' CHAPTER 32
1946 Guide
applied to systems having characteristic curves A, B and C, will deliver . 10,000, 13,000 or 16,400 cfm respectively.
-The curves in Fig. 4 also illustrate the effect of errors which may be made in calculating the resistance of a ventilating system. For instance, if a given system requires 13,000 cfm and the resistance to flow of the system has been computed as 1.25 in. static pressure, such a system would be represented by system characteristic curve B in Fig. 4. If a 100 per cent error had been made and the resistance were 2.5 in. instead of 1.25 in., then the system characteristic would be as shown in curve A and would cross the fan curve at 10,000 cfm. Such an error would cause the flow of air to be decreased from a design volume of 13,000 cfm to 10,000 cfm. If the resistance to flow had been over estimated and
Fig. 4. Parabolic System Characteristic Curves
the resistance actually were ,0.625 in., the system characteristic curve would be as shown in curve C and the fan would deliver 16,400 cfm to the system instead of the design volume of 13,000 cfm.
In this example extreme errors have been selected to emphasize the' effect the square function of the system characteristic has in maintaining the fan performance within comparatively narrow limits. In , the first . example a system estimated at half what it should have been, resulted in a drop of 23 per cent in volume; and in the second example; a system . estimated at twice what it should have been resulted in an increase of 26 per cent in volume.
In . some, instances fans may be applied to variable flow systems. In such cases' the limiting systems may be plotted and the effect on fan ' . performance examined. For instance, a system might have a'character istic curve between A, shown in Fig. 4, as one limit, and B as the other limit. The fan performance will then fall between points X and Y on the fan curve at a point determined by the system characteristics at that
Fans
575 '
particular time. If A and B are the limiting characteristic curves of the systems, the fan performance will never .be .outside the points X or Y.
SELECTION OF FANS
The following information is required to select the proper type of fan:
1. Cubic feet of air per minute to be moved. 2. Static pressure required to move the air through the system. 3. Type of motive power available. 4. Whether fans are to operate singly or in parallel on any one duct. 5. What degree of noise is permissible. 6. Nature of the load, such as variable air quantities or pressures.
; f
;
In order to facilitate the choice of apparatus, the various fan manu. facturers supply, fan tables or curves which usually show the following
factors for each size of fan operating against a wide range of static pressures: (1) volume'of air in cubic feet per minute (68 F, 50 per cent .' relative humidity, 0.075 lb per cubic foot), (2) outlet velocity, (3) revo lutions per minute, (4) brake horsepower, (5) tip or peripheral speed, and (6) static pressure.' The most efficient operating point of the fan is " usually shown by either bold-face or italicized figures in the capacity '
tables.
Other important factors to be considered in selecting fans are: (1)
efficiency, (2) space occupied, (3) sound emission, (4)'first cost, and (5) speed (both peripheral and revolutions per minute). These factors
are not necessarily shown in the order of importance. In some installations space occupied may be' of first importance. In others lowest power consumption is desirable. In many cases quietness of operation
of the entire system is essential. Practically all fans operate at their lowest sound level when selected at or near the peak of the static efficiency , so that in selecting a fan for highest static efficiency the quietest operating
range of the fan will also be obtained. Table 1 shows desirable outlet velocities and tip speeds, or peripheral velocities, for various static ,
pressures. Fans selected accordingly will operate at or near the peak of
,
: ;. >
t
i i
!! '
1
\\. ' .
Table 1. Good Operating Velocities and Tip Speeds for Multiblade Ventilating Fans
Static Pressure'Inches of Water
K %y2 Vs Vi l 7A Wt. l'A lH
2 2M
2y2 3.
Forward Curved Blade Fans
Outlet Velocity `
Feet per Minute
Tip Speed Feet per Minute
1000-1100
1520-1700
1000-1100
1760-1900
1000-1200
1970-2150
1200-1400
2225-2450
1300-1500 . 2480-2700
1400-1700 . 2660-2910.
1500-1800 ; ' 2820-3120
1600-1900
3162-3450
. 1800-2100 1900-2200
3480^3810
. 3760-4205
2000-2400
4000-4500
2200-2600
4250-4740
2300-2600
4475-4970
2500-2800
4900-5365
4Backward Tiffed and Double Curved Blade Fans
Outlet-Velocity
Tip Speed
Feet per Minute ' Feet per Minute
800-1100 . 800-1150 900-1300 1000-1500 1100-1650 1200-1750 1200-1900 1300-2100 1400-2300 1500-2500 1600-2700
1700-2800 1800-2950 2000-3200
2600-3100 . 3000-3500
34004000 38004500 ,4200-5000 4500-5300 4800-5750 5300-6350 5750-6950 .
6200-7550 . 6650-8050
7050-8550,
7450-9000 8200-9850