Document vB612Dq9X5XRZbJ48XLgkRwyw

592 CHAPTER 21 1958 Guide When selecting the size of the pump, consideration should be given to the temperature conditions under which the pump will operate. To illustrate this, at 212 F the density of water is 59.88 lb per cu ft, whereas at 380 F it has dropped to 54.36. Therefore, as the weight of a gallon of water is considerably less, the pump will have to handle a much larger volume of water. On large installations the pump sizes can be kept down to practical limits by the use of multiple pumps connected in parallel to a common header. . To. prevent flashing at the pump suction line, a bypass connection with . valve is made between the supply and return lines to allow a small quantity 'of the cooler return water to mix with the supply water from the expansion drum. Thus the temperature of the water entering the pump suction line .is a few degrees lower than the evaporation pressure, yet subjected to the full pressure in the drum. The valve is set manually to pass the minimum quantity of water as required above. Pipe, Fittings, and Insulation Steel pipe and fittings are generally used. An effort should be made to avoid the use of non-ferrous materials, since the action of the water at elevated temperatures on these materials is difficult to predict. Steel pipe should be used throughout, and piping external to the boiler house should be welded. Within the boiler house flanges are recom mended to facilitate inspection and provide ready access. Branches should take off with easy sweeps and full radius bends be used for all changes of direction. Provision for expansion is as important as for steam at the same temperatures. Piping should be insulated to the same thickness and stand ards as for steam at the same temperature. - Valves for high temperature water should be made with cast steel bodies and stainless steel trim since these have: proved far more satisfactory than "bronze valves. Wedge-type gate valves are recommended for isolating and for use within the boiler house. For general use throughout the system, globe valves are preferred. Valves combining flow control and regulation are preferable for high temperature water where heat balancing is necessary, since a small quan tity of this water contains a large quantity of heat. As high temperature water is more penetrating than low temperature water, leakage due partly to capillary action should not be ignored because even a small amount of leakage evaporates immediately. This slight leakage becomes noticeable only on the outside of the gland and spindle of the valve where thin de posits of salts are left after evaporation. Control The control of temperature is usually obtained by conventional means although it is common practice to place control valves on the outlet line of the heat absorbing equipment where the temperatures are lower. In ' larger distribution systems means of controlling differential pressures be tween the flow and return mains are advisable. With space and process heating, temperatures can be controlled within close limits by the use of two- and three-way mixing valves modulating or 'by-passing some of the high temperature water. Such controls are essential - at heat exchangers or converters. Boilers or Hot Water Generators Almost any high presssure boiler can be used for high temperature water Hot Water Heating Systems 593 systems, but certain types as, for example, the water tube boiler, are.moreadvantageous than others. Boiler selection is important and such probp; lems as frictional head loss, available water space, flue outlet, type of firing.etc., need careful consideration. The larger the system, involving heat dis-. tribution circuits of three, four, five miles or more, the greater, will be the, frictional head on the pumps, so every care should be taken to reduce the, head loss in the boiler to a minimum and thus reduce the pump horsepower. Frictional loss through a boiler operating with entrained steam and air in' the tubes and headers,, can be a serious factor. ;, Balancing is another problem which can be made simple when the system is well designed. During the: spring and autumn months and in mild; Temperature F Pressure* peia Density Lb/Cu Ft Specific Heat Btu/(lb)(F) Total Heat Above 32 F Btu/Lb? .. Btu/ Cu Ft 212 14.70 59.88 1.0055 180.00 10.760 220 17.19 59.66 1.0068 188.06 11.222 230 20.78 59.37 1.0087 198.15 ; 11.764 240 24.97 59.17 1.0104 208.26 12:327 250 29.82 58:84- 1.0126 218.39 .12.856 260 270 35.43 41.85 58.62 58.25 . 1.0148 1.0174 228.55 238.74 13.403 13.912 . 280 49.20 58.04 1.0200 248.95 14.555 290 300 57.55 67.01 57.65 57.41 1.0230 1.0260 259.20 269.48 14.942 15.476 310 320 330 340 77.68 89.65 103.03 117.99 57.00 56.65 56.31 55.95 1.0296 1.0332 1.0368 . 1.0404 279.80 290.17 300.59 311.05 15.955 16.444 16.931 17.407 3w 134.62 . 55,65 . 1.0440 321.55 17.899 360 153.01 55.19 370 173.33 54.78 380 195.70 54.36 390 220.19 "53.96 400 247.25 53.62 1.0486 1.0532 1.0578 , 1.0624 1.0670 332.10 342.71 353.39 364.14 374.96 18.333 18.778 19.213 19.644 20.106 r -- ~~~ pviiuiooiuu muuj j. itC'iinvuyimi/uc rupemcis vj oieam, oy j. j and F. G. Keyes published by John Wiley and Sons, Inc., 1936 edition. eather at any time, the heat load will be low and only one boiler will be quired. To put a boiler on the fine or. take one off is simplified if all ar * tv. SUpp y ^nes are connected into a common expansion drum. Boilers temcontrolled from the pressure developed in the drum and the high perature water supply taken through a dip pipe below the water level. in RtCe the llea.t storaSe in the system is very high (Table 6 illustrates this (.. -u per cubic foot) advantage of this high temperature water characThe can oe taken when considering the number and output of the boilers, cost nf tv * central boiler plant can be greatly reduced and the initial i,, . system lowered accordingly if the thermal storage of the system 1S taken mto account. Storage evTO^i!fmi.v,era^ure water systems offer the opportunity of storing heat to. 1 Ine peak loads and low loads within the 24-hour cycles.