Chapter 14
1945 Guide
--Return-piping may be sizedwith-the aid of-Table-5 where pipe capacities for wet, dry, and vacuum return lines are. shown for the pressure drops
per 100 ft corresponding to the drops in Table 4. It is customary to use
the same pressure drop on both the steam and return sides of a system.
Example 2. What pressure drop should be used for the steam piping of a system if
the measured length of the longest run is 600 ft and the initial pressure is not to be over
2-lb gage?
.
Solution. It will be assumed, if the measured length of the longest run is 500 ft, that
when the allowance for fittings is added the equivalent length of run will not exceed 1,000 ft. Then, with the pressure drop not over one half of the initial pressure, the drop could be 1 lb or less. With a pressure drop of 1 lb and a length of run of 1,000 ft, the
drop per 100 ft would be Mo lb, while if the total drop were Mi lb, the drop per 100 ft
would be Mo lb. In the first instance the pipe could be sized according to Column D for Me lb per 100 ft, and in the second case, the pipe could be sized according to Column C for Mi lb.' On completion of the sizing; the drop could be checked by taking the longest line and actually calculating the equivalent length of run from the pipe sizes determined.
If the calculated drop is less than that assumed, the pipe size is all right; if it is more, it is probable that there are an unusual number of fittings involved, and either the lines must be straightened or the column for the next lower drop must be used and the lines resized. Ordinarily resizing will.be unnecessary.
PIPE SIZING FOR INDIRECT HEATING UNITS
Pipe connections and mains for indirect heating units are sized in a manner similar to radiators, but the equivalent direct radiation must be
ascertained for each row of heating unit stacks and then -must be divided into the number of stacks constituting that row and into the number of connections to each stack. :
where
_ Q X 60 X i - le) _ Q X (fi - fe)
55.2 X 240
220.8
(1)
EDR. = equivalent direct radiation, square feet.
Q =* volume of air, cubic feet per minute.
tc =* the temperature of the air entering the row of heating units under con sideration, degrees Fahrenheit.
(1 = the temperature of the air leaving the row of heating units under considera
tion, degrees Fahrenheit.
v
60 = the number of minutes in one hour.
55.2 = the number of cubic feet of air heated 1 F by 1 Btu.
240 = Btu equivalent of 1 sq ft of EDR.
Example S. Assume that a 3-row heating unit shown in this chapter in Fig. 38 is handling 50,000 cfm of air and that the rise in the first row is from 0 to 40 F, in the
second row from 40 to 65 F, and in the third row from 65 to 80 F. What is the load in EDR on each supply and return connection?
Solution. For row 1,
.50,000 X (40 - 0)
R=
220.8
For row 2, R = 50,000 X (65 - 40) 220.8
For row 3,
_ _ 50,000 X (80 - 65) 220.8
9058 sq ft. 5661 sq ft. 3397 sq ft.
Steam Beating Systems and Piping
. 257
~Each row of Keating units consists of-four stacks and-each-stack-has-two connections, so that the load on each stack and each connection of the stack is as follows; ,
Row
Total Load
. (EDR)
Stack Loads
(EDR)
Connection LoaD*> ,
(EDR)
i
9058
2265
2265 or 1132
2
5661
1415
1415 or 708
3 3397 849
849 or 425
&One quarter of total row load. bOue of stack load if two steam connections are made; otherwise, same as stack load.
The. pipe sizes would then be based On the length of the run and the pressure drop desired, as in the case of radiators. It generally is considered desirable to place the in direct heating units on a separate system and not on supply or return lines connected to the general heating system.
GRAVITY ONE-PIPE AIR-VENT SYSTEM
This system is the most common of all methods of,steam heating, especially for small size installations, due largely to its low cost and simplicity.
The downward pitch of a one-pipe air-vent system is indicated in Fig- 2. Low points and ends of steam mains pitched down from the boiler should be dripped. All drips should be sealed below water line before connecting together. In the risers and radiator connections, steam and condensation flow in opposite directions. In long steam mains it flows in the same direction as the steam and is removed from the main through the drip. Short mains may be arranged for the condensate to flow in a direction opposite the steam by sizing them so the critical velocity is not exceeded. It is customary to drip the heel of each riser in buildings of several stories to avoid counter-flow of the steam and condensate in the riser branch. In buildings of one or two stories the condensate is returned