HEAT TRANSFER SYSTEM CLEAN-OUT PROCEDURE (USED SYSTEMS)
1. Drain the system Hot into clean drums and store for reclamation when de sired.
2. Recirculate Oakite 85, 20% by volume, 160F. four to six hours. During recirculation, air or steam should be injected into the inlet side of the system periodically, permitting a surging action.
3. Drain solution and as soon as the system has been drained flush it immediately with ambient temperature water, five to ten minutes; during rinsing surge with steam or air.
4. Drain and rinse with Oakite 190, in recirculating manner, 12oz. /gal. , 170F. to 190F. , thirty to forty-five minutes, surging with air or steam.
5. Rinse ambient temperature water five to ten minutes, 6. Rinse with 170F. to 190 F. water ten to fifteen minutes. 7. Inject air to dry.
The local Oakite representative will provide no-charge standby service to assure the proper application of the product if requested. This will include on-the-spot testing which is performed during the clean-out. The system should be as dry as possible prior to charging with THERMINOL to minimize startup difficulties caused by moisture flashing to steam as the system is brought to temperature.