American Society of Heating and Ventilating Engineers Guide, igjj
Figs. 36 and 37 show typical connections to indirect cast iron convi
heaters, and apply to vapor and vacuum systems especially. p;,,.
and 38 show duct connections to such heaters.
s'
Pipe Coil Connections
Fig. 39 shows practicable piping connections to pipe coils. it, important that the supply valves for all radiators which come below supply mains shall be above these mains, or that there shall be a drain connection consisting of a trap or of a pipe leading to the wet re depending on the type of system, above these supply valves. Witho such provision water will condense above the valves when they are clo and this may cause objectionable noise or damage when the valves opened.
Blast Heater Connections
Fig. 40 shows vacuum system returns for fan-blast heaters with i auxiliary air vent piping and air-line valves usually required with th heaters, especially when they are of cast iron.
Fig. 41 illustrates another typical blast heater piping hook-up freq encountered, but with which only the return ends have auxiliary air ven It is to be noted that while the two super-imposed heaters may drain i a trap common to both, the successive layers of heaters with referem to the air flow from the fan should each have a separate trap, since d condensation- rate varies in each successive layer after its predecess has warmed the entering air.
Unit Heater Connections
When unit heaters are used with steam heating systems the designe must always take into consideration the great condensing capacity o these devices. They must be placed high enough above the boiler wate line to compensate for the pressure drop or must be used with system having pumps or other positive return devices, and must always hav pipe connections proportional to their maximum heat emission.' Sora typical details of unit heater connections are shown in Chapter 9, Uni Heating and Ventilating Machines.
IMPORTANCE OF LAYOUT
With the increasing use of automatic temperature control, the prope layout of the steam mains to secure even distribution of the steam to a! the radiators is of importance. It is not sufficient thai the pipes b properly designated to -carry the maximum amount of steam. Stean heating systems are operated at their maximum capacity only for a fractioi of the time and they should be designed to distribute evenly at reduce! capacity. Almost any piping layout will give heat in sufficient quantitie to all the radiators for zero weather if the pipes are large enough, but thi is only one of the requirements; the system must be' capable of operatinj efficiently at reduced capacities. Hence the importance of careful an( intelligent arrangement of the steam mains.
Chapter 11
HOT WATER HEATING
- `-V'rnvitv and Forced Circulation; Maximum Water Temperature; remoerature Drop through Radiator; Arrangement of Piping; Pine Sizes; Changing a System from Gravity to Forced Circulation; r>lrc Relative Economy of Gravity and Forced Circulation.
OT water heating systems are of two general types, namely, (1) gravity systems which depend for circulation upon the different
dciiercnAusliatgytrioaor,nu(f -sttshhyees-tJewwm--aa-s-tt-ee, rrthcceooclluuirmmcnunsslaimtniontuhnbe.efinlogwma-a-n-ind--t-ar--ein-t-eu--dr-1n--1b---l-y-i--n--m--e--s-e--aa--nn--sdoIf(2na)rpfMouirmmcenpd, The heat losses from buildings heated by direct hot water heating s,ystems are determined in the manner indicated in Chapter 5. The amount of radiation to be installed in buildings heated by direct hot water heating depends upon the total heat loss from the building and the type and operating characteristics of the radiation to be used.
Several different piping systems may be designed for any given com bination of heater and radiator. The general rule to apply to the design of a pipe system is that thefriction head leadingfrom the heater to a radiator arid bock again must equal the pressure head causing the water to flow for that particular circuit. This rule is based on the condition that the water in the system is circulating with a uniform velocity as is the case when the radiators (and piping) dissipate exactly the same quantity of heat in a given period of time as is delivered to the water in the heater.
The principal factors to be considered in the design of the piping system are;
- - 1. The heat losses of the rooms or spaces to be heated. .* 2.,`The location and type of radiators. , - .3."'Arrangement of the circuits of the system, including length of pipe and number ' and type of fittings.
4. The temperature of the water in the flow and return risers. " 5. Whether gravity or forced circulation is to be used.
GRAVITY SYSTEMS
Before undertaking the design of a pipe system, it is necessary to assume:
*
- 1- The maximum temperature of the water leaving the heater when the outside temperature is the minimum for which the system is to be designed.
The drop in the temperature of the water while it is flowing through the radiator. 3. The arrangement of the pipe connecting the heater with the several radiators.