CHAPTER 41
1954 Guide
* = 10 Io&
where I = the sound intensity' in watts per square centimeter.
The reference intensity.is, IQ-16watts, per square centimeter, coinciding
with the reference pressure of 0.0002 dynes per sq cm or 2 X 10-4 microbar.
A microbar is the unit of pressure commonly, used in acoustics, one micro
bar being equal to one dyne per sq cm.
.'
The relationship , pf the decibel scale to sound pressure and sound in
tensity is shown, in Table 1. A stated sound level in decibels, under
standardized procedure, will thus be related to a threshold of t).0002 dynes
per square centimeter, or to a threshold of 10-16 watts per sq cm. The
standardization upon terminology, procedures and reference levels may be
found in Standards1 published by the American Standards Association, c
APPARATUS FOR MEASURING SOUND
, . The measurement of sound or noise is conventionally made by means of a sound-level meter2 consisting of a microphone,: an amplifier, a variable attenuator, weighting networks, and an indicating meter; which reads directly in decibels. The approved sound-level meter.must comply with the specifications of the American Standard for Sound Level Meters for .. Measurement of Noise and Other Sounds, Z24.3-1944, approved and published by the American Standards Association., The meter.is designed to indicate sound level above the standard reference level. Three measur ing networks are generally provided: (1) flat response, (2) 70 db network and (3) 40 db network. The .various networks, are approximations of the equal-loudness contours relating intensity and frequency sensation response of the normal human ear.1 Where there are'rio specific codes which specify the particular network to be used, general'practice would indicate use of the 40 db network for sound levels up to about 55 dbj the 70 db network for sound levels from about 55 db to 85 db, and the flat response network for higher levels. When sound level measurements are stated, the specific weighting network used, i.e., 40 db, 70 db or flat response, should always be reported. Complexity in design and calibration, and variations in component parts of the sound level meter impose some deviation from design objective response. Allowable" deviatibns in response or accept able tolerations recognized in the Standard, vary from 2 db in the 1000 cycle range to 5 db, or more, below 100 cycles arid above 1200 cycles
per second.
GENERAL PROBLEM OF SOUND CONTROL
The problem confronting the'air conditioning engineer is to design a
system which will operate without increasing the'noise level in the con
ditioned space. It is therefore necessary:
:
1. To determine the noise level existing without the equipment. 2. To ascertain the noise level which would exist if the equipment were installed
without sound control. 3. To provide as a part of the installation, sufficient sound control appliances and
treatment to reduce the sound level due to the installation to a sound level at least three decibels, and preferably five decibels, below that found in Item 1.
To accomplish this the engineer should have information of three kinds:
1. A knowledge of the noise levels currently considered acceptable in various
rooms, in order that he may have a basis on which to proceed.
11
Sound Control
907
Table 1. Decibel Scale vs. Sound Pressures and'Sound Intensities
Decibel Level
0 1 2 3 4
6 8 10 20 30
Pbessubb : dynes per sq cm;
Intensity
Decibel
watts per sq.cm. . Level .
Pbesbube . dynes per sq cm
0.000200 0.000224 0.000252 0.000282 0.000317
D00O X 1(T"
1.259 X 10-18 1.585 X 10-" 2.000 X 10-" 2.520 X 10-".
.... .40 50 60 70
80
0.000399.v 4.000 X 10-"
90
0.000503 ... ;6.310 X J0-," . 100
0.000631
i.ooo x;io~" ' 110
0.00200 ' 1.000 X 10-" 1 120
0.00631 ' 1.000 X 10"
0.0200 0.0631 0.200 0.631 2.00
6.31 . . 20.0.
'63.1 200.0 '. '
Intensity watts pereqcm
1.000 X 10"" 1.000 X':10"n1.000 X 10"10 1.000 X 10"* 1.000 X 10-8
1.000 X 10"7
i.ooo x i6" i.ooo x 10"*
1.000 X 10~*
i. a Knowledge ol the nature and intensity of the noise created by the various
parts of the equipment:
"
3. A knowledge of how, when necessary, to vary and control the noise level be tween the equipment and the conditioned, space.
In addition, the engineer should have sufficient information to predict the levels produced by noises which may. be transmitted by the duct
system from one conditioned space to another, or from an outside space to the conditioned space. In either case, the designer must know the prob able noise level at the point where the noise originates. From this he can compute the attenuation or transmission loss required , in order to bring this level down to that required in the conditioned space. If there is likelihood of direct transmission through a duct,: the attenuation required
may be computed as shown in section Noise Transmitted Through Ducts. If the transmission is through dividing wallsj it will be necessary to refer
to published data on losses through standard building constructions.2
Information concerning the sound levels created by ventilating and air conditioning equipment such as fans, motors, air washers and similar items, has not yet 'beeni completely established; However, numerous
manufacturers are in a .position to supply such data for. many , of their products. Additiprial information is being collected. Uniformity. in method of test arid'presentation of sound measurement data for fans, has been standardized in. the Sound Measurement Test Code for Centrifugal
and Axial Fans, developed by the National Association df Fan Manufac turers. The Code prescribes that the sound level shall be measured by the flat response network of the sound-level meter.. Readings on the 40 db.
and 70 db networks may also be taken and reported, but' the'flat response reading is required to comply, with the Code requirement. General -prac tice is to use the slow or damped needle reading of the meter. The.fast
r undamped needle ofthe. indicating meter generally reads one to two db lower than the slow or damped meter needle. The same Code prescribes
a method of determining the sound level reading at each Of- seven stations, spaced at 5 ft'from the'Outside Of the fan housing, and located in a hori zontal plane passing through the fan shaft. The sound level Of the fan 18 the average of the seven readings. The level so determined is valuable
Primarily for Comparative purposes rather than absolute values. : Of more
yalue to the design engineer would be the sound level at the fan outlet
and at the beginning of the distribution duct system.
.
The technique of sound measurement in a moving air stream of ap-