Document wqEq2Kp71Ja58mEZK5yZGMMXV

554 CHAPTER 37 1960 Guide Heating Value af Gcu Btu per Cu Ft 500 535 800 1000 Table 4 .... Unit Fuel Consumption Constants (U) for Gas* Bated on 0 F Outdoor Temperature, 70 F Indoor Temperature Hal Water Sleao Word Air Cu Ft Go* per Degree Doy per Sq Ft EDS Co Ft Go* per Degree Day per Sq Ft EDS Cu Ft Gas per Degree Day per 1000 Btu Hourly Design Heat Low Up to 500 Sq Ft 0.149 0.139 0.094 0.075 500 to 1200 Sq Ft 0.142 0.132 0.087 0.071 Over 1200 Sq Ft 0.134 0.126 0.085 0.068 Up to 300 SqFt 0.254 0.237 0.159 0.127 300 to 700 Sq Ft 0.242 0.226 0.151 0.121 Over 700 SqFt 0.231 0.216 0.144 0.116 0.896 0.840 0.660 0.449 Fan Systems. 0.861 0.805 0.538 Gas Consumption in Therms per Degree Day I Therm - 100,000 Btu 0.000743 0.000709 0.000675 0.00127 0.00121 0.00116 0.00450 boat Comfort Haadne, American Gaa Association, 18SS, and 6 percent added far operation without night reduction of temperature. 0.00430 volume of a given building than to measure and evaluate the hgating capacity of its heating system, or calculate its maximum hourly Btu loss. The comparison of buildings on a straight volume basis does not allow for variation in expo sure, type of construction, ratio of exposed area to cubical contents, and type of occupancy. It is inaccurate for estimat ing purposes unless the buildings are of very similar nature. The calculated heat loss or the heating capacity of the in stalled radiation may be used as the unit. The use of the heat ing capacity of the installed radiation is of questionable value when referring to heat-transfer surfaces used in warm air furnace or central air-conditioning systems. Where steam or hot water radiation is already installed,- care should be exercised when using the installed radiation as the basis for estimating, since actual installed radiation may differ con siderably from the exact radiation requirements. In view of all these considerations, it is believed that the unit based on thousands of Btu of hourly calculated heat loss for the design hour is probably the most desirable. Estimating Gas Consumption Values of the Unit Fuel Consumption Constant U for gas are given in Table 4 for various gas heating values, and dif ferent types and sizes of heating systems. They are based on an indoor design temperature of 70 F and an outdoor design temperature of 0 F, and apply only to these conditions. For other outdoor design conditions corrections must be made by applying factors given in Table 3. The factors in Table 4, as corrected if necessary, are satis factory for regions having 3500 to 6500 degree days per heat ing season. In regions with less than 3500 degree'days the unit gas consumption is higher than given; where over 6500, the unit is less than given. Ten percent addition or deduction in these cases is recommended by A.GA. publications. This table cannot be used for making estimates for industrial buildings where low inside temperatures are maintained. For gas heat values other than those given in Table 4, simply interpolate or extrapolate. It will also be noted that Table 4 applies only to small installations. Since the unit gas consumption becomes smaller as the installation becomes larger, the values in the table should be used with care, if at all, for large gas-burning installations. Example 4- Estimate the gas required to heat a building located m Chicago, 111., where the heating season has 6310 de gree days and the gas heating value is 800 Btu per cu ft. The calculated heating requirements are 1000 sq ft of hot water radiation based on design temperature of --10 F and 70 F. Solution; From Table 4, the fuel consumption for a design temperature of 0 F with 800 Btu gas is found to be 0087 cu ft of gas per (degree day) (square foot of hot water radiation). Table 5 .... Unit Fuel Consumption* Constants (U) for Oilb Bated oo Of Outride Temperature, 70 F Inside Temperature Unit* Efficiency in Percent 70 80 Gal oil per sq ft steam radiator............. 0.00105 Gal oil per sq ft hot water radiator.... 0.00066 0.00437 0.00092 0.00058 0.00383 * Bsned oo * heating value af 141,000 Btu per gellas. b Abstracted by permintoa from Ocgrte-Doy Handbook (8eeoad Edition, 1037), by C. 8troek and C. H. B. Hotrtikaa. Seven percent added for operation without night reduction of temperature and change to value of 141,000 Btu per gallon. * Per degree day. Table 6 .... Unit Fuel Consumption* Constants ((/) for CoaP* Bated on 0 F Outdoor Temperature, 70 F Inode Temperature Unit* Efficiency in Percent 40 50 60 70 80 Lb coal per Bq ft steam radiator..................... 0-0216 0.0172 0.0143 0.0123 0.0108 Lb coal per sq ft hot water radiator.......... 0.0135 0.0108 0.0091 0.0078 0.0068 Lb coal per 1000 Btuh heat loss......... 0.0889 0.0717 0.0592 0.0507 0.0444 * Baaed on a *--vaJoe trf 13,000 Btn per poenri. b Abstracted by perminkm from Dtfrto-Dar Handbook (Second Edition, 1837), by C. Strock and C. H. B. Hotchkiss. Eight percent added far operation without night redaction of temperature. * Per degree day. Estimating Fuel Consumption for Space Heating 555 From Table 3, the correction factor is 0875 for --10 F outdoor design temperature, bence, 0875 X 0087 -- 0076. By Equation 4, F - 0076 X 1000 X 6310 - 480,000 cu ft- Estimating Oil Consumption Table 5 gives unit fuel consumption factors for oil, similar to those given for gas in Table 4. The factors in Table 5 apply only to an indoor design tem perature of 70 F and an outdoor design temperature of 0 F. For other outdoor design temperatures, the constants in Table 5 must be multiplied by the values in Table 3 as ex plained under Estimating Gas Consumption. Values given in Table 5 are based on use of oil with a heat ing value of 141,000 Btu per gallon. For other heating values, multiply the values in Table 5 by the ratio of 141,000 divided by the heating value per gallon of fuel being used. Example 5: Estimate the seasonal oil consumption of a boiler, designed for oil firing, in a building located in Toledo, Ohio. The building has a calculated heat loss of 240,000 Btu per hr. The oil heat value is 144/100 Btu per pi, and the as sumed seasonal efficiency is 80 percent. The outdoor design tem perature for Toledo is --10 F, and the indoor design temperature is 70 F. Solution: From Table 5, under SO percent efficiency and in the bottom line, the value of U is found to be 080383 gal per 1000 Btu hourly beat loss for 0 F outdoor temperature. The correction factor for --10 F outdoor design temperature from Table 3 is 0875 which makes the correction 0875 X 080383 -- 080335. Making a further correction for the heating value, 080335 X (141,000/144,000) = 0.00328 gal per 1000 Btu per hr calculated heat loss per degree day. From Table 2, the total normal degree days for Toledo are 6394. Since U is expressed in 1000 Btu, N is equal to 240. Sub stituting in Equation 4 is 6047, so that during these three months the estimated consumption is 5JJ5 X 56,500 - 27,000 lb. Estimating Steam Consumption In estimating steam consumption the efficiency is generally assumed at 100 percent. If for low-pressure steam an average heating value of 1000 Btu per pound of steam is used, no correction is necessary. In comparing values from different cities, correction should be made for design temperature (see Table 3) when the unit figures are in terms of heat Ipf-w but not when the values are in terms of building volume or floor space. Where the heat loss is calculated in Btu per (hour) (de gree difference in temperature) the ample Equation 7 may be used: B X 24 X D 1000 (7) P b pounds of steam required for estimate period. H = calculated heat loss, Btu per (hour) (degree differ ence). 24 " hours in one day. D -- number of degree days for the period of estimation. 1000 = Btu delivered per pound of steam condensed. In this method the number of degree days automatically takes care of average indoor and outdoor temperature dif ference. When degree days are taken from Table 2, an av- P = 080328 X 6394 X 240 - 5030 gal Estimating Coal or Coke Consumption Coal or coke consumption estimates are made by following exactly the same procedure as for oil. Values of U are given in Table 6 which only apply to an indoor design temperature of 70 F and an outdoor design temperature of 0 F. A correc tion must be made for other conditions by use of the mul tiplying factors in Table 3. Data in Table 6 are based on 12,000 Btu per lb coal, and forother heating values of coal they must be multiplied by the ratio of 12,000 divided by the heating value of fuel used. Example 6: A building in Scranton, Pa. has a calculated heat loss of 240,000 Btu per hr based on an indoor design temperature of 70 F and an outdoor design temperature of --10 F. What will be the estimated normal seasonal anthracite or coke consump tion for heating if 13,000 Btu per lb fuel is burned in a handfired boiler, with automatic control, at a m-mom) efficiency of 80 percent, and what part of the total will be used during November, December, and January? SolxUion: From Table 6, U is 08444 of coal or coke per 1000 Btu per hr heat loss per degree day. Correcting for the out door design temperature of --10 F from Table 3, the value of V is 0875 X 08444 - 08389. From Table 2, D is 6218 and from the problem, N is 240. Substituting in Equation 4, F = 08389 X 240 X 6047 = 56,500 lb. Fuel used over any period is, according to the theory of the degree day, proportional to the number of degree days during the period. Froni Table 2, the average numbers of degree days for November, December, and January in Scranton are 693, 1057, and II4I respectively, a total of 2891. The yearly total Table 7 .... Steam Consumption of Buildings with Various Types of Occupancy* Type of Budding No. Bldgs Volume Hoofed 1000 Ci Ft Steam for Heating age to per OO per of 1000 Occu Co Ft pancy Office.............................................. Office and Bank........................... Office and Printing..................... Office and Theater...................... Office and Stores or Shops........ 334 49 8 7 26 Bank............................................ Department Store....................... Stores............................................. Loft................................................ Warehouse.................................... 16 63 73 63 24 Hotel and Club............................ Apartment or Residence........... Theater................................... Garage..................................... Manufacturing............................. 73 61 22 13 19 Church...................... Hospital......................................... School...................................... Municipal or Federal................. Lodge, Gym, Hall, or Audito rium........................................... Miscellaneous............................... 9 4 8 15 12 7 2160 3000 1895 4950 1615 0.685 0.577 1.230 0.412 0.617 12.1 13.1 17.7 12.9 13.2 806 3400 310 865 2230 0.786 0.385 0.624 0.588 0.459 11.7 11.1 10.4 10.0 9.4 1795 1425 1240 1540 1350 0.990 0.962 0.482 0.202 0.808 22.3 21.8 12.9 21.4 9.5 656 3306 1115 3215 0.532 1.194 0.592 .0.587 7.9 22.0 11.5 15.6 880 0.390 12.4 1387 0.479 21.4 * PrineipUt af Economical Heatin$, National Association at Building Owner* tod Manager*.