as low as possible.
After blending is completed the mix is drummed off at the regular drumming station. This system is not grounded or equipped to handle flammable liquids. It is recommended that the Xylene drumming operation be altered to adhere to Monsanto safety specifica tions for handling flammable liquids. ~
5. By-product HC1
a. Synonyms: Muriatic acid, Chlorohydrlc Acid, Hydrogen Chloride. b. PescripCTon: Colorless gas c. FormulaHCl d. Toxic hazard Rating:
Acute local: Irritant 3; Ingestion 3, Inhalation 3 Acute Systemic: U Chronic local: Irritant 2 Chronic Systemic: U e. M.A.C.: 5 ppm in air for 8 hr. day f. Toxicology: Hydrogen chloride is an irritant to the mucous membranes of the eyes and respiratory tract. Concentration of 35 ppm causes Irritation of the throat after short exposure. Concentrations of 50 to 100 ppm are tolerable for 1 hour. More serious exposures result In pulmonary edema and often laryngeal spasm. Concentrations of 1000 to 2000 ppm are dangerous even for brief exposures. Mists of HCl are considered less harmful than the anhydrous form since the droplets have no dehydrating effect.
This by-product containing some hydrogen is collected in a common header and flows to the central HCl absorption unit for the production of Muriatic Acid in Dept. P-218. If Dept. P-218 Is unable to use all the off-gas. It may be sewered in the Aroclor department after drowning It with water in a drowning Jet. The removal of HCl from the off-gas concentrates the original quantity of hydrogen and air to a point well within the explosive limits. Therefore, it is necessary to either dilute this gas going up the vent stack or Increase its velocity past the flame propagation rate (15 ft./sec.). This is accom plished by introducing a sufficient quantity of steam in the vent stack. At present there Is no means to guarantee that there is sufficient steam going up the stack. It la recommended that an alarm be put on the steam supply to the stack to detect loss of flow.
MOMS 0A9303
- 14 -
B. Loading Facilities
All loading facilities are adequate with the exception of the tank car loading dock on #11 track, Spot #4. It is recommended that the stairs be replaced and the guard rails be repaired.
I'll. Safety Equipment
All emergency equipment is in good condition and located in positions listed in Operating Instructions.
A. Fire Extinguishers
1. Dry Chemical - SW comer of building CH - main floor.
2. Two dry chemicals - W wall at top of stairs - 2nd floor. 3. COg snow - Main floor by N lean to door. B. Chlorine Masks 1. SW Corner - 2nd floor
2. Control room - 2nd floor 3. E - outside repair room 4. Wall - SW corner on sprinkler house
C. Scott Air Paks 1. Outside west wall of lean to.
D. Stretcher 1. NW corner of Building CQ.
2. South side of Dept. 25^ by road. E. Safety Showers and Eyebaths
1. Two showers and eyebaths SE corner of building - one unit on ground level and one on 2nd floor. These showers and eyebaths are equipped with temperature controllers which do not work. It la recommended that the temperature controllers be fixed.
F. Oeneral Comments on Safety Equipment and Operations. 1. Sufficient instructions are available to cover shutdown during an emergency situation (steam failure, power failure, water failure, plant disaster). Date of last review - April 1966. It is recommended that more specific procedures be written to cover shutdown during the preparation of a xylene blend.
MONS 049304
- 15 -
F. Qeneral Comments on Safety Equipment and Operations (continued) 2. It is possible to trap personnel on the north side If the south and middle part of the department is contaminated. It Is recommended that the Installation of an emergency exit on the north side of the department be considered. 3. There are no emergency lighting facilities. It Is recommended that equipment for emergency lighting be provided. 4. Fire protection Is adequate for the hazard existing, however, a fire In the biphenyl storage system could not be controlled.
HONS IH9305
- 16 -
APPENDIX I Definitions
A) Flash Point
The lowest temperature at which a flammable liquid will give off
a flammable liquid will give off a flammable vapor which will burn
momentarily. Fire protection standards recognize the "closed up (c.c.)" flash point. This Is determined by testing the material in a closed cup. This test reveals the lowest temperature at which sufficient vapors escape at the surface of the material to
flash when an ignition source is applied. This flashpoint tempera ture is the lowest temperature at which a stable explosive mixture of the material vapor and air can exist, and is the lower explosive limit expressed as temperature.
Many manufacturers, trade publications and the Interstate Commerce
Commission recognize the "open cup (o.c.)" flash point. This is determined by testing the material in an open cup. Because some vapor escapes during the test and because the vapor above the liquid is usually cooler than when the closed cup test is made, the 'bpen cup" test is as much as fifty or more degrees higher than the closed cup figure.
For this reason most of the flash points listed in this audit are by the "closed cup" method. He consider a liquid as flammable when the flash point is l^O* F. or lower by the tag closed cup method (American Standards for testing materials or A.S.T.M. D56-56). Materials having flash points above 140* F. should be treated as flammable liquids if they are stored, handled or processed within a temperature range starting at 15* F. below their flash point and
extending to above the auto ignition temperature.
B) Ignition Temperature (Fire Point)
The minimum temperature at which ignition will occur by application of flame or spark and burning will continue without further heating or application of flame.
C) Auto Ignition Temperature
The minimum temperature at which the substance will Ignite spontan eously upon heating. The degree of danger is determined largely by the flash point of the liquid, the concentration of vapors in the air (whether the vapor-air mixture is in the explosive range or not) and the possibility of a source of ignition at or above a
temperature sufficient to cause the mixture to burst into flame.
D) References
1) Factory Insurance Association: Safeguarding flammable liquids (1953).
MQNS 049306
- IT -
References (continued) 2) National Safety Council: Accident Prevention Manual for
Industrial operations. (1955). 3) National Fire Protection Association: Standards of the
National Board of Fire Underwriters for Storage, Handling and use of Flammable liquids. (Bulletin #30, 1950). 4) Commission of Illinois Publication: Rules and Regulations relating to labeling in the use. Handling and Storage of Substances Harmful to the Health and Safety of Employees. (June 1951) 3) Section VIII of the W.Q.K. Design and Construction Manual Safety Guidelines by T. H. Becker, 1958 and 1959.
MONS 049307
Product Aroclor. 1143-1342
Code
811.01
1148-1548 1154-1S54 IlWJ-lSbO
1102-1202
bii.02 '811.03 on .05 811.07
pyranol i486 810.94
InortMn PPO 810.92
54SBTTB------- 010.9S (1254 PPO)
- 18 -
APFEHDIX II Finished Products
Composition
Bolling Plash Point Point (760 mb)
1. R.i.sax - Dangerous rro^erllei or* Industrial Products.
2. T.H.Becker - W.C.K. Plant Flammable Hazardous Materials.
REMARKS
Chlorinated Biphenyl 42* chlorine
350*P. 325#c. c .c.
Chlorinated Biphenyl -480 Chlorine. Chlorinated Biphenyl -$40 Chlorine Chlorinated Biphenyl -600 Chlorine. chlorinated Biphenyl -620 Chlorine.
3H2"P. c.c. Hone
345
3b5'CT
Hone 305'C.
Rone -~39(nr-
600 Aroclor 1260 and 400 Trlchlorobensene
--
600 Aroclor
Plaeh
1260 plue 400
Pt. of
Trlchlorobentene TCB la
plus 0.200
230* P.
Olyeldyl phenyl
Bther (PPO)
7W Aroclor iz>4"
300 Trlehloro-
bentene and .200
Olyeldyl phenol
ether.
Slight fire hazard when exposed to heat or flame. Can become dangerous when heated to decomposition. Aroclore can emit highly toxic fumes. Ho problem operating tempera tures .
Ro particular hasard. Handle similar to Aroclor 1260 and TCB. Blight fire hasard If exooeed to heat or flame. Slight fire hazard whan exposed to heat or flam#. Vapors of Olydlcdyl phenyl ether should not be Inhaled above bO* C. Ro problem at operating temperatures. 4am# as above.
04S308 HONS
Product 1254 + 100 Xylene Pyranol ATira"
pydreul a-zbb
Pydreul 2B0 "
Santlclzer 79**
Montare
Finished Products
Code
811.12
Composition 900 Aroclor 1254 and 100 Xylene
Plash Point
Bolling ?olnt (760 mm)
REMARKS
Plash Pt. of Xylene 18 05 to 300* P.
Fire and Explosion Hazard when exposed to heat or flame due to presence of Xylene.
810.97
450 Aroclor 1260 plus 550 trl-tetra chlorobenzene and 0.1250 Unox Epoxide.
810.96
3340 Aroclor 1242, 66-2/30
Flash Pt. of
Aroclor 1240
plus minor amounts
of Santolube 70,
Lubrlzol 1360,DCF,
A20-011 Black dye
and blue A dye.
"811.19" 15.90 Aroclor
Plash
1260, 61.90 Aroclor 1246
Pt. of Aroclor
plus 21.80 Trl- 1246
cresyl phosphate is
and minor amounts or Sentolube 70
302* F.
(.400) DCP and
Blue A dye.
8ii.au11 500 Aroclor 1240 Flash Pt.
and 500 Aroclor of Aroclc r
1260.
1248 Is
388* r.
898.bU still bottoma
from Aroclor
Process.
Fire and explosion hazard when exposed to heat or flame. Should avoid prolonged breathing of fumes. No problem at operating temperatures. Slight fire hazard when exposed to heat or flame. Can become dangerous when heated to decomposition ee It will then emit highly toxic fumes, tfo problem et temperature handled in the dept. Seme as above.
Seme ee ebove. No problem et operetlng temperatures. These materiel* ere extremely hot end must be handled carefully. Fumea muat not be inhaled, present drum area la enclosed and should be adequate. Puma respirator should be worn.
HONS 049309
liqulp. Hunber (Item Number)
21-2210
(102) 21-0767 (103)
21-3261
(105)
21-32*5 (106) 21-3251 (107) 21-1203 (100) 21-11112
(109)
38-5H87 (116)
21-2066 (l?6)
Service Biphenyl Storage Biphenyl Head Tank
Size 10'b'1 x It0'6" U'6" x 5'6W
Capacity Jallona 55,000
700
Chlorinator 3' x 16' n
050
Chlorinator 3' x 16' #2 Chlorinator 3' x 16' #3
Chlorinator 3' x 16' **
Chlorinator 3' x 16'
#5
Chlorine 8*-5/0" * Vaporiser 11*
850 850
8^0 850
Blow Tank 7' x 7' 2,000 #2
20 Dept. 246 - Group Equipment
Jacket Breather Relief Vent Coila 5" Ho Jacket Tea 1V*e"nted to
Biphenyl Sts. Tank Ro Jacket 2* Valved line beaded With the chlor. to fl blow tank. ""
n"
Plame
Relief or
Arrestor Rupture Disc
96 Rone
No Ro
Ro Rupture Disc 20# - 3" line OK
Ro " No "
"M
No "
No Jacket
No
When Ifo internal pressure- 50# ateam auto, shut off. Coila -no 18" vent jacket line to
handle air blowing.
No No
No No
Grounded No No
No
No No No No No
No
MGNS 049310
Kquip. Number
(Rem
Number)
20-001*3 (130)
27-001*5 (131)
20-0062 (133)
38-0770 (136) 38-1378 (137)
U30)71
21-1377 (139) 21-0779
(J*2)
21-1399
0*3)
1V0238 ( : ' I-0700
') '.! .1*00 l'l?)
- 21 _____________ Dept. 246
Service Still #1
Size
Capacity Jacket
lal.
Relief
6' x 5'6" 1100 No Jacket
Furnace #1
Still #2
3/16" x
ZZy
6oo,ooc BTU
61 x 11'10"
2200 Gal.
"
Condenser
#1
Condenser #2
Receiver #1
Receiver
#2
Blend Tnk.
#1
12" D x 5'
12w D x 5'
5'6" x 5-6"
5'6" x 5'6"
7' x V
No
No
1000 N > Jacket
1000
"
2000 N a Jacket
Ml end Tnk. 7' x 7'
#2
CD
Sparkler FI ltcr
FI n Frnil .
7' x 7*
2000
2000
Yes
Breather Vent No Vacuum
6" Vent Stack to roof No
No
Flame Arrestor No
No
Relief or Ruoture Disc
30# Rupture Disc k 4" Line
No
Grounded No
No
No
30# Rupture
No
Disc ! 4"
Line
No No
No
No
No No
No
No
No No
No
N
" '*
"
2" line around Bldg, dischg. 2 ft. from
ground.
No
2" thru leanto tees Into #1 vent.
No
No No
No No No
No No No
2" (manifold d schg. abo> e control room)
F-r. d . 7' x 7'
2000
2" conserva tion vent
MUMS 049311
Equ1p. Humber (Item Number)
SI-0768 (1*8)
Service
Stg.Tank
X
Site 10' x 26'
Capacity Oal.
- 22
Jacket Relief
Dept.
Breather vent
246 1--------------------------- i---------------------i
Flame Arrestor
Relief or Rupture Disc
15,000 No
2"
No No
No
SI-0769 (150)
Stj^.TanK
Pydraul A-200
10' x 26* 18,000 No
Consv.Vent 2" 2 ot.
11
21-1110 Stg.Tnk.
(152)
#5 1254
10' x 26' 15,000 No
2 oz.
""
"
21-3526 Stg.Tnk.
(<)
#8 1260
12'6" x 22'
20,000 No
3" Traced Ji Insulated
"
*
21-2404 (156)
Stg. Tnk. #7 1248
13' x 20' 20,000
No
2" Vent
"
"
21-0750 Blow Tnk.
(167)
#1
7' X 7'
2000
No
18'' Vent
"
"
"
#1 Mix Pydraul
12500 No
2" Vent
No
"
"
#2 Nix Pyranol
14580 No
3" traced
"
11
"
21-1396 (186)
38-5328 * Air Cooled 38-5569 - Heat
67 Exchanger
1.2 H BTU
35-3333 Steam Vac. 2 Stage
150# Stm
(205)
Jet #3
Porcelain 2 m Abe.
Yes
HONS 049312
Equip. Number (Item Number)
14-0138 (207)
Service
Tank TCB
Size
S% Tank 1242
#10 1254
#11 1242
- 23 -
Dept. 246
Capacity Jacket
Oal.
Relief
Breather Vent
9,500
No
20,000
20,000 20,000
No
No No
li" - 3 ft. Prom Ground Level
3" Conaerv. vent + i oz.
-
3" Conaerv. Vent j oz.
Flame Arrestor
Relief or Ruoture Disc
No No
No
No No
No No No No
No
No No
HONS 049313