Document wgwX2do2OeemYKmjmbQXXrY2d
142
CHAPTER 9
1962 Guide And Data Book
Utod by pormixdoa from hfawo 6.
Fig. 8 .... Direct Contact Heater for Generating High* Temperature Water
into the boiler through a pipe connecting the outlet of the higb-temperature water circulating pump to the boiler. This system is also applicable where both steam and high-tempera ture water services are required.7 Where heat and power pro duction are combined, the direct contact heater becomes the inuring condenser.*
System CrculaHng Pumps
Forced circulation boiler systems may be either of the one-pump or txuo-ptanp type. These terms do not refer to the number of pumps, but to the number of groups of pumps em ployed. In the former (see Fig. 9) a single group of pumps
assures both generator and distribution system circulation. Lq
this system both the distribution system and the generator*
ate in series.'
However, to assure the minimum flow through the boiler
at all times, a bypass around the district must be provided.
This applies generally only to systems in which the total
friction head is relatively low, since the energy loss of available
circulating head due to throttling in the bypass at
^
reduced flow requirements in the district may substantially
increase the operating cost
The two-pump system (see Fig. 10) employs an additional
group of recirculating pumps solely for the purpose of pro.
viding circulation for the generators.* One pump is normally used for each generator to draw water from the expand
drum or the system return and pump it through the generator
into the expansion drum. The system circulating pumps draw
water from the expansion drum and circulate it through the
distribution system only. This system provides full flexibility.
The supply temperature to the distribution system can be
varied by mixing water from the return into the supply on the
pump suction side. Where zoning is required, several groups
of pumps can be employed with a different head and different
temperature in each zone. The flow rate can also be varied
without affecting the generator circulation, and without tire
use of a system bypass.
In steam-pressurized systems the circulating pump is in
stalled in the supply line in order to maintain all parts of the
distributing system at pressures exceeding boiler pressure,
and thus minimize the danger of flashing into steam. Special
care must be exercised in the design of the suction line from the'
expansion drum to the pump in order to avoid flashing in the
line, and to provide the net positive suction head (NPSH)
required by the pump at the inlet to the impeller.
It is common practice to install a mixing connection from
the return to the pump suction which bypasses the high-
temperature water generator. This connection is used for
Fig. 9 .... High-Temperature Water Piping for Combined (One-Pump) System
High-Temperature Water Systems
>aj-tuD and for modulating the supply temperature. This connection should not be relied on for increasing
vpSH at the pump inlet. Where it is impossible to provide therequired submergence by proper design, a separate smallSL oremixing line should be provided.
In selecting a pump, the pumping head and water circuiatkin rate must be carefully evaluated in order to permit selec tion of a proper motor. The effect of density variation bet*en the high and low temperature must be considered. p[unp characteristics, as affected by system characteristics,
gbould be given consideration to assure non-overbading con
ditions in pump motor operation. Most pump applications today are of the vertical, spht-
a3e centerline-mounted type with mechanical seals. Care
must be taken to keep the shaft seal and sleeves clean during tbe initial startup of the system. Many manufacturers recom mend the use of water cooling chambers for both seal and bear ing cooling in HTW applications. Also available today are hermetically sealed pumps which eliminate the shaft sealing
problem by putting the motor into the water circuit.
DISTRIBUTION PIPING DESIGN
Fig. 11. shows the relation of the flow of water in thousands of pounds per hour to the friction loss in feet per 100 ft of
Schedule 40 pipe in sizes from ^ in. to 12 in. Fig. 12 shows a correction curve to be used with Fig. 11 to correct the friction
loss according to the water temperature. For example, with 17,000 lb per hr of water at 400 F flowing through a 2 in., Efrjywhilp 40 pipe, the friction loss is found from Fig. 11 as 2.25
ft per 100 ft. The correction for temperature, from Fig. 12, is
1.185, and the corrected friction loss is 2.25X1.185 = 2.67 ft
per 100 ft of pipe. The arrangement of piping and necessity for zoning will
be determine* by such factors as the hours of operation,
the nature of the space occupancy, and the required water
temperature. These factors, together with the heat require
ments of the equipment served, will establish the tempera
ture drop which, in common practice, may range from 80
to 150 deg. Economic considerations require that the savings due to
use of small pipe and high velocity circulation be balanced
against the cost of valves, pumps, etc., that are suitable for
operation at the high friction loss and pressure. The best
overall investment will be secured when there is a proper
relation between first cost, operating cost (including that
of the operating personnel), and the fired charges.
The conventional conduit or tunnel distribution systems
are employed with
techniques used for installation.
Although the uiftinn) may be run at different elevations at
will, it is important that high points be vented and the low
points drained by the air collection and venting arrangement
described earlier. Grading is not critical. See Chapter 7,
District Heating.
The piping serving each building or process load should
have a valved bypass connection between the supply and
the return pipe in addition to the usual stop valves as indi
cated in Fig. I.
All pipe, valves, and fittings used in high-temperature
systems should comply with the requirements of the Ameri-
caa Standard Code for Pressure Piping, ASA B 31.1--1955.
This code states that hot water systems shall be designed
[or the highest pressure and temperature actually existing
in the piping under normal operation. This pressure is the
cushion pressure plus pump bead plus static pressure. Schedule
*0 steel pipe is applicable to most HTW systems with welded
rteel fittings and steel valves. It is desirable to minimize the
tonnber of joints in the system and many installations are
143
welding or brazing all valves in the piping system. Flange connections generally used at major equipment may be of the serrated, raised flange facing or of the ring joint type. It is desirable to have all valves of the back-seating type and pro vided with special packing suitable for this service.
Individual heating equipment units should preferably be in<rtallpH with a lock-shield valve for balancing the flow and a separate valve for shut-off. These may be placed in the most convenient position for accessibility. If the unit is to be isolated for service, valves will be needed in both the supply and return piping to the unit. Valve trim should be of stainless steel or other alloy that will prevent corrosion.
High points in piping should be provided with chambers and air vents for collecting and removing air and low points should have provision for sludge removal.
Loop-type expansion joints, in which the expansion is ab sorbed by deflection of the pipe loop, are preferable to the packed-metal type. If mechanical expansion joints are used, they should be of the guided type.
As higb-temperature water is more penetrating than lowtemperature water, leakage due partly to capillary action should not be ignored because even a small amount of leak age vaporizes immediately. This slight leakage becomes no ticeable only on the outside of the gland and stem of the valve where thin deposits of salt are left after evaporation.
HEAT EXCHANGERS
Heat exchangers or converters generally use steel shells with stainless steel, admiralty metal, or cupro-nickel tubes. The choice of material needs careful consideration in relation to the pressure-temperature characteristics of the particular system. All connections should either be flanged or welded. On larger exchangers, water-box type construction is de sirable to facilitate removal of the tube bundle without breaking piping connections.
AIR HEATING COILS
In HTW systems over 400 F, it is recommended that coils be of all-steel construction. Below this point other materials may be used after careful checking of their suitability for the temperatures involved. Coils in outdoor air connections need careful freeze-up protection. This may take the form of damper closure or fan shut down from a freeze-up thermostat. It is also possible to set the control valve on the preheat coil to a minimum positron. This may protect against freeze-up as long as no unbalance takes place in the tube circuits where parallel paths of HTW flow exist. Special coil design of a tube-'" within-a-tube construction is available. A further alternative is the use of a HTW heat exchanger,bundle in the base of a vertical tube section which then operates as a gravity steam ing heat exchanger surface.
Pressure gages should be installed in the pump discharge and suction and at locations where pressure readings will assist operation and maintenance. Thermometers (prefer ably dial type) or thermometer wells should be installed in the flow and return pipes, the pump suction and discharge, and at any other points of major temperature change or where temperatures are of importance in operating the sys tem. Thermometers and gages are desirable in the piping at the entrance to each building converter.
SPACE HEATING EQUIPMENT
In industrial areas, space heating equipment may often be operated with high-temperature water due to its avail ability. Convectors and radiators may require water tem peratures in the low and medium temperature range (120 to