Document wg4gqX3zqze84Q32yXEyN9Zro

HEATING VENTILATING AIR CONDITIONING GUIDE 1941 Table 9. Pressure Losses in Dichlorodifluoromethane Suction Refrigerant Lines Copper Pipe Actual O.D. Inches h iH iH m Capacity Btu feb Hour 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 7,000 10,000 15,000 20,000 25,000 35,000 45,000 60,000 70,000 10,000 15,000 20,000 30,000 40,000 50,000 60,000 80,000 100,000 30,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 120,000 140,000 Pressure Drop in Pounds pbb Square Inch feb 100 Ft* FRefrigerant Temperature Deo -10 0.3 1.3 2.8 4.8 7.4 10.5 14.0 0.4 1.0 1.9 3.3 5.0 9.7 15.8 0.3 0.7 1.2 2.6 4.6 7.0 10.0 1.6 2.7 4.2 6.1 8.7 0 0.3 1.0 2.2 3.8 5.8 8.4 11.0 14.5 0.3 0.7 1.5 2.6 4.0 7.7 12.6 0.2 0.5 0.9 2.1 3.6 5.5 7.8 14.0 1.3 2.1 3.2 4.5 6.3 8.4 10 0.2 0.8 1.8 3.1 4.8 6.8 9.1 12.0 15.0 0.3 0.5 1.2 2.1 3.2 6.2 10.0 0.2 0.4 0.7 1.6 2.8 4.4 6.2 11.0 1.0 1.7 2.5 3.6 4.8 6.3 8.0 10.0 20 0.2 0.7 1.5 2.6 3.9 5.6 7.6 9.8 12.3 15.0 0.2 0.5 1.0 1.7 2.7 5.1 8.4 14.8 0.2 0.3 0.6 1.3 2.3 3.5 5.0 8.7 13.5 0.8 1.4 2.1 2.9 3.8 4.9 6.2 7.6 30 0.2 0.6 1.2 2.1 3.3 4.7 6.4 8.3 10.4 12.7 0.2 0.4 0.8 1.4 2.2 4.3 7.0 12.2 0.1 0.3 0.5 1.1 1.9 2.9 4.2 7.3 11.3 0.7 1.1 1.7 2.4 3.1 4.0 4.9 6.1 8.6 40 0.1 0.5 1.0 1.8 2.8 4.0 5.4 7.0 8.7 10.7 0.2 0.3 0.7 1.2 1.9 3.6 5.9 10.2 14.0 0.1 0.2 0.4 0.9 1.6 2.5 3.5 6.2 9.5 0.6 0.9 1.4 2.0 2.6 3.3 4.1 5.0 7.0 9.5 50 0.1 0.4 0.9 1.5 2.3 3.3 4.5 5.8 7.2 8.9 0.1 0.3 0.6 1.0 1.6 3.0 4.9 8.6 11.7 0.1 0.2 0.4 0.8 1.4 2.1 3.0 5.2 8.2 0.5 0.8 1.2 1.7 2.2 2.8 3.5 4.2 5.9 7.9 Length of tubing includes the average number of fittings- 464 CHAPTER 24. REFRIGERATION ------------ - Table 9. Pressure Losses in Dichlorodifluoromethane Suction Refrigerant Lines (Continued) Pbessubb Dbop in Pounds pbb Square Inch pbb 100 Ft* Coppeb Pip Actual O.D. Inches Btu pbb Hour FRefrigerant Temperature Deo 50,000 100,000 150,000 -10 0 10 0.7 0.5 0.4 2.6 1.8 1.4 5.6 3.9 3.0 20 30 0.3 0.3 1.1 0.9 2.4 2.0 40 50 0.2 0.2 0.8 0.7 1.6 1.4 200,000 9.8 6.7 5.2 4.1 3.4 2.8 2.4 V/s 250,000 14.8 10.3 8.0 6.3 5.1 4.2 3.6 300,000 14.5 11.3 9.0 7.2 6.0 5.0 350,000 400,000 19.5 15.3 19.6 12.0 15.3 9.7 12.5 7.8 10.0 6.7 8.5 50,000 100,000 150,000 0.2 0.2 0.1 0.1 0.1 0.1 0.1 0.7 0.6 0.5 0.4 0.3 0.2 0.2 1.6 1.2 1.0 0.8 0.6 0.5 0.4 ' 200,000 2.8 2.1 1.7 1.4 1.1 0.9 0.7 250,000 4.3 3.4 2.6 2.1 1.7 1.3 1.1 300,000 6.1 4.5 3.7 3.0 2.4 1.9 1.5 2H 350,000 8.2 6.0 5.0 4.0 3.2 2.5 2.0 400,000 7.8 6.5 5.1 4.2 3.3 2.7 450,000 7.7 6.4 5.3 4.0 3.5 . 500,000 550,000 .600,000 7.8 6.4 5.0 4.2 7.7 6.2 5.1 . 7.4 6.2 200,000 300,000 ' 400,000 1.2 1.0 0.8 0.6 0.5 0.4 0.4 2.6 2.0 1.6 1.3 1.0 0.8 0.7 4.5 3.4 . 2.6. 2.1 1.7 . 1-4 1.3 500,000 7.3 5.4 4.1 3.3 2.7 2.2 1.9 3 'A 600,000 8.1 6.0 4.7 3.8 3.1 2.7 700,000 8.4 6.5 5.2 4.2 3.5 800,000 900,000 1,000,000 8.6 6.8 5.5 4.6 8.7 7.0 5.9 8.9 7.3 300,000 400,000 500,000 1.2 0.9 0.7 0.6 0.5 0.4 0.3 2.0 1.6 1.3 1.0 0.8 0.7 0.6 3.2 2.5 1.9 1.6 1.3 1.0 0.9 600,000 4.6 3.6 2.8 2.2 1.8 1.5 1.3 700,000 6.4 4.9 3.8 3.0 2.5 2.0 1.7 800,000 8.7 6.4 4.9 3.9 3.2 2,5 2.2 3H 900,000 8.2 ' 6.2 4.9 3.9 3.2 2:7 1,000,000 7.7 6.1 4.9 4.0 3.3 1,100,000 9.4 7.3 5.8 4.8 4.0 1,200.000 1,300,000 1,400,000 8.7 --- 6.9 8.0 9.3 5.6 . 4.8 6.6 . 5.6 7.6 6.4 Length of tubing includes the average number of fittings. . 465