Document wr4z5grEzDZr1NwBkZ0MOOQGE
R. C. Homil, Atlanta
November 6, 1967 {,''Prlto Lay Boiler Accident "Monday, October 30, 1967 '
(j '
*
G. R. Buchanan. St. Louis PPQjRP-USh. St. Louis Jt . IDS . MWw r4 imgVhVt, AAHtlantxa--
Stan Shaw - St. Louis
Stan i
With reference to the phone calls, 1 thought it might be wise if we recorded the sequence of events that have taken place with reference to the Frito Lay boiler accident.
On Monday, October 30, 1 received a call from an individual at Frito Lay in Jacksonville, who was inquiring about the medical aspects of Aroclor-1240 vapors which had been emitted from their heater and saturated the plant area at this location. Ibis call was referred to you, and in turn was handled by Dr. Kelley of our Medical Dopartment. (The name of this individual should bo on file with our Medical Department, but 1 am temporarily unable to find the particular name).
On Tuesday, October 31, I received a call from a Bill Dawson, Ouality Control Laboratory, Frito Lay in Atlanta, who was in quiring about tiie chemical makeup of Aroclor-1240. His request was primarily to find out if Frito Lay should try to salvage the peanut oil which had come in contact with the vapors of 1240. I indicated to Dawson at that time that 1248 was a chlorinated diphenyl product and that 1 felt that he should run a laboratory analysis on his material to insure that none of this material had been left in his peanut oil. I further offered Monsanto's assistance in running an analysis of his oil to Insure no con tamination from the vapors of the 1248 fluid. He indicated at this time that he felt that the peanut oil would bo disposed of and that an insurance claim would be placed with the Insurance Company involved to replace his peanut oil.
On Friday, November 3, Robert Crabtree of the Atlanta Office was
contacted by two individuals requesting information on the Aroclor
1248 fluid. Mr. Crabtree indicated that he would not be in position
to answer these questions, and asked that I return their call on
Monday, November 6. This was accomplished on Monday with the
following resultsi (l) Mr. William R. Lewis of Hartford Steam
Boiler Insurance Group had requested information as to the fire '
point and flash point of Aroelor-1248. The Information given
,
to Mr. Lewis consisted of numbers extracted from the aroclor
polychlorinated polyphenyls technical bulletin 0-FF/1. I gave
'
MONS 097765
Fego 2 Mono to - Stan dhow, ct. Louis
November 6, 1967
him a flash point of 379 to 384 with no fire point, and explained pro foot note that there wan no firo point up to tho boilin'} temperature of the materiel itself. I further gave him distillation range of 340 to 375 C. and he felt quite Bure this was all the information which would be re quired st this time by his organization.
-
The second individual requesting information with regards to
this unit was a O. IS. Johns of Register & Cummings Company,
218 V.'ost Church Street, Jacksonville, Florida, Mr. Johns is
s consulting engineer for the General Adjustment insurance
Division of Factory insurance Association, was quite inter
ested in the decomposition products of Aroclor-1249. At this
point 1 would like to regress and gives the sequence of events
as related to roe by Mr. Johns. lie indicated that at approxi
mately six o'clock on Monday morning the boiler wre fired from
a cold position,At approximately one hour or one and a quarter
hours loter^ n't was noted that the flame had fa Hod on the
burner unit. At this time an employee completely r.hut down the
system to ijicl'riq induced draft ian, which in Mr. Johns' own
words almost|Vnu^veKsel air tight. About fifteen minutes later
a muffled explosion occurred which buckled one side of the
heater about one foot, end the other side of tho heater was
buckled to tho point that it had e hole occur st one of the
Joints. Mr. Johns Indicated that the site of this haatwr
walls was approximately 3/les to 1/4 inch steel with re
fectory beckup. He furthor indicated that it bad been csteb-
llsYied that the tubes which ere made of black steel had cor
roded but this had occurred from the outside in, therefore,
eliminated any fault with tho hroclor material as being at
fault as far as corrosion is concerned. Johns indicated
that the refactory was somewhere in the neighborhood of
1100 to 1000 F. as a good estimate from the time the flame v.
cut off until the muffled explosion occurred. Information
A
going to Johns was that from the V. L. let lor,, .which indicated )
tho percentage by volume of gaseous decomposition of materials i
formed at 600 C. Which was given to me by Stan Shaw on Monday,/
November 6.
Z
Johns indicated his further need for information from some 'other 1 .incidents which have Involved Aroclcr heat transfer fluid, and ' indicated that his main concern here was what would have caused the hoater to buckle and to blow out on one side. H6 Indicated that this Information which'wes being disseminated to him would be held as privileged information, however, that it could bo used
M0NS 097766
page 3 Mumo to - Eton Shaw, 6t. Louis
November 6, 1907
tV/y\
In some sort of legal action if this were deemed necessary In the future.
It seems to mo in retrospect that the key to this entire problem Is the fact that the exhaust fan was cut off, thus making the heater almost airtight, and When these gaseous decomposition materials were formed they hod absolutely no place to go, and therefore caused perhaps this "muffled" explosion os experienced and reported by the Jacksonville fire department.
i, hny comments from any of the above individuals would be greatly
\f\.r appreciated, ond secondly, pleoee coewent *8 to similar expor-
`f / loneee with froclor heat transfer fluids which have happened,
\jy * \ \ oyn end which might shed some light on the Frito Lay incident.
' .v
V(V
Regards,
pJ'/viA^v ys*
r\\\yt1 \VvS''
Dick Ham11
r>'A. : J
Vv HCH/rb
j.
I l! ' .
.
MONS 097767