Document wgzXV12VYB3dK9eqVrgYpz7RJ

American Society of Heating and Ventilating Engineers Guide, 1936 10 What is the coefficient U for a built-up flat roof of 4-in. concrete with a ^ metal lath and plaster ceiling insulated with 1-in. cork board? a^ 0.17 (Table 11. Roof 3N). ' 11 A solid 12-in. common brick wall is finished on the inside with %-ir, i insulation plaster base, and J^-in. plaster; the plaster base is furred 1 in. from' \ the brick; k for insulating material = 0.34. Calculate the over-all coefficient t V. ft f\ = /o k1.65; = 6.00; for brick = 5.00; o for 1-in. air space = 1.1 i' ov,,.,nh,,t-*-T5s + nr + g + n- + f + -f-5.7oj -i-- j 12 A wall is built with two layers of J^-in. insulating material spaced 1 in. ;i apart; the air space is lined on one side with bright aluminum foil; mean temperature is 40 F; still air on both sides of wall; k for insulating materia] is 0.34. Calculate the value of (/. ' ft = 1.65;/0 - 1.65; a = 0.46 _L_ + + _J_ 1.65 ^ 0.34 ^ 0.46 + 0.34 + 1.65 6.327 i;?; V= = 0;l58 a T; 13 What is the inside surface temperature of a 6-in. solid concrete wall? v Inside air, 70 F; outside air, --20 F with 13 mph wind. t, The temperature drop from point to point through a wall is directly proportional to the ) heat resistance. i fi = 1.65; k for concrete = 12;/Q = 6.0 Over-all resistance R = ^ + -L =1.27 1 Temperature drop, inside air to surface = 1.65 Temperature drop, air to air 1.27 qa Temperature drop, inside air to surface = , __ w .= 43 1.27 X 1.65 70 -- 43 = 27 F, inside surface temperature of wall. 14 How many inches of insulating material having a conductivity of 0.30 would be required, for the wall of Question 3, to raise the inside surface tem perature to 60 F? Temperature drop, air to inside surface = 10 F; temperature drop, inside surface to out side air = 80 F. Therefore, the heat resistance from inside wall surface to outside air must be eight times that from inside air to inside wall surface,'or 8 X = 4.85. The .- 1.65 resistance for. added material is, therefore, 485 - (1 + i) =419 4.19 X 0.30 = 1.25 in. of insulation. Chapter 6 air leakage Nature of Air Infiltration, Air Leakage Through Walls, Window Leakage, Wind Velocity to be Selected, Crack usedfor Computa tions Multi-Story Buildings, Heat Equivalent of Air Entering * by Infiltration AIR leakage losses are those resulting from the displacement of heated air in a building by unheated outside air, the interchange taking place through various apertures in the building, such as cracks around doors and windows, fireplaces and chimneys. This leakage of air must be considered in heating and cooling calculations. (See Chapters 7 and 8.) THE NATURE OF AIR FILTRATION The natural movement of air through building construction is due to two causes. One is the pressure exerted by the wind; the other is the difference in density of outside and inside air because of differences in temperature. The wind causes a pressure to be exerted on one or two sides of a building. As a result, air comes into the building on the windward side through cracks or porous construction, and a similar quantity of air leaves on the leeward side through like openings. In general the resis tance to air movement is similar on the windward to that on the leeward side. This causes a building up of pressure within the building and a lesser air leakage than that experienced in single wall tests as determined in the laboratory. It is assumed that actual building leakages owing to this building up of pressure will be 80 per cent of laboratory test values. While there are cases where this is not true, tests in actual buildings substantiate the factor for the general case. Tests on mechanically ventilated classrooms of average construction have shown that air infiltration acts quite independently of the planned air supply. Accor dingly, the heating or cooling load owing to air infiltration from natural causes should be considered in addition to the ventilating load. The air exchange owing to temperature difference, inside to outside, is not appreciable in low buildings. In tall, single story buildings with openings near the ground level and near the ceiling, this loss must .be considered. Also in multi-storied buildings it. is a large item unless the sealing between various floors and rooms is quite perfect. 'This tempera ture effect is a chimney action, causing air to enter through openings at lower levels and to leave at higher levels. 131