Document vBp5zdozeYLBX7d0o4jxmqz4q
TECHNICAL DATA SHEET-
pyrocLor
APR 20 '
MONSANTO COMPANY
INFORMATION CENTER
MonsantoTRANSFORMER ASKAREL BY
Pyroclor 5 is a fire resistant transformer coolant in the Askarel class. A new Monsanto transformer coolant Inerteen* 70/30, introduced in 1967, achieved remarkable suc cess in the U S.A. Because of this Monsanto in Europe has started manufacture of this product at the Newport U.K. plant. This new fluid is called : Pyroclor 5.
Pyroclor 5 is now the recommended fluid for all Pyroclor transformers and has the following important features : Better cost performance from lower weight per gallon. Same compatibility with materials of construction. Higher relative permittivity. Similar viscosity over the normal temperature range of transformer operation
(--5 to +90 C).
The Pyroclor synthetic transformer coolant at present on the European market is still available for cases where viscosity at unusually low temperatures is an important factor. This fluid will be known simply as Pyroclor.
Pyroclor 5 incorporates all the advantages of previous Pyroclor:
Maximum fire protection
No special fire equipment needed
*
No maintenance
No siting limitations
Low noise level
Low power loss
High impulse level
Gas scavenger to absorb any free hydrogen chloride should transient arcing occur
' Trad* nam* of W*atlnghou** Corporation.
0615115
TOWOLDMONOQ39188
Typical Properties
In terms of physical, chemical and electrical properties Pyroclor 5 and Pyroclor are very similar but detailed properties are listed for comparison in Table 1.
TABLE 1
A Comparison of Typical Physical, Chemical and Electrical Properties of Pyroclor 5 and Pyroclor (This table is not a specification)
Property
Test Method
Pyroclor
Pyroclor 5
Physical Description
ASTM D1702
Colour (APHA) Density at 20 C (kg/m3) Density at 100 C (kg/m3) Coefficient of expansion
20-100 C (deg. C'1) Viscosity at 20 C (cSt) Pour point (C) Refractive index at 25 C
Chemical Fire point
ASTM D1702 BS 733 BS 733 Calculated from density BS 188 IP 15 ASTM D1807
ASTM D92
Inorganic chlorides (ppm) Neutralization number
(mg KOH/g) PPO content (%) Stability test (Details follow) Water content (ppm)
Electrical Dielectric strength at 25 C 4 mm gap (kV) .. withstand
.. breakdown Dissipation factor at 50 Hz,
1kV/mm (%) ... at 25 C ... at 100C
Resistivity at 500 V/mm, 1 minute (Tflcm)... at 25 C ... at 100 C
ASTM D1821 Monsanto ASTM D1701 Monsanto ASTM D1533
B9148
ASTM D924
ASTM Dll69
Limpid, mobile liquid
40 1556 1468
0.000743
Limpid, mobile liquid.
40 1520 1436
0.000732
21 -- 34
1.6147
26 -- 32
1.6158
None to boiling point
0.05
0.004 0.2 Pass 30
None to boiling point
0.05
0.004 0.2 Pass 30
40 for min. >70
0.5 5
10 2
40 for 1 min. >70
0.5 5
10 2
2
Ofclbllb
TOWOLDMONOQ39189
Stability (Corrosion) Test
Description A sample of the Pyroclor is heated in darkness for 6 hours at a temperature of 210 C with a prepared piece of aluminium foil. At the end of this period, the appearance, colour, inorganic chlorides and neutralization number of the sample of Pyroclor are determined. The piece of aluminium foil is examined for changes in appearance and its weight loss is determined. Results The values in the following table must not be exceeded for the sample of Pyroclor to pass this test.
TABLE 2
Property
Aluminium foil Weight loss (g) Change in appearance Pyroclor sample Colour (APHA) Inorganic chlorides (ppm) Neutralization number (mg KOH/g)
.Test method
--
Visual
ASTM D1702 ASTM D1821
Monsanto
Value
0.0 None 200 (max) 5.0 (max) 0.01 (max)
3
061511?
TOWOLDMONOQ39190
1
I
i
A Comparison of the Compatibility of Transformer Insulating Materials with Pyroclor
In past years we have accumulated a considerable amount of data on the compatibility of various types and brands of transformer constructional materials with Pyroclor. In order to test whether this information is also valid for Pyroclor 5 we have run
side-by-side tests with 5 different materials. The details of these tests are as follows:
Ageing conditions :
7 days at 100 "C
Concentration :
As given in the table 3
Testing conditions :
Temperature 100'C; dissipation factor measured at a fre quency of 50 Hz and a stress of 1 kV/mm; resistivity measured at a stress of 500 V/mm after 1 minute.
TABLE 3
Material
Concentration
Pyroclor
Pyroclor 5
Disaipatlon factor (%>)
Reslstivity
(Tficm)
Dlssipation factor (/o)
Resist* Ivity
(Tftcm)
'Varnite' core insulation
64 cm2 in 150 cm3 5.4 2.9
5.5 2.8
ML enamel wire, 0.116" dia. 14.5 cm2 in 150 cm3 3.3 4.0
2.3 5.4
Grade K `Elephantide'
pressboard, 0.375" thick
3 % w/w
6.3 4.0
4.0 5.6
'Nebar PR', 0.125" thick,
smooth grade
0.4 % w/w
35.4 0.20 36.2 0.27
SRBP tube, 0.7" dla.
1 % w/w
11.6 1.0
13.5 1.9
From these tests we conclude that compatibility data obtained for Pyroclor are equally valid for Pyroclor 5.
4
06 L 511ti
TOWOLDMONOQ39191
Kinematic Viscosity
A comparison of the kinematic viscosity of Pyroclor 5 and Pyroclor is shown in table 4.
TABLE 4
Temperature ("O
-- 30 -- 20 -- 10
0 + 10
20 30 40 50 60 70 80 90 100
Pyroclor
ca. 16 000 1 800 350 100 42 21 12.3 7.8 5.4 3.9 3.0 2.4 1.98 1.70
Kinematic viscosity (cSt)
Pyroclor 5
Typical mineral oil
ca. 60 000 4 524 655 162 57 26 15 9.4 6.4 4.6 3.4 2.7 2.2 1.86
2 500 750 270 118 62 33 21 14 9.7 7.2 5.5 4.3 3.4 2.8
Vapour Pressure
A comparison of the vapour pressure of Pyroclor 5 and Pyroclor is shown in Table 5.
TABLE 5
Temperature fC)
40 60 80 100 120 140 160 180 200 220
Vapour Pressure (torr)
Pyroclor
Pyroclor 5
<1 2 5
.12 ' 27
55 105 188 322 527
<1 1 4 9
20 41 79 141 242 397
In the above table the values at the lower temperatures have been obtained by extrapolation. This procedure was adopted to overcome inherent difficulties in the measurement of low vapour pressures of mixtures of liquids.
5
0616119
TOWOLDMONOQ39192
Density
A comparison of the density of Pyroclor 5 and Pyroclor is shown in Table 6.
Temperature (C)
0 10 20 30 40 50 60 70 80 90 100
TABLE 6
Density (kg/m5)
Pyroclor
Pyroclor 5
1578 1567 1560 1545 1534 1533 1512 1501 1490 1479 1468
1541 1530 1520 1510 1499 1488 1478 1468 1457 1446 1436
Safe Handling of Pyroclor
Pyroclor 5 and Pyroclor are made from blends of chlorinated hydrocarbons and skin contact should be avoided. For detailed instructions on handling of Pyroclor S please see our leaflet Safety with Pyroclor*.
Monsanto Europe S.A. 1, Place Madou, Brussels 3 Monsanto Chemicals Ltd. 10*18 Victoria*Street, London S.W.1
The Information in thie bulletin le. to our beet knowledge, true end eoourate. but all recommendatlone or sugges tions are made without guarantee, since the conditions of us* are beyond our control. Monsanto disclaim any liability incurred In connection with the us* of these data or suggestions. Furthermore, nothing contained herein shall be construed as a recommendation to us* any product In conflict with existing patents covering any material or Its us*.
Publication : 11 16 (E) M.E. 1 (11/99)(Publlahed by : Monsanto Europe S.A. 1, Place Madou, Brussels 3. Belgium)
6
061b120
TOWOLDMONOQ39193