HEATINC VENTILATINC AIR CONDITIONING CUIDE 1944
tubular radiators with a spacing of in. per section are now available,
the large-tube type which had a spacing of 234 in. per section having
been discontinued. Small-tube radiators occupy less space and are particularly suited for installation in recesses.
After a complete study of the demand for various sizes of radiators, the Institute of Boiler and Radiator Manufacturers, in cooperation with the Division of Simplified Practice, National Bureau of Standards, established
Table 1. Small-Tube Cast-Iron Radiators .
Number OF
Tubes
per Section
Catalog . Rating
per Section
3d 4d 5a
-'6d.
Sq Ft
1.6
1.6 1.8 2.0
2.1 2.4
1.6 2.3 ;3.0 3.7
Section Dimensions
A Height
In.
B Width .
Minimum Maximum In. In.
c
Spacingb
In.
25
3M
3M
m
D Leg
Height
In.
2'A
19
V/k
4%
m
22
4%
4%
m* ' 2x/i
25
4%
4%
m
2H
m22 5% 6%
2A
25 5% 6he m 2A
14. 19 25 32
6'% 6>% 6% 6%
8 8 8 8
W 2A.
m 2A
m 2)4 m 2y2
l-c-l. |-B-1
[1 w
I
'
R1 ) It- Ilxi
ajhe square foot of equivalent direct steam radiation is defined as the ability to emit 240 Btu per hour, with steam at 215 F. in air of 70 F. These ratings apply only to installed radiators exposed in a normal manner; not to radiators installed behind enclosures, grilles, etc. (See A.S.H.V.E. Code.for Testing Radi-' ators.)
^Length equals number of sections .times 154 in.
Over-all height and leg height, as produced by some manufacturers, are'one-inch (1 in.) greater than shown in Columns A and D. Radiators may be furnished without legs. Where greater than standard leg heights are required this dimension shall be 4)^ in.
dOr equal.
Simplified Practice Recommendation R174-43 for small-tube cast-iron radiators. Table 1 shows the size and dimensions of small-tube,cast-iron radiators which are being manufactured at the present time.
Wall radiators are now rated in terms of equivalent square feet, the same as small-tube radiators. Tests have shown that the heat emitted from a wall-type radiator may be reduced from 5 to 10 per cent if the radiator is placed near the ceiling with the bars horizontal and. in an air temperature exceeding 70 F. When radiators are placed near the ceiling,
there is usually such a large difference in the temperature between the floor level and the ceiling that it becomes difficult to heat the living zone
of the room satisfactorily.
*.
Pipe coils are assemblies of standard pipe or tubing (1 in. to 2 in.) which are used as radiators. In Older practice these coils were commonly used in factory buildings, but now wall-type radiators are most frequently used for this-service.. When coils are used, the miter type assembly is to be
252.
CHAPTER 13. RADIATORS AND CONVECTORS
preferred as it best cares for expansion in the pipe. Cast manifolds or headers, known as branch tees, are available for this construction.
The heat emission of pipe coils placed vertically on a wall with the pipes horizontal is given in Table 2. This has been developed from avail able data and does not represent definite results of tests. For such coils the heat emission varies as the height of the coil. The heat emission of each pipe of ceiling coils, placed horizontally, is about 126 Btu, 156 Btu, .' and 175 Btu per linear foot of-pipe, respectively, for 1-in., 134-in., and
134-in- coils. .
CONVECTORS
Cast-iron radiators may be concealed in a cabinet or other enclosure for appearance. In such cases a greater percentage of heat is conveyed to the room by convection thereby resulting in a form of gravity convector.
Table 2. Heat Emission of Pipe Coils Placed Vertically on a Wall (Pipes Horizontal) Containing Steam at 215 F and Surrounded with Air at 70 F
Btu per linear foot of coil per hour {not linear feet of pipe)
Size or Pipe
1 In.
Single row ............. ..............................
132
Two
252
Four............ ;1..... ;.......... ......................
t 440
Six.... .......... ......................... ......................
Eight----------- ;.--4......................
567 651
Ten - . 732
Twelve..................... ........... .....................
812
IX In.
162 312 545 702 796 907 1005
1M In. -
185 348 616 793 907 1020 1135
.
A typical recessed convector is shown in Fig. 1. The heating element consisting of a large percentage of fin surface is usually shallow in depth and placed low in the enclosure in order to produce maximum chimney effect in the enclosure. The air enters the enclosure near, the floor line; just below the heating element, is moderately heated in passing through the core and delivered" to the room through an opening near the top of enclosure. Since the air can only enter the enclosure at the floor line, the cooler air in the room, which always lies at this level, is constantly beingwithdrawn and replaced by the warmer air. This air movement accom plishes the desired reduction in temperature differentials and assures maximum comfort in the living zone.
Concealed heaters or convectors are generally available as completelybuilt-in units. The enclosing cabinet should be designed with suitable, air inlet, and. outlet grilles to give the heating element its best performance. Tables of capacities are catalogued for various lengths, depths and heights, and combinations are available in several styles, for installations, such as the wajl-hung type, free-standing floor type, recess type set flush with wall or offset;, and the completely concealed type. Most of these types may be arranged with a top outlet grille in a plane parallel with the floor, although the front, outlet, is practically standard. In cases where enclosures, are to be used, but are not furnished by.the heater manufacturer, it is important that theproportions of the cabinet and the grilles be so designed that they:
253