CHAPTER 29
,1953 . Guide
principally to insure satisfactory and economical service to the consumer. There are certain fundamental principles that should be followed in. the design of a building heating system which is to be supplied from' street mains.' Although some of these apply to , any building, they have been demonstrated to be especially important when steam is purchased.
1. Provision should be made for conveniently shutting off'the steam supply at night and at other times when heat is not needed.
It has been thoroughly demonstrated that a considerable amount of heat can be saved by shutting off steam at night. Although there is, in some cases, an increased consumption of heat when steam is again turned bn in the morning, there is a large net saving which may be explained by the fact that the lower inside temperature maintained during the night obviously results in lower heat loss from the building, and less heat need therefore be supplied.
Steam can be entirely shut off at night in most buildings, even in very cold weather, .without endangering plumbing. It is necessary, however, to have an ample.amount
Because of the lack.of coincidence between the heating system.load and the-hot; water demand, a greater, amount of heat can be extracted from the. condensate-if; storage capacity is provided for the preheated water. Frequently, a type of econ omizer is used in which the coils are submerged in a storage tank. ;
S. Heal supply should be graduated according to variations in the outside temperature.<
The maximum in economical operation and satisfactory heating can only be ob tained by the use of automatic temperature; control (See Chapter 39). '
METERING '''
The perfection of fluid meters has contributed as much to the advance
ment of district heating as any other one thing. Meters, are classified
into two groups: Condensate Meters and Rate ofFlowMeters.
'
Condensate Meters
The one type of quantity vjneter used is the condensate meter, which may be of the tilting bucket or revolving drum type.
The condensate meter is a popular type for use on small and medium
Fig. 5. Method op Installing a Water Heater and Economizer in a Gravity Heating System
of heating surface so that the building can be quickly warmed in the morning. Where the hours of occupancy differ in various parts of the building, it is good practice to install separate supply pipes to the different parts. For example, in an office build ing with stores or restaurants on the first floor which are open in the evening, a sepa rate main supplying the first floor will permit the steam to be shut off from the re mainder of the building in the late afternoon. The division of the building into zones, each with a separately controlled heat supply, is sometimes desirable, as it permits the heat to be adjusted according to variations in sunshine and wind.
2. Residual heat in the condensate should be salvaged.
This heat may be salvaged by means of a cooling coil, or as iB more frequently done, by a water heating economizer (see Fig. 5) which preheats the hot water supply to the building.
The condensate from the heating Bystem, after leaving the trap, passes through the economizer. The supply to the hot water heater passes through the economizer, absorbing heat from the condensate. If the hot water system in the building is of the recirculating type, the recirculating connection should.be tied in between the economizer and the water heater proper, not at the economizer inlet, because the recirculated hot water is- itself at a high temperature.
Fig. 6. Gravity Installation for Condensation Meteb Using Vented Receivers
sized installations, where all the condensate can be brought to a common point for metering purposes. Its simplicity of design, ease in testing, ac curacy at all loads, low cost, and adaptability to low pressure distribution have made it standard equipment with many heating companies.
. Condensate meters should not be operated under pressure; they are made for either gravity or vacuum installations. Where bucket traps are used, a vented receiver is essential, ahead of the meter. Where continuous flow traps are used, a vented receiver is not necessary, but is desirable. Fig. 6 illustrates a gravity condensate meter installation using a vented, receiver.
Rate of Flow or Flow Meters
Flow meters used for district heating work are of three types: Area Meters, Head Meters and Velocity Meters. (See Chapter 4, Fluid Flow.)
Area meters are those in the operation of which a variation in the crosssection of stream, under constant head, is used as an indication of the rate, of flow. A tapered plug is suspended in an orifice and moves axially with the flow, which is vertically upward. The weight of the plug_ provides a definite pressure differential, and the plug floats at such a height as will provide enough orifice area to pass the flow at the pressure difference. The