John A. Jurgihl & Associates, Inc.
July 30, 1985
2o2coMcoi/*3e oflive sr. louis. uissouni ni44
<3 1 367*7466
Mr. Bob Suter Insulating & Materials Corp. 1042 Central Industrial St. Louis, Missouri 63110
Re: Results of area air samples during asbestos removal on pipe rack in CCU.
.Dear Bob:
To determine if asbestos fibers were being released outside the controlled area during the removal of asbestos insulation, from the pipe rack in the CCU, air samples were collected around the perimeter of the removal area. These samples were collected on July 24, 1985.
Results of laboratory analysis indicate airborne fibers levels at the boundaries of the removal area were essentially negative or at normal background levels for this unit. Based on these findings, it would appear that the areas adjacent to the demolition site are free from health hazards associated with this operation. Sampling results are contained in- the attached table.
Should you have any questions regarding our report please feel free to cal 1.
Nimmo Certified Industrial Hygienist
cc: V. J. Grizzle (Shell Oil Company) Chuck Spann (Strange & Coleman)
DNN/kn
LAM 019565 ABS-000376
RESULTS OF AREA AIR SAHFLES AT CCU INSULATION
REMOVAL FROM PIPE RACK July 24, 1985
SAMPLE NO. TIME
ON - OFF
CCU-1 1110-1424
CCU-2 1111-1422
CCU-3 1109-1422
-
LOCATION
At entrance to CCU control room downwind
At southeast corner of removal area downwind
West edge of pipe rack upwind for removal
FI5EP.S PER
CUBIC CENTIMETER N.D.2
N.D.
<D.L.3
All samples were collected with MSA model G pumps that were calibrated to a flow rate of two liters per minute. The collection media was 25mm, 0.8 micron MCE filters.
2 When 100 randomly selected microscopic fields are negative
for fibrous materials the sample is reported as None Detected.
3 Detection limit for phase contrasb^microscopy for the volume
*
collected is 0.03 f/cc.
LAM 019566 ABS-000377