CHAPTER 33
Rg. 15 .... Steam GHd Humidifier
lem ph^nlH be considered in selecting equipment'and insetting
up maintenance schedules on installed equipment. industrial humidifiers Sis available in many types.'Larger
versions of the residential types. Figs. 11-14, ale quite fre-
qttentiy used. In additionto thoste noted undefr the section on
Residential Humidifiers, pans with steam or hot water pipes
to heat the .water are.quite'frequently used-. Where-steam is
available, steam grids are also frequently, used. (Fig. 15).
There are aim commercial atomizing types usirtg pneumatic
sprays. Commercial air washers, also frequently used,-have
been discussed in previous sections, as were pad type evapora
tive coolers.
''
Calculations
The method used to calculate the*moisture required Lor ah
industrial area is shown in Example 1. In addition to the fac
tors noted, some locations may have the problem'df maintain
ing humidity while cooling the area. The humidification engi
neer ahrnild work closely With the cooling engineer so that the
cooling equipment-is designed for maximum cooling.with
minimum dehuihidificatidn, and sufficient capacity, to offset
dshumidification should be included in 'sizing the humidifier.
"'Example t: Determine the hUmidiScation required for tory in Dallas, Texas, to maintain 45 percent relative humidity at 72 F. The factory h** a volume of 100,000 cu ft. Machines within the factory will give off 5.8 lb per.hr of moisture. There will be 10 workmen in the plant. No additional load will be neces sitated by cooling (dehunudification) and no moisture will be ab sorbed by stored materials.
Solution: The quantity of moisture required to maintain the -desired indoor conditions may -be found from Equation 5.
The number of air changes per.hour is assumed to be 1. The values of hi and K artfouad frOm th% ASHRAE Psychrometnc Chart (Chart l).fe tie 0.0077 and 0.0817 lb per lb dry air, re spectively.
1965 Guide And Data ftook
IDO 000
Therefore, H -
(1) (0.0077 - 0.0012)
-- 49.2 lb of moisture per hour. - - `
This amount would be reduced by the moisture given off by the people in the area and by the machines in the area and would be increased by the amount of moisturerequired by the material stored in the area. If the area were cooled, the requirements would-be increased by an-amount equal to the dehumidification caused by the cooling equipment.
The moisture released by Workers is,10 X 0.4 = .4 lb per hr, the total moisture given off by workers and machines is
4 + 5.8 = 9.8 lb per hr. Therefore, the net load for the humidifier is 40.2 -- 9.8 = 39.4 lb per hr.
The number and type of units to be used and the location Will vary with the installation. In the example given, where the area is one large room, one large humidifier is economically more feasible than several small units. If, however, the area to be humidified consists of several isolated areas separated by vapor barrier walls and not interconnected by a duct sys tem, then several small units would be recommended.
- Where the size of the area issuch that several units are used inone large area, they should be preferably distributed equally through the area being -humidified. They should be located so that other air movement systems will assist the distribu tion of humidity rather than hinder it. The controls should be spotted where the closest control is desired.
: REFERENCES
1 R. R. Irwin". Panel cooling for a residence (ASHAE Transac
tions, Vol. 61, 1955, p. 297). * j. R. Watt, and R. A. Bacon: The indirect evaporative an
Cooler (ASHAE ThansaeAtons,' Vol. 62, 1956, p. 553). * Q. W. Armspact': Private communication with R. S. Ash,
I960..
-
. H. S. Diitcher: Private communication with R. S, Ash, 1960,
` R. M. Wesdott: Water 'treatment for evaporative coolers
(Compilation of Papers, USAF Evaporative Cooler Conference,'
March 1955)-
. ,- .
,,,
* 8. F. Duncan: Air cOoliagbyevaporation (ASHAE Joubnal
Section, Heating, Piping and Air Conditioning, August 1955, p.
141).
r`
'
1 L.- Smith: How to design controlled environment for best
greenhouse gmwing conditions (Heating, Piping xmd Air Con-
aitioning, VoL 6&No. 2, 1958, p. 41)...
-
` * S. C. Hite and J. L/Dray: Research tn Home Humidity Control
(PUrdde University, Engineering Experiment Station Research 8&iea NO. 106,-November 1948).
BIBLIOGRAPHY
H. M. Hendrickson: How air washers perform when cooling
(Heating, Piping and Air Conditioning, Much 1954, p. 119).
H. M. Hendrickson: How to calculate air washer performance
(Beating.Piping and Air Conditioning, September 1954, p. 116).
R. S. Farr: Evaporative cooling for comfort (RETBioEBA-riNa
ENGBrtEBiftd, May 1953, p. 527).
R. 8.: Ash: Many types of evaporative coolers (American
Artisan, August 1953, p/72>.
_ _.
R. E. Treybd: }kass-Transfer Operations (McGraw-Hill Book
Company, New York,-1955).
'
,_
T. K. Sherwood and R. L. Pigford: Absorption and Extraction,
2nd Edition -(McGraw-Hill Book Company, New York, 1952).
CHAPTER 34
AIR-COOLING AND DEHUMIDIFYING COILS
Uses for Coils; Cor? Construction and Arrangement: Water Coils, Direct-Expansion Coils, Control, Row Arrangement, Applications; Cor? Selection: Application Range, Dry Cooling Coils, Dehumidifying Coils; Heat Transfer and Air-Row Resistance> Performance of Dry Coo/mg Coils: Overall Coefficient of Sensible Heat Transfer; Performance of Dehumdifying Coils; Determining Refrigeration Load
COILS described in this chapter are used for cooling an simplify the control problem. In this case, the dry-bulb air stream under forced convection. Extended-coil equip temperature is also the dew point, and hence, a dew-point ment may consist of a single coil section or a number of indicontrol can be arranged by using a simple duct thermo
vidual coil sections which are built-up into banks and as stat Spray dehumidifiers have the advantage over unwetted
sembled in the field. Coils arc also used extensively as com coils of obtaining more air cleaning and odor absorption.
ponents in central station type air-handling units and. in On the other hand, coils make possible a closed and balanced
factory-assembled self-contained air conditioners. The ap cooling-water circuit, obviating the unbalanced pumping
plications of each type of coil are limited to the field within bead, the complication of water4evel control, and danger
which it i3 rated. Other limitations are imposed by code regu from possible floods incidental to multiple-spray dehumidi
lations, by proper choice of materials for the fluids used and fiers, especially if located; on different levels. The use of
the condition of the air handled, or by an economic analysis coils often makes it possible for the same surface to serve
of the possible alternates for each installation.
for summer cooling and winter heating by circulating cold
water in one season and hot water in the other, with'conse
USES FOR COILS
Coils are used for air cooling with or without accompany ing dehumidification. Examples of cooling applications with out dehumidification are precooling coils using well water or other relatively high temperature water to reduce the load on the refrigerating machinery, or water-cooled -coils
quent saving in apparatus and piping. Another advantage is that where the extended surface-coil system can be used with direct expansion of refrigerant, it is comparatively low in ini tial and operating costs.
The regulations of the applicable national and local safety codes should be consulted by the design engineer.
removing sensible heat in connection with chemical, mois ture-absorption apparatus. A major portion of coil equip ment is designed to provide, simultaneously, both air sensible cooling and dehumidification. The assembly usually includes air cleaning means to protect the coil from accumulation of dirt, and to keep dust and foreign matter out of the condi tioned space. Although cooling and dehumidification are the principal functions, cooling coils are additionally and pur posely wetted with water or a hygroscopic liquid to aid in air cleaning, odor absorption, or prevention of frost.
The usual cooling media used in extended-surface coils are cold water or Group I (ASA Classification) refrigerants, but others are used in special cases. Brines are seldom required for the range of applications covered by thi chapter, al though there are cases where low entering-air temperatures' with large latent-heat loads require a refrigerant tempera-' tore so low that use of water becomes impracticable. Some times, also, brine from an industrial system already installed is the only convenient source of refrigeration.
COIL CONSTRUCTION AND ARRANGEMENT
. Coils are basically of two types, those consisting of bare tubes or pipe, and those having extended or firmed surfaces.' The former are little used for the applications covered by this chapter, but are often employed where conditions cause frost accumulation, and for cooling within spray dehumidifiers.
In fin or extended-surface coils the external .surface of the tubes is known as primary, and the fin surface.is called teoondary. The primary surface consists generally of round tubes or pipes which may be staggered, or placed in line withrespect to the air flow. The staggered arrangement is usuallypreferred because it obtains a somewhat higher heat transfervalue. Numerous types of fin arrangement are used, the most' common of which are.-smooth spiral, crimped spiral, flat plate, and configureted'plate, all as shown in Fig. 1. While the spiral fin surrounds each tube individually in'all cases,' tire plate types may be continuous- (including several 'rows of tubes), or they may be round or square, with individual
For combined cooling and dehumidifying, extended-surface . coils present an alternate to spray dehumidifiers. For many applications it is possible, by proper selection of apparatus,
choice of air velocities, refrigerant temperatures, etc., to perform the same duty with either. In a few cases both sprays and coils are used. The coils may then be inctAiwi
8Fray chamber, either in series with the sprayB 0r^^ow ^iem- 1 making the selection between spray and Kirface dehumidifiers, certain advantages of each
OttHKD SPIRAL fun SMOOTH SPUUL POO
*if|"||[|h o o oo
CONTINUOUS PLAT PLATS-PINS
3 OO C
be considered. The fact that a spray dehumidifier is usu*lly designed to deliver nearly saturated air, tends to
O O MM
CONPICURATCD RJTl P
- PLATS PISS ON MBIVOUAL ruses
11 U}TC0A-Coa*
Rg. 1 .... Types of Rn-Ccal Arrangement