CHAPTER 21
1958 Guide
When selecting the size of the pump, consideration should be given to the temperature conditions under which the pump will operate. To illustrate
this, at 212 F the density of water is 59.88 lb per cu ft, whereas at 380 F
it has dropped to 54.36. Therefore, as the weight of a gallon of water is
considerably less, the pump will have to handle a much larger volume of
water. On large installations the pump sizes can be kept down to practical
limits by the use of multiple pumps connected in parallel to a common
header.
.
To. prevent flashing at the pump suction line, a bypass connection with
. valve is made between the supply and return lines to allow a small quantity 'of the cooler return water to mix with the supply water from the expansion drum. Thus the temperature of the water entering the pump suction line .is a few degrees lower than the evaporation pressure, yet subjected to the full pressure in the drum. The valve is set manually to pass the minimum quantity of water as required above.
Pipe, Fittings, and Insulation
Steel pipe and fittings are generally used. An effort should be made to avoid the use of non-ferrous materials, since the action of the water at elevated temperatures on these materials is difficult to predict.
Steel pipe should be used throughout, and piping external to the boiler house should be welded. Within the boiler house flanges are recom mended to facilitate inspection and provide ready access. Branches should take off with easy sweeps and full radius bends be used for all changes of direction. Provision for expansion is as important as for steam at the same temperatures. Piping should be insulated to the same thickness and stand ards as for steam at the same temperature.
- Valves for high temperature water should be made with cast steel bodies and stainless steel trim since these have: proved far more satisfactory than "bronze valves. Wedge-type gate valves are recommended for isolating and for use within the boiler house. For general use throughout the system, globe valves are preferred.
Valves combining flow control and regulation are preferable for high temperature water where heat balancing is necessary, since a small quan tity of this water contains a large quantity of heat. As high temperature water is more penetrating than low temperature water, leakage due partly to capillary action should not be ignored because even a small amount of leakage evaporates immediately. This slight leakage becomes noticeable only on the outside of the gland and spindle of the valve where thin de posits of salts are left after evaporation.
Control
The control of temperature is usually obtained by conventional means although it is common practice to place control valves on the outlet line of the heat absorbing equipment where the temperatures are lower. In ' larger distribution systems means of controlling differential pressures be tween the flow and return mains are advisable.
With space and process heating, temperatures can be controlled within close limits by the use of two- and three-way mixing valves modulating or 'by-passing some of the high temperature water. Such controls are essential - at heat exchangers or converters.
Boilers or Hot Water Generators Almost any high presssure boiler can be used for high temperature water
Hot Water Heating Systems
593
systems, but certain types as, for example, the water tube boiler, are.moreadvantageous than others. Boiler selection is important and such probp; lems as frictional head loss, available water space, flue outlet, type of firing.etc., need careful consideration. The larger the system, involving heat dis-. tribution circuits of three, four, five miles or more, the greater, will be the, frictional head on the pumps, so every care should be taken to reduce the, head loss in the boiler to a minimum and thus reduce the pump horsepower. Frictional loss through a boiler operating with entrained steam and air in' the tubes and headers,, can be a serious factor. ;,
Balancing is another problem which can be made simple when the system is well designed. During the: spring and autumn months and in mild;
Temperature F
Pressure* peia
Density Lb/Cu Ft
Specific Heat Btu/(lb)(F)
Total Heat Above 32 F Btu/Lb? .. Btu/ Cu Ft
212
14.70
59.88
1.0055
180.00
10.760
220
17.19
59.66
1.0068
188.06
11.222
230
20.78
59.37
1.0087
198.15 ; 11.764
240
24.97
59.17
1.0104
208.26
12:327
250
29.82
58:84-
1.0126
218.39
.12.856
260 270
35.43 41.85
58.62 58.25 .
1.0148 1.0174
228.55 238.74
13.403 13.912 .
280
49.20
58.04
1.0200
248.95
14.555
290 300
57.55 67.01
57.65 57.41
1.0230 1.0260
259.20 269.48
14.942 15.476
310 320 330 340
77.68
89.65 103.03 117.99
57.00 56.65 56.31 55.95
1.0296 1.0332
1.0368 . 1.0404
279.80 290.17 300.59 311.05
15.955 16.444 16.931 17.407
3w
134.62
. 55,65 .
1.0440
321.55
17.899
360 153.01 55.19
370 173.33 54.78
380 195.70 54.36
390
220.19
"53.96
400 247.25 53.62
1.0486 1.0532
1.0578 , 1.0624
1.0670
332.10 342.71 353.39 364.14 374.96
18.333 18.778 19.213 19.644
20.106
r -- ~~~
pviiuiooiuu muuj j. itC'iinvuyimi/uc rupemcis vj oieam, oy j. j
and F. G. Keyes published by John Wiley and Sons, Inc., 1936 edition.
eather at any time, the heat load will be low and only one boiler will be quired. To put a boiler on the fine or. take one off is simplified if all ar * tv. SUpp y ^nes are connected into a common expansion drum. Boilers temcontrolled from the pressure developed in the drum and the high
perature water supply taken through a dip pipe below the water level. in RtCe the llea.t storaSe in the system is very high (Table 6 illustrates this (.. -u per cubic foot) advantage of this high temperature water characThe can oe taken when considering the number and output of the boilers, cost nf tv * central boiler plant can be greatly reduced and the initial i,, . system lowered accordingly if the thermal storage of the system 1S taken mto account.
Storage
evTO^i!fmi.v,era^ure water systems offer the opportunity of storing heat to.
1 Ine peak loads and low loads within the 24-hour cycles.