Document wqwVaRd8Zbmk5yMwEqKjY37nD
INVESTIGATION OF POTENTIALLY HAZARDOUS BYPRODUCTS FORMED FROM PCS'S
DURING THE ADELAIDE STREET TRANSFORMER FIRE
This report summarizes the efforts of the MOE Laboratory Services Branch and MOE Central Region to investigate the possibility of formation of toxic oxygenated compounds by the partial combustion of PCBs during the fire at 60 Adelaide Street, December 9th, 197f.
Laboratory Services Branch February 9th, 1978.
MOMS 211763
CONTENTS
Summary .............................,................................................................ i
Introduction ....................
l
Toxicity ............................................................................................. 1
Experimental Summary .............................................................. 2
Results ................................................................................................ 3
Numerical Data Table ............................................................... 5
Mass Spectra................................................................................... 7
Appendix A: Toxicology & Environmental
Behaviour of Polychlorinated
Diben^dioxins .................................... .. . . 8
Appendix B: Toxicology & Environmental
Behaviour of Polychlorinated
Dibenzofurans ................................................13
Appendix C: Analysis of Materials from
the Adelaide St- Transformer
Fire for the Presence of Potentially
Hazardous Byproducts formed
from PCBs......................................................, 17
NONS 211764
1
(1) MOE Laboratory Services Branch has analyzed a range of samples from the location of the Adelaide Street lire to determine the level of PCB contamination;
(2) In conjunction with the above analyses a sample of soot from the fire scene, and a sample of transformer fluid have been examined for the presence of chlorodibenzo furans and chlorodioxins;
(3) These tests were carried out on an emergency basis, and are the first tests of this type carried out by MOE laboratories. No standards are yet on hand for compara tive evaluation, and calibration. Estimates of concen trations present in the samples are thus tentative. Special instrumentation was acquired (gc/ms) and set up in mid January, 1978 to begin the experimental work;
(4) The presence of one tetrachlorodibenzo furan in the soot
sample has been positively confirmed. The estimated con
centration in soot is 2.5 ppm (possible range 0.5-4.5 ppm).
A range of other chlorodibenzo furans have been tenta
tively identified in the soot sample. Estimated total
concentration of these other furans 5 ppm (range 0.7-10 ppm).
Positive confirmation of the identity of these compounds
is not yet possible and further analytical work has to
be carried out.
.
(5) Trace levels (0.05 ppm) of the tetrachlorodibenzo furan was tentatively identified in the sample of transformer oil from the site of the fire;
(6) No positive identification of any dioxins (chlorodibenzo
dioxins) in any samples from the Adelaide Street fire has
yet been obtained.
' HONS 211765
7
Introduction
During the period commencing December 0th, 1977, the Laboratory Services Bianch was required to provide analytical support, and technical information for the investigation, monitoring and decontamination procedure resulting from the Ontario Hydro transformer fire at 60 Adelaide Street, Toronto. Analyses acre carried out on soot, solvent, swabs, air samples and other materials for PCBs.
At the same time, it was considered necessary to carry out experimental investigations into the possibility of formation of oxygenated bi-products from PCBs during the fire.
Since furans are known to be produced in PCBs, both as a I
byproduct of manufacture, and also after long term use at i clevatod temperature, it was decided to check for the presence
of these materials, and the related compounds - dibxms.
"J:no',.'A uvoduc"
-possible product
Toxicity
Chloroben:sodioiin
Furans aud Dioxins are very toxic compounds. Dioxins are known to be powerful teratogens (cause birth defects).. Brief reviews of the toxicity, known modes of production, and environmental behaviour arc given in appendices A fit B.
NONS 211766
. .2
2
The presence of chloroclibonzofurans in trace levels m new PCD fluids lias been well documented (1-3), Greatly enlifUiced levels of chlorodibc-nzofur.nis have also been documented in used PCBs (4). It is believed that those impurities and not PCD itself, were responsible for the outbreak of "YUS1I0" disease in Japan in 19GS, when a large number of people were poisoned by rice oil contaminated by PCBs (5). To date, no reports ha\e been made of the presence of c.hlorodibenzodioxins in now or used PCD fluids.
No reports have yet been published to indicate that these
toxic materials are formed during fires involving PCBs. However,
conditions during the Adelaide St. fire were such that formation
was considered possible - high temperatures with electrical
nrcing, partial combustion with limited oxygen supply, vaporized
PCBs,
.
Experimental work was initiated to check out this possibility of the formation of chlorinated dibenzofurans and dibenzodioxins. A sophisticated high sensitivity Gas Chromatograph/Mass Spectrometer (GC/MS) with capillary column capability was installed during January, 1978 for use in this project. This instrument provides the necessary separation capability, positive identification, and high sensitivity quantitative measurement necessary for analysing trace levels of chlorodibenzofurans and chlorodibenzodioxins.
Due to the lack of proper handling facilities for materials of this extreme toxicity, and the fact that staff has no previous experience of working with them, it was necessary to proceed with extreme caution, and restrict present work cm this project to the minimum necessary to obtain this data.
Literature searches provided a relatively comprehensive sol of sample handling, extraction, cleanup and separative techniques for isolating ch 1 orudihenzol mans and chlorodibonv.e-
HONS Z U 76?
3
It was decided to analyze soot from the walls of the building which contained up to 10,000 ppm of TCB residue (wet weight) and which was also a strong adsorbent for the compounds of interest.
A sample of soot was extracted, cleaned up, the compounds of interest separated from PCBs by column chromatography, and the appropriate column eluate fractions analysed first by gas chromatography using electron capture detection, then by GC/MS in both full spectrum scanning mode and selected ion monitoring modes. A full description of the analytical techniques used, and results obtained can be found in Appendix C.
At the same time that the soot extracts were analysed, samples of new PCB and used PCB fluid from the transformer at 60 Adelaide St. were also analysed using the same techniques.
Hesults
The soot extracts were shown to contain many polynuclear hydrocarbons which, in the full spectrum scanning inode, masked most of the other components present. However, one full confirmatory mass spectrum was obtained for an oxygenated product (Fig. 4). Tuis spectrum gave an excellent match with published spectra for tetrachlorodibenzofuran (Fig. 5).
Selected ion monitoring of ions characteristic of chlorodibenzofurans and chlorodibenzodioxins gave good confirm atory evidence of the presence of di-, tri-, tetra-, penta-, and hexa-chlorodibenzofurans, but insufficient evidence for positive confirmation of the presence of chlorodibenzodioxins.
Analysts of new PCB similar to that from the Adelaide St. transformer showed no trace of chlorodibcnzofurans or chlorodibonzodioxin. Analyses of used PCB from the Adelaide St. transformer showed traces of chlorodibenzofurans.
HONS 211768
. . 'j
4 These levels of chlorodibenzofurans were much lower than the levels found in the PCS residues from the soot-extract. This would indicate that the oxygenated products were formed during the fire, and did not originate directly from the used PCB fluid as was the case in the Japanese "YUSHO" incident.
Estimated dibenaofuran concentrations are shown in Table 1.
HONS 211769
5
TABLE 1.
\
CHLORINATED DIUEN7.QFUHANS IDENTIFIED EY GC/MS AND THEIR ESTIMATED CONCENTRATIONS IN DIFFERENT SAMPLES
Retention
Tentative
Time (min.) Identity
6.3 .8.3
9.9 11.1 11.6 12. 8 13.1 13. 1
CL2-F cl3-f Cl4-Fb cl3-f
ci5-r CVF CVF CVF
_____ Estimated Con contrations (ppm) Wot Soot Simple Transformer Oil Arochior
_____________________ _______________
1260 S
0.02-0.2 0.2-1.6 0.5-4.7 0.1-0,9 0.4-3.7 0.1-1,2 0.03-0.3 0.01-0.05
N.D. N.D. 0.01-0.1 N.D. N.D. N.D. N.D. N.D.
N.D. N.D. N.D. N.D. N.D. N.D. N.D. N.D.
Estimate of Total PCDF in sample tS 1-13 ppm
Concentration of PCB in sample - 1%
0.01-0.1 ppm N.D.
50%
100%
Estimate of Total PCDF per PCB present 100-1300 ppm 0.02-0.2 PPm
N.D.
(median = 600 ppm) (median := 0.1 ppm)
N.D. > not detected a dibenzofuran
b *= Positive confirmation on the basis of a full mass spectrum.
All values arc reported relative to weight of soot as obtained
from fire site. No correction for moisture content has been
made. A|>pro\imate soot moisture level 80%.
HONS 211770
6
Investigations wore limited byi
1. Lack of pure standard materials necessary for comparison and quantitative calibration. These materials were not ordered previously due to the lack of suitable handling facilities. The quantitative data presented here is an estimate, based on the response factors for standards made up with materials of similar structure to the furans and dioxins (e.g, tetrachlorobipheny1). Standards have been ordered and will be run in the near future.
2. Lack of an adequate high resolution gas chromatographic
column. Since the GC/MS has just been installed
the only column available was the test column
provided - a 3 ft. OV101 column of low resolving
power. Capillary columns will be installed as soon
as the system is fully tested and adequate disc
based data storage is acquired. Capillary operation
will provide the proper separation required to
obtain full confirmatory mass spectra for each of
the compounds so far identified by selected ion
monitoring.
.
HONS 211771
i !:; --
03
S3
S3
2E
Figure K Mass spectrum of GC peak at 9.9 nin.
' ` * *sA 1 * 1
iTt
ist jr.
i;l i I, auLii. lie I I t 1,^1 I t r2^' 1
3o(,
<i111
vf-1
rV
:1_
2io*f_-3L| I_ZIIt_l ___!l1h||1!iiir, >
1 1 zz
1 *322 * 1
' 3^2
R e la tive In te n s ity %
Figure *>. Kass spectrun of tetrachlorodibcnzofuran froa the literature (5).
aot. 3of
I I I sri i i
ZcQ
ni
2*1
14 IC1
ii___Ik
II.
11C31 ' f 1 fit:1 1 f 'sia1 1 r 'sic I I ' ' n-r~<
II
3^2
M/3
HONS 211772
APPEND IX A. THE TOXICOLOGY AND ENVIRONMENTAL BEHAVIOUR
OF POLYCHLORINATED DIDENZODIOX1NS
HONS
DIOXIN'S 1
The name dioxins refer to a group of chemicals of the chlorodibenzo dioxin family.
They have the structure:
The'benzene rings can be substituted with chlorine atoms resulting in many possible isomers, 75 in all. In general, only 5 or 6 have been made. Dioxins have been identified as impurities formed in the manufacture of some chlorinated phenols and chlorophenoxy acid herbicides. They have recently been identified in products resulting from an explosion in a chemical plant manufacturing the germicide "Hexnchlorophene".
Dioxins have very low solubilities in water 0.6 ug/1, (1).
occimncKCE
Dioxins can occur as impurities in the manufacture of some chlorinated phenols and chlorinated phenoxy acids herbicides, Reaction occurs when a chlorophenol condenses with itself to form a dioxin.
Cl Cl II a Cl o;
2XaCL
In the manufacture of 2,4,5,T (2,4,5-tri chlorophenoxy acetic acid) a common herbicide from trichlorophenol, certain reactions and high temperatures arc required. Under ideal condition, 2,4,5,-T will be produced.
HONS 211774
.2
-lo
ir the conditions are wrong, a small amount or chlorophcnol will combine with itself to form a molecule known as 2,3,7,8 telrachlorodiben^.o-p-dioxin (TCDD). This material is extremely toxic.
Analysis of commercial 2,4,5-T formulation t>r dioxin contamination over a 7 year period indicated levels of 0.01 1,9 ppni (1). Tetra and penta-chlorophenols contained >10 ppm of dioxins (4).
Thermal decomposition of wood treated with pentachlorophenol produced no dioxins in the residue. However, dioxins were formed if the sodium pentachlorophenate was used instead of the parent phenol. (6). Dioxins do not occur in the manufacture of 2,4-D herbicides,
BIO-CONCENTRATION-PERSI STANCE
The most toxic dioxin, TCDD has been found to have the following environmental effects,
a. It is not leached vertically from a wide variety of soils, b. Plants have no significant uptake of TCDD when grown in
contaminated soil. c. TCDD has a half life of about 1 year. d. TCDD is not translocated from a point of application on a
leaf surface to other plants parts. c. TCD is less persistent than most chlorinated hydrocarbon
insecticides but is more persistent than 2,4,5,-T. TCDD at 1 ppm in soil is 10^ greater than the amount that would be found in soil receiving 2,24kg/ha of 2,4,5,-T with a contamination level of ,1 ppm TCDD (1). f. Dioxins are not biosynIhcsizcd by condensation of chlorophcntols in soils, nor ate they piiotoproducts of 2,4-d ichlorophcnol. g. PhotoduoomposiLion is insignificant on dry soil surfaces.
HONS 211775
JjxLracts of 19 bald eagles Trom locations in the United States were examined lor dioxin residues. No dioxins were detected at a level of <50 ppb, (4)
Analysis of fish taken in Viet Nam which was subjected to 2,4,5-T applications indicated levels of TCDD ranging from 0. 07.- 0.81 ppb. (5).
TOXICITY
Studies on the toxicities of chlorodibenzo-dioxins have resulted in the following conclusions (3).
1. 2,7-dichlorobidenzo-p-dioxm (DCDD) and octachlorodibenzo-pdioxin (OCDD) have low acute toxicity. No deaths occitred in rats given oral doses of lg/kg.
2. 2,3,7,8-telrachlorodibenzo-p-dioxin (TCDD) has an unusually high toxicity, LD^q ranged from 0.6 ug/kg for male guinea pigs to 115 ug/kg for rabbits.
Death following treatment with a single dose of 2,3,7,8-TCDD is often delayed for several weeks.
3. llexachlorodibenzo-p-dioxin (IICDD) is highly toxic, but less toxic than TCDD. The lethal dosage ranges from mg/kg for HCDD to ug/kg for TCDD.
4. All chlorodibenzo-dioxins are not alike in their toxicological properties. Isomers of the same dioxin vary in toxicological properties, making it important to identify them specifically. 2,3,7,8-TCDD is high embryoloxic and a potent acnegen. 1,2,3,4-TCDD is neither embryotoxic nor acnegemc.
5. 2,3,7,8-TCDD and IICDD were feund to bo acnogemo, highly
embryotoxic, caused liver necrosis, and were positive for
chick edema factor.
MOMS 211776
-12
t
G. 2,7-DCDD and OCDD weic not chloroacneGmc, and caused
neither tetratogemcity or cmbryotoxicity at doses of
100 mg/kg/day. They were both low in acute oral lethality
lg/kg for mice. OCDD was negative for the cluck edema factor.
7. TCDD at dosage levels of 00 ug/kg body weight regularly produced lethal liver necrosis in rabbits (4).
8. 2,3,7,8-TCDD was found to be teratogenic in laboratory animals causing such fetal detects as lack of heads and eyes, cystic kidneys, cleft palates and abnormal livers. (7).
9. 2,3,7,6 has been found to be mutagenic to certain bacterial systems caused by its intercalation with DMA (6).
HEFEKENCES
.1 Kearney', P.C.
2. Kearney, P. 3. Schwartz , B.A. 4. Welling, C. 5. Baughman
.6 Langer, M. G.
7. Gnbbie, G. Vf. S. Hussain, S.
Chlorodioxins - Origin and FateChpt. II Weeds today Fall, 1975. Chlorodioxins - Origin and Fate, Chpt. 7 J. Env. Qual. (1973) Vo . 2. No. 2 Env. Health Perspectives 1973 No. 5 Chlorodioxins - Origin and Fate Chpt. 4. Chemistry, 47 (2), Pg. 15-19, 3974 Ambio 1^ (1) pg. 32-33, 1972.
HONS 211777
APPENDIX 13. THE TOXICOLOGY AND ENVIRONMENTAL BEHAVIOUR
OF POLVCHLOnINATI'D DIUENZOFURANS
HOMS 211778
POLYCHf.ORlMATKD niUKNZOl'UltAPS
Polychlorinated tlibeirz-ofurarib (PCDP) have the general formula:
Dibenzofurans are a byproduct in the manufacture of PCB's; in particular the formation of 245 2'4'5' hexachlorobipheny1 (4). They are also found, along with chlorodioxins, in commercial preparations of pcntachlorophenol (3) and Hexachloiobenzene (14). PCDF concentrations in PCB's have also been shown to increase when the PCB's are heated in the presence of oxygen (5).
Photodocomposition of the lower (di, tri and tetra chloro) PCB isorners have also been shown to produce dibenzof urans, which themselves then undergo photo decomposition with half lives of days to months depending on the degree of chlorination (S).
The levels of chlorodibenzofurans in PCB fluids, after prolonged use, has also been shown to increase markedly under certain conditions.
Toxicology:
Polychlorinated dibenzofurans are known to be highly toxic substances, Chick embryo bioassays have demonstrated that the ability of 2,3,7,8, tetrachloro- and 2,3,4,7,8 peutcchloro dibenzofurnns to affect induction of aryl hydrocarbon hydroxylase is comparable to that of 2378 tetrachloro dibcitzodioxin (TCDD) (7). The latter compound is known for its high acute toxicity and strong teratogenicity and mutagenicity (10,11).
MONS 211779
-lb
A single oral dose of 0,5 - 1.0 mg/kg of a PCDP was found to be lethal to rabbits (1).
As noted earlier dibenzofuraus have been detected as impurities in various formulations containing PCB, and have been shown to be produced as trace byproducts in the manufacture of PCB's (1).
They were shown to be present m the Japanese PCB product Kaueclor 400 (KnegaCuchi Chemical Co.) v.liich has been identified as the causative agent for the outbreak of "Yuslio" or rice oil poisoning in 196S in Japan (2), The ingestion of KCdOO contaminated rice oil (average of 2 gms KC400 ingested per Yuslio patient) caused "Yuslio" disease characterized by follicular accentuation, acneform eruptions, aniland skin pigmentation and hypersecretion of the Mciltonian gland. An abnormal incidence of stillborn babies or birth defects (including cleft palates, nail and skin pigmentation and swelling of eyelids) was also reported for mothers who had ingested the contaminated rice oil.
The majority of these "Yuslio" effects have* now been ascribed to the chlorinated dibenzofurnns present m the KC400 (8r9).
Levels of PCDF's in a sample of now KC400 were reported to be in range of 20 ppm, ivhjle the actual used KC400 product in the "Y'usho" incident had levels in excess of 1. l^o PCDF, due to excessive use and heating in the "closed" PCB system. This would indicate individual total human exposure levels lor Yuslio patients of approximately 20 mg of PCDF (5).
HONS 2U780
- ]G -
I.nvironmental Behaviour ft Occurrence
Doth the chlorinaLect dibenxofurans- and dibenzod lomns arc unstable to light m the presence of organic subsLrates (G). Even if these compounds were generated under envn onmental conditions, light provides a mechanism for their rapid destruction. Thus far, PCDF's have not been detected (at levels oT 0.01 ug/gm or less) in such environmental samples as the muscle of white shark, og;s of double crested cormoranLs and Herring gulls, muscle of eel and chain pickerel and in commercial samples of herring oil and groundfish - herring fish meal (15).
He form c.es
,
1. Vos ct al, Fd. Cosrnet. Toxic, 8, 625-33, 1970, 2. Roach et al, Dull, Env, Cont. Ton, _12, (3) 338-42, 1974, 3. Plummer, J. Agr. Food Chein, 2^, 90, 1973, 4. Moron et al , Acta Chciu, Scandia. 27, 3121, 1973. 5. Morita, ct al, Bull, Env. Cont. Toxic. _18 (1), 1977, 6. Crosby, D. G. , Bull. Env, Cont. Toxic. _10 (G), 1973. 7. Kende, Agr, Food Chcm., 23, (G) 1222, 1975, 8. Kimbrough, Arch. Env. health, 25, 125, 1972, 9. Panel on Hazardous Trace Substances, Env, Res. 5, 249, 1972, 10. Siler, J. P., Kxperimentia 29, (5) G22-23, 1973. 11. Hussain, S., Ambio, 1 (1) 32-33, 1972, 12. Sparschu, G. L. , Toxicol, Appl, Pharaincol, 1_7, (1) 317-8, 1974, 13. Villanueva. E.C., J, Agr. Food Chcm. 22 (5) 91G-17, J974. 14. Zitko, V. Dull, Env, Cont. Tox. 7 (2/3) 105-10, 1972.
HONS 211761
17 APPENDIX C, ANALYSIS OF MATERIALS PROM THE ADELAIDE STREET TRANSFORMED FIRE FOR THE PRESENCE OF POTENTIALLY HAZARDOUS BYPRODUCTS FORMED FRO.'.l POPS
MONS 211762
In irofluction
The recognition of the high toxic!Ly and mutagen ici ty of chlorinated dibcnzofurans (TCDI's) and dibcnzodioxins (PCDDs) lias led to the public<ition of many articles on the determination of these substances in environmental samples and commercial preparations of pesticides. The technique most widely used for this analysis is combined tins chromatography/inass spectrometry (CC/JIS). The major problem in the analysis of these compounds in environmental samples at trace levels is the sample matrix, which may contain many substances that can interfere in usual methods of analysis. Only GC/MS has the high sensitivity and selectivity required for such determinations.
In this particular problem, we have a sample of sooL, formed during the combustion of transformer materials, which contains in addition to carbon, a large amount of PCBs (Arochlor 12G0) and organic combustion products,
Tho experiment described below attempted to determine ii there are any detectable traces of PCDFs and PCDDs in the soot sample and in samples of tho original transformer oil and pure PCB preparations. Several studies have already been published on the determination of PCDFs and PCDDs in the presence of PCBs (1-6). The procedure for sample clean-up described below is a slight modification of the method of Roach (1), as suggested by Hutzmger et al (2).
A sample of soot from tho GO Adelaide St. fire (400 mg wcL, 106 mg dried) was extracted with 50 ml benzene in a Soxhlct extractor for four hours. The benzene was evapoiatod from this cxtracL to give a yellow oil.
HONS 211783
- 19 -
Tin:, was then dissolved in 1 m3 o f hexane prjoi' to column chromatography. Samples ol transJormer otl (90 my) and Arochlor 12G0 standard (4 mg) wore sunpl> weighed and dissolved ill 1 ini oi hexane.
The chromatographic procedure used lor cample clean-up is indicated in Figure 1. Samples were applied to a Flonsil column (250 mm x 7,5 inm ID, previously washed with 100 ml hexane) and then eluted in three fractions: (1) 100 ml hexane, (2) 50 ml 5% ethcr/hexane; and (3) 50 ml 23*i ether/hexane. Fraction 2 was evaporated and dissolved m 1 ml of 2% ClAf_CCl*,,/-hcxane. This solution was applied to a micro-column of activated basic alumina fSO mi x 4 mm I.D., previously washed with 20 ml 2'ic CIIQC1,/hexane) and eluted into two fractions: (4) 10 ml 2% CHgClg/hexane; and (5) 10 ml GOii/CH^C^/hexane According to the literature, Fraction 5 should contain any PCDFs and PCDDs present in the samples. A blank was also run through all stages of sample clean-up,
Gas chromatography was performed on a Tracor GC with an
electron capture detector (ECD) and a 1% Doxil 300 column (6 ft,
x 2 mm ID.) operated at 200 isothermal. GC/MS was performed
with a Hewlett-Packard 5992A instrument using a short 3% OV-101
column (2 ft x 2 mm ID), The temperatures were as follows:
injector - 250; jet interface - 250; ion source - 150; and
column oven - 120 for 2 min., then programmed 10/min to 250,
The mass spectrometer was operated in either the full spectrum
scanning mode or with selected ion monitoring (SIM). Table 1
lists the ions characteristic of PCDFs and PCDDs that were
monitored in the SIM mode. Confirmation of a species involved
observation of each ion in the molecular ion cluster of a
compound, along with the correct relative abundance. Estimation
of concentrations of various species with the SIM mode was
performed by calibrating the instrument response with compounds
ot similar structure (individual chlorinated biphenyls). Tins
provides only ail approximate quantitation; accurate determinations
require pure standards.
MONS 2117*4
F1CUIW 1.
scipwr Fon tsotatton of rcnr5 and rcma FHOM G.MTLSS AND CONTAMIMTINS FCBs
(PCBs)
(P0DF=+PCDDs)
\ GG + CC/nG
HONS 211785
tabu; ]. SKLL'CTbD IONS MONITORED FOR THE DETECTION' OI' CHLORINATED DIDLL7.Q1TJHANS AND DIDEUEODIOviNS
CcmpcuJKl a
ci2-f Cl3'F
<V* ci5-r CJ6--F
cx7-f C13-
ci4-d
Clfh-D
Ions Monitored- m/g (AsST^.n.-icnt) % HI Espoctcd
1 tt 2
it 3
23C(M)100. 23S(M+2)68 270(M)100 272(H+2)9S 30G(M4-2)100 30i(.M)77 340(*r*-2)100 338(H)61 374(M+2)1G0 372(M)51 408(114-2)100 406(M)44 28G(M)100 2B8(M*-2)93 322(Mi-2)100 320(M)76 356(1.142)100 35-1 (M) 61
240(MM)11 274(M+4)32 30S(M+4)49 342(M+4)65 37G(MM)82 410(MM)93 290(MM)33 324(MM) 49 358(M+4)66
^ ** dibenzofuran; D = dibenzotlio.'d.n
HONS 211786
- 22
Analysis of Fraction 5 of the soot extract by OC revealed the presence of a number of components sensitive to electron capture detection and with retention times in tho range expected for PCDFs and PCDDx. Figure 2 gives the chromatogram resulting from this GC/EC'D analysis. Assignment of peak identities using GC only requires the use of authentic standards, which were not available at the time.
GC/MS analysis in the full spectrum scanning mode provided a great deal more information on the sample compositions. Figure 3 illustrates the total abundance chromatogram of Fraction 5, MOst of the peaks were determined to be polynuclear aromatic hydrocarbon (PAIIs) by interpretation of spectra. It appears that the clean-up procedure was not selective enough to remove these substances. This is unfortunate because the spectra of the PAIIs, which arc in high concentrations, mask the spectra of any other components present. However, one peak with a retention time of 9.9 min, was well separated and gave the spectrum shown in Fig. 4. A search of the literature gave an almost perfect match with the spectrum of totrachlorodibenzofuran illustrated in Figui e 5. This is considered a positive identification.
Determination of the presence of other PCDFs and PCDDs by the full scanning mode is not possible at present and must await installation of a higher resolution capillary column and
improved clean-up procedure.
In order to avoid interference from the PAIIs and to provide an est innate of concentrations, the more selective and sensitive SIM mode of the GC/mS was used for detection. Table 2 lists a number of dibennofuraus tentalivel> identified by
HONS 211767
A
ii i i i i i m f
26 24 22 20 13 16 14 12 10 8
i 6
ii 42
r
Figure* 2. CC-ECD chromatogram of Fraction 5 of the aoot extract.
HONS 2)1788
l to
fT
5
~T
10
1----------- r Minutes
T
Figure 3. CC/llS total abundance chromatogram of Fraction 5 of the scot extract, The soak narked
with an arrov gave the spectrum Illustrated in Figure
HONS 211789
R elative In te n s ity %
I EJ3 G3 -a na 2a
Figure U. Hass spectrun of GC peak at 9*9 nin.
t30i M.
si 1 1 1 1 i &b 1
17 t tst
udL L_J
` 1 ' I g1 1 1 '
|3oa
2*i-l r+J j
200 IV/
ici
h _L_ L:
!i.
1 1 1 1 cc1 1 1 1 .iaa1 ` 1 13Jb
FlPTJrs 5. Mass spectrum of tetrachlorodibenzofuran from the literature (5).
H(
;-/!
HONS 211790
-2G TAPED 2.
ciidori kited nincNXorcR \.\s identified hy gc/ms ato tulip estimated concentrations in diffj'i:];.nt samples
Hot ention Yu ie (min , )
Ten t ative.
Identity ,l
Estimated Concern trations ( ppm)
Wet Soot S.uipie Transfonwr Oi l Amohlor ]?60 St ci.
G. 3 8.3
0. 9
1] .1
11.6
12. 8 13.1 13. 1
Cl'2-F
CVF C1<1-rb
cl3-f C1d-F ci4-f Cl^F Cl6-F
0.02-0.2 0.2-1.6 0.5-4.7 0.1-0.9
0.4-3.7
0. 1-1.2
0.03-0.3 0.01-0.05
N.D. KJ),
0.01-0.1
N.D. N.D. N.D. ' N.D. N.D.
N.D. N.D. N.D. N.D. N.D. N.D. N.D. N.D.
Estimate of Total PCDF in sample = 1-13 ppm
Concentration of PCB in sample
= 1%
0.01-0.1 ppm N.D.
50%
1007c
Estimate of Total PCDF per PCB present
100-1300 ppm 0.02-0.2 ppm
N.D.
(median - 600 ppm) (median == 0.1 ppm)
N.D, = not detected a F = dibenzof itrau ^ = Positive confirmation on the basis of a full mass spectrum.
MONS 211791
monitoring the selected ion;, gi veil J n Table L. hutluM t. on J 11 m.i L mu
of the
I i ti es of tin go compounds-- the di-, tn-, ,irul tetrn-
chJorod ibenaolurans (ref. times- G.3, 8.3, and 0.9 min . )-- w,r;
afforded by matching thoir retention tin.es with t hose of compounds
foiMdtl by chlorination of dibcn<;of uran , and as mentioned above,
the tetrachlorodibenzofiiran was also positively identified by the
full spectrum m Figure 4, Positive confirmations of other
compounds require the analysis of standards. These have been
ordered, but it should be noted that these cannot be studied until
adequate handling facilities are made available.
The presence of chlorodibenzodioxins has not been established as yet. Considerable interference from other materials m the sample was experienced in the SIM experiments. Signals were observed for various selected ions monitored, but relative abundance did not agree well with those expected for dioxins, Tnus, the determination of chlorodibenr.odioxins must await the acquisition of pure standards, the installation of a higher resolution column, and better cleanup procedures..
Tabic 2 also gives an estimation of concentration of compounds tentatively identified in the different samples analyzed. The results are expressed as a range of values, since it was not possible to determine concentrations accurately without pure standards.
The most important point to note is the relative amounts of
PCDFs in the soot sample versus the transformer oil and a
standard of unused PCB (Arochlor 12G0). No traces were detected
in tite PCB standard, while only a small concentration (0,1 ppm
maximum) of a tctrachlorodibenzofuran was observed in the used
transformer oil. The soot sample, on the other hand, was found
to contain a total concentration of PCDFs in the range of 1 to 13
ppm. Based on the amount of PCB m the samples (l^o in the wet soot;
in Lhc transformer oil), this represents up to a G00t)-fold
dificrcnce in concentrations. This indicates that the oxygenated
products v.oro formed during the fire and did not originate directly
from Lhc transformer oil.
HONS 211792
A number of oxygenated products of PCBs have been oboewed in the soot sample at far higher concentrations than in the transformer oil prior to the fire. One compound was positively identified: tetraehlurodibcnzofuran. Di-, triT, penta-, and hcxa-chlorodibenzofuran were tentatively identified. There is no evidence as yet for the presence of chlorinated dibenzodioxins. Determination of the latter compounds must await acquisition of authentic standards, the installation of a high resolution capillary column in the GC/MS, and the develop ment of beLter clean-up procedures.
He ferenccs
1. J. A. G. Roach and I. V/, Pomerantz, Bull. Environ. Con tarn. Tox. 12, 338 (1974).
2. 0. Hutzinger et. al,, "The Chemistry of PCBs", CRC Press, 1974.
3. J. Nagayama et. al. , Bull. Environ. Contani. Tox. JL5, 9 (197G).
4. G. XI. Bowes, et. al. , Nature 256, 305 (1975).
5. D. Firestone, ct. al. J.A.O.A.C. 55, 85 (1972).
6. M. Morita, et. al. , Bull. Environ. Contam. Tox. JL8, 67 (1977).
MQNS 211793