574 CHAPTER 31 1965 Guide And Data Book By use of Equation 3, the d term may be eHminnteri and the pressure loss expressed in terms of length, volumej and velocity. '.. ..t - ,,'"39X10"'.*"(^:)' "`V US) . As defined above, the static regain method requires that the increase in static pressure at the takeoff junction be equal to Uie pressure kiss.in the succeeding section of the run..Therefore:-f . ` 3.9 X ( m,' (16) In any given design, the yalue of Vl Q,, and L-are.known and tiie equation may be solved for V,. This, in tun^, permits calculation of dj By use of. Equation 3. ' ..... 1 . Equation 16 may be solved graphically by use of F1g&13 and 14. Fig. 13 is used to find. .the valueLof L/Qi*- and this value is then used as one of the given values in Fig. 14. Fig. 14 is a plot of two superimposed families of curves. One family of curves is a plot of Vt vs friction drop for various values of L/QttM, while the other is a plot of Vt vs!stktic regain for various values of V,. Thus, the friction loss may be equated to the static regain and a point ofTioToM^-no ^iRn determined. This point occurs at the intersection of the Vi curves and' the L/Qtta curves for the particular problem. To the left of this point, the distance between' tHfe. two. curves represents a net gain in static pressure: .To the'tight of this point, the distance between the curves represents a net static pressure, loss. See Guide'to Use sketch in Fig. 14. This feature will be found useful when a net loss must be added to one branch of a'system in order to balance the static pressure values at outlets on other branches of the duct eystefa. '; Example-- 7:- (Static-Regain Method). The duct ahown.in Kg. 15 handles 8000 cfm. Determine the duct.sizes' in.Section. A, B, C, D, E, F, and G, mftintftiniwg an operating pressure ` of 0.12 UL'water in the duct behind each outlet.-Kna the total pressure loea of the system. . . - - - ,:-ti .. .-oii Solution: The following nine steps indicate the solution: ' ' 1. Assume the velocity in' 8ection A to be 1500 fprdl This results in an initial duct size of 48 X 16 in. The 16-in. duct depth will be maintained throughout the systeml-- 2. The circular equivalent of a 48 X 16-in. duct is 29.2 in. (from Table 2), and with 8000 cfm Sowing in duct, the friction loss from Fig. 3 is 0.13 ini per 100 ft '' 3. To size the ducts/ determine the shortest equivalent' length of duct up to the nearest outlet. 6ectioD B - 35.ft tooutletl, as compared to Section F -- 10. ft, plus equivalent length of elbow, up to outlet 6. Assume the width of the duct in Section F to be 15 in., therefore, B/W - 16/15 - 1.07. Abb assume the elbow radius-to-width relation R/W to be 1.25. Then the equiva-, lent length L, Fig. 8, will be 6.5 X-(15/12) - 8.1 ft! Equivalent length of duct in Section F 10 +8.1 - 18.1 ft. Therefore; since Section F is shorter titan Section B, sise Section F first, Air Duct Design 575 Table 8 .... Tabulation of Results (Example 7) zSec Air kaf0" tion Vofooo Cfm Length ft todtf ftectoagvtar Duet In. Equtir. Frfcfioo Dio. Per 100 In. fttnHtO Net lots or Gain A B C D .B 8000 6000 4500 3000 1500 40 35 15 25.5 15 1500 1420 1300 1125 965 48X16 38X16 31X16 24X16 14X16 29.2 26.4 24.0 21.3 16.3 0.130 0.120 0.110 0.095 0.083 -0.0620 -0.0240 -0.0000 +0.0003 +0.0027 F 2000 18.1 1200 15X16 16.7- 0.130 ' -0.0240 G 1000 15 1000 9X16 13.0 0.130 +0.0029 the friction rate as!in Section A, 0.13 in. per 100 ft. This friction rate and 2000 cfm results in an equivalent diameter of 16 7 in Section F. From Table 2, the rectangular equivalent of , 16J in. diameter duct is 15 X 16 in. This results in an average velocity of 1200 fpm in Section F. ____ Note that the shorter equivalent length is sized first to prevent the velocity in the otiier branches from exceeding the recom mended velocities. 4. Loss in Section F = 0.13 X 0.181 - 0.0236 in. water. 5 Since the operating pressure of outlet 1 is to be the same as that of outlet 6, the loss in Section B must equal the loss in Seo- - 1000 Duct size for Section G -- --:-- X'144 -- 140 sq in. -- 9 X 16 1030 in. ~ Actual velocity - 1000 fpm. 10. Total pressure loss of the system is the algebraic sum of the static pressure losses gains. Since the system was designed basically for no gain-no loss, it will have only losses in Sections A and B (or F) and the outlet operating pressure (see Table 8). tion F. Using the Static Regain Chart, Fig. 14, size Section B for Loss in Section A -- 0.13 X 0.40 -- 0.062 a net loss of 0.0236 in. water. Enter Fig. 13, with 6000 cfm after Loss in Section B (or F) --0.024 take-off, proceed to 35 ft (Section B duct length between the Outlet Operating Pressure -- 0.120 take-offs) and find L/Qi*-*1 -- 0.18. Entering the regain chart, Fig. 14, with L/Q* *" -- 0.18 and Total Pressure Loss > 0.206 in. of water velocity (Ft) before take-off of 1500 fpm, move to the right to . obtain 0.0236 in. loss; find velocity (V*) after -take-off = 1420 fpm. (See Net SP Loss in Guide to Use in Fig. 14.) , DESIGN OF HIGH-VELOCITY DUCTS Duct size for Section B = (6000/1420) X 144 514 eq in. -- 38 X 16 in. The transmission of air at high velocities, though common in industrial exhaust systems for many years, has gained Aefaml velocity -- 1420 fpm. Actual friction loss -- 0.032 ini'' water, compensated by provision for it and static pressure regain. , 6. To size Section C, enter Fig. 13 with 4500 cfm after take-off, proceed to 15 ft ^length of Section O and find L/Q***1 " 0.09. ..wide acceptance in comfort air-conditioning and ventilation ..systems only in the past few years. This acceptance is,due partly to the use of improved fans and special eound-attenua- Enter the regain chart with L/Q**-*1 ** 0.09 and velocity,before -4 ,'ltion and control equipment, and partly to improved'design take-off = 14^ fpm; find for no ^atn-no lose velocity after take-off - and installation methods based upon a better understanding 1300 fpm. of the general problems connected with the design and instal Duct size for Section C = (4500/1300) X 144 lation of high-velocity air-conditioning systems.1*-0 For - 498 sq in. - 31 X 16 in. general information on these systems, see Chapters 1,2,3, and Actual velocity -- 1300 fpm. . 7. Before Section D is sized, the equivalent length of the elbow m this section'must be determined. Assuming the width of Sec tion D to be 25 in.,' then H/W -- 16/25 -- 0.64.-Aasummg-R/W of the elbow to be 1.25, then the equivalent length (Fig. 8) of the elbow will be 6.0 X 25/12 -- 12.5 ft. The total equivalent length of Section D then'will be 6.5 + 6.6 + 12.5 -- 25.5 ft. . * ' . ` _ Enter Fig. 13 with 3000 cfm after take-off, then move up to 255 ft (Section D length) and findL/Qj*-*1 -- 0.20. Enter the regain chart with L/Qt-- 0.2'and velocity before take-off - 1300 fpm; find for no gain-no loss, velocity'after,takfri off -- 1120 fpm. 4 of the 1964 Guide And Data Book The design of high-velocity duct systems involves a com promise between' reduction of duct size and the consequent necessity for higher fan horsepower. While .the size of the ducts and the air velocities are governed in large part, by the available building space, the maximum velocities given later, in this section should not be, exceeded without careful examination of all factors involved. The following general rules will prove helpful in designing high-velocity duct systems: Duct size for Section D - (1300/1120) X 144 -- 386 sq in. -- 24 X 16 in. Actual velocity -- 1125 fpm. 8. To size Section B, enter L/Qt*-*1 chart with 1500 cfm after toke-off, up to 15 ft (Section E duct length) and find L/Q**- _ Enter the regain - chart with L/Q**- -> 0.175 and-' velocity before take-off -- 1120 fpm; 6"d for.no gain-no loss the velocity after take-off - 980 fpm. ... Duct size for Section E - (1500/900) X 144 . -- 200 sq in. -- 14 X 16 in. ;* Actual velocity -- 965 fpm. , 9.. To size Section G, enter L/Q**-** chart with 1000 cfm, move aP to 15 ft (Section <7 duct length) and find L/Q**-*1 -'0.22. Enter the regain,chart with L/QttM. -- 0.22 and velocity before toke-off -- 1200 fpm, find for no oasn-no loss velocity after take* off - 1030 fpm. 1. The same general rules which apply to conventional duct design also apply to high-velocity duct design. (See Section, Design Methods.) ' < 2. Static regain must be accounted for in high velocity systems. Latest data indicate that approximately 75 percent of the original velocity pleasure can he regained if the ducts are of recommended and air-tight construction. The allowances, for static regain must be made with all three duct design methods described in this chapter.... . 3.-Proper sound control-must be provided.-To take care ot low-frequency fan noise; a-sound attenuator must usually be jpafullXn after the fan. When acoustic terminal devices are not used, attenuator chambers or sound-lined ducts must: be..in stalled after living valves, in order to attenuate duct and valve noise to acceptable levels. '- ; - _ 4. Air velocities in main ducts may vary from 2500 fpm in some installations to over 6000 fpm in others. Corresponding x'