Document vXXRn6310qyDjyOQ2QnzZG7Y
270
CHAPTER 12
1958 Guide'
average wind velocity from December through February is 15 mph or
higher in only 7 of the cities listed and Column 9 shows that a wind velocity of 15 mph did not occur in any city listed for temperatures equal to or lower than those shown in Column 8 for the years. 1935-1939. Conse quently, it will often be desirable to modify the U values in Tables 5 to 15, 18, and 19 of Chapter 9 to correspond to lower wind velocities. Correc tion factors for wind velocities can be found in Table 20 of Chapter 9.
' -
Column 6 in Table 1 lists the average annual minimum temperature which is the average of readings of the one lowest temperature occurring for each year the weather station has been in existence. A comparison of
the temperatures listed in Columns 6, 8, and 10 of Table 1 offers some guid ance in selecting a suitable outdoor design temperature for particular cities. For the 63 cities in the United States having temperatures listed in all three columns the average annual minimums in Column 6 average 2.3 deg warmer than the design temperature in common use listed in Column 10 whereas the design temperatures in Column 8 average 11.0 deg warmer/ than those in Column 10. There are variations of 6 deg or more in either
direction from these average differences, however, for a few cities in this' group.
Designers are cautioned against attempting to compensate for internal
vagrant heat sources in a structure, the heat generated by electrical equip-;'
ment, the approximations that may exist in heat transmission factors and1
infiltration rates, and the safety factors used in selecting heating plant'
capacity by adjusting the design temperature difference between indoors
and outdoors. These factors should be accounted for by more careful
analysis of their existence and magnitude in computing the heating load-
that must be carried by the heating plant itself.
;
INSIDE TEMPERATURES
.:
The inside air temperature which must be maintained within a building
is understood to be the dry-bulb temperature at the breathing line, 5 ft.'
above the floor, or at the seating level, 30 in. above the floor, and not less:
than 3 ft from the outside walls. Inside air temperatures usually specified;,
vary in accordance with the intended use of the building. Table 2 presents;
values which conform to good practice.
!ji;
The proper dry-bulb temperature to be maintained depends upon theU
relative humidity and air motion, as explained in Chapter 6. In others,
words, a person may feel warm or cool at the same dry-bulb temperature;;'
depending on the relative humidity and air motion. The optimum winter.-
effective temperature for sedentary persons, as determined at the A.S.H.A.E-.t_
Research Laboratory, is 67-68 ET.
-
As explained in Chapter 6 for so-called still air conditions, a relativehumidity of approximately 50 percent is required to produce an effective,; : temperature of 68 ET when the dry-bulb temperature is 72.5 F. However; K even where provision is made for artificial humidification, the relative,':, humidity is seldom maintained higher than 40 percent during the eX'-tremely cold weather, and where no provision is made for humidification/;*:
the relative humidity may be 20 percent or less. Consequently, in using/; the figures listed in Table 2, consideration should be given to the actuag/; relative humidity to be maintained, if provision is to be made for humidifi'/cation. If no humidification is to be provided, the higher temperatures
Heating Load
271
may not even produce comfort on cold days; if humidity is to be main tained at 50 percent, the lower temperatures will apply. . .
In rooms having large glass areas, when sun is not shining, or in rooms with walls having a high transmission coefficient, the lowered surface tem perature will cause a feeling of coolness even though the air temperature in the room is at or above the temperatures indicated in the table. In rooms of this character, it is desirable to design for even higher temperatures than those listed, unless a compensating higher temperature surface is installed to offset the low temperature surfaces.
Table 2. Winter Inside Dry-Bulb Temperatures Usually Specified*
Ttpe of Building
Deg F
Ttpe op Building
Deg F
Schools--
Toilets and baths.............................................. Wardrobe and locker rooms...........................
70-72 68-72 55-65
70 65-68
66
Naiatoriums................................................
Hospitals-- Private rooms......................................... Private mnmn fsnririrall Operating rooms.................... Wards.......................................
Toilets Bathrooms....
75
70-72 70-80 70-95
68
70-80
Theaters-- Hotels--
Toilets and service rooms.............................
68-72 68-72
68
70
66 65-68
68
Paint Shops.......................................................................
68-72
120 110
60-65 50-60
80
The most comfortable dry-bulb temperature to be maintained depends on the relative humidity and
air motion. These three factora considered together constitute what is termed the effective temperature. (See HifP ,?< ,When relative humidity is not controlled separately, optimum dry-bulb temperature for comfort will be slightly higher than shown in Table 2.
The inside temperatures specified in Table 2 may be used for panel heated spaces as well as for spaces heated by warm air, radiators or con vectors. It is true that warm panel surfaces tend to produce a comfortable environment at a lower room air temperature than when warm panels are
not present, but field experience in the United States has indicated that actual reductions in air temperature are slight in operation.
Temperature at Proper .Level. In making the actual heat loss compuations, however, for the various rooms in a building it is often necessary
t temperatures given in Table 2 so that the air temperature a Proper level will be used. By air temperature at the proper level is meant, in the case of walls, the air temperature at the mean height be tween floor and ceiling; in the case of glass, the air temperature at the
ean height of the glass; in the case of roof or ceiling, the air temperature
ron . m<;an he'ght the roof or ceiling above the floor of the heated m, and in the case of floors, the air temperature at the floor level.
hiehe^nT1^6 Ceiling. The air temperature at the ceiling is generally
the t1 (1 n
breafhmg level due to stratification of air resulting from
fact sh
warmer or less dense air to rise. An allowance for this
case ofhV> .n?a<fe m calculating ceiling heat losses, particularly in the
somewh f
However, the exact allowance to be made may be
(11 * `mocult to determine as it depends on many factors, including
outsidp t 6 keatmg system, (2) . ceiling height, and (3) the inside-
emperature differential. The type of heating system is par-