Document v16Y6rxGOZyaBwjM0E6yEKbjY
'Uoi
ilUU
December 19, 1975
Scottdale, PA 15685
Bear Mr. Uptcgraff:
I have received our laboratory report based on tbe Askarel samples sent to us from your 2500 KVA transformer, recently returned to you from the Atlantic Richfield Hanford Company at Richland, Washington. A copy of that laboratory report was sent directly to Mrs. Crowell at Uptegraff.
Your customer claimed that, their boble tests showed the power factor of the Askarel l'luid was too high. In this respect, I'd like to refer to our Transformer Askarel Inspection and Maintenance Guide, (enclosed) Bulletin No. IC/FP-38R, March, 1975, page 14:
It states, in part: "The power factor test normally used for the detection of contamination in mineral oil filled transformers is of little use for this purpose in Askarel filled transformers, due to the extreme effect of extraneous soluable polar materials."
Further down page 14 it states:
"The different behavior of A.skarel vs. mineral oil in these respects can be summarized as follows:
High power factor and low volume resistivity in transformer mineral oils are commonly regardod as "danger signals" that the oil has deteriorated and broken down chemically or excessive moisture is presont.
This is NOT TRbF of Askarel liquid insulation unless the dielectric breakdown voltage is lowoor the moisture content is high,"
I no actual tests of dielectric breakdown voltage and moisture content showed the following results:
WATER PCB-SP000000367
Roy H, Uptegraff It. b. Uptegraff Manf. Co.
Page 2
December 16, 1975
Jar No. 1
Jar No. 2
Now Fluid Spec.
Dielectric Strength, 25C
Water
38 KV 15
43 KV ' 15
35 KV minimum 30 maximum
Furthermore Mr. Uptegraff, our booklet continues on the top of page 15:
"Manufacturers of Askarel type transformers point out that it
is quite well known that Askarql transformers with initial power factor of the Askarel fluid in excess of 50 percent at room temperature and 60 HZ are giving satisfactory service life. However, there needs to be assurance that both dielec tric breakdown voltage and moisture are at satisfactory levels and do not show adverse trends."
As our tests show Mr. Uptegraff, dielectric strength and mois ture level on the two samples submitted, meet our specifica tions for new fluids.
Sincerely,
MAP/kao
Michael A. Petrilli Industry Sales Specialist Functional Products
Qi,3't5<t5
WATER PCB-SP000000368