INDUSTRIAL RISK INSURERS
PHILADELPHIA DISTRICT OFFICE 399 Market Street, Philadelphia, PA 19! 06-2 \\7 Tel: (215) 925-5050 Fax: (215) 925-5549
Hr. John Sovich B.F. Goodrich Company P.0. Box 400 Pedricktown, N.J. 08067
Dear Mr. Sovich:
July 5, 1990
K CEIVtlD JUL 09 1990
ILLS. INC. OUR 2r CENTURY
B.F. GOODRICH COMPANY PEDRICKTOWN, N.J. L0C. ID: 800083/727091
The following is a list of minor items which were noted at the time of my survey. A review or completion of all items is anticipated prior to the next survey. Completion of these maintenance type items should be considered to be part of the overall plant's fire safety, with items of greater importance
submitted as recommendations on our Loss Prevention Survey. Should there be any questions concerning these items, please contact the Philadelphia Office of this Association.
From the previous maintenance letter:
1. The fire door in Building No. 515, first floor, between the Abcov and bagging areas should be kept closed.
to
cn
o
Q)
2. The double fire doors in Building No. 547 should have guards provided to
protect them from being damaged or blocked open by stock. 3. Address the following items in Building No. 533.
_
BFG50813
a. The Make-up Room for the catalysts should have the pipe chases and holes on the first floor sealed with masonry material.
b. The air damper on the first floor of the Make-up Room should be replaced with a fire rated fusible link damper.
4. Building No. 534 - Some of the deluge sprinkler heads on the ground floor corridor may be obstructed by beams and duct work. Obstructed heads should be relocated.
5. The electric and diesel pump test stand should be equipped with an additional hose and nozzle support.
6. Remove the isobar C (Group 1A liquid) from the area next to the stripper column outside of Building No. 513.
KB
ThLs review was niadefor property Insurance purposes only. The information contained herein Is not meant to (mply that every possible hazard has been identified, or that no other hazards exist. IR1 specifically disclaims any warranty, or representation that compliance with any advice contained herein u><U make any premises or operations safe or healthful, or (n conxpliance with any law. mle, or regulation.
Mr. John Sovich -2- July 5, 1990
B.F. GOODRICH COMPANY PEDRICKTOWN, N.J. LOC. ID: 800083/727091
New items from the current survey:
7. Remove the water from the vapor detection light fixtures on the third floor of Building No. 531.
8. Provide a PIV Key in the emergency packet located in the Boiler Room Disaster Control Center.
9. Replace the fusible links on the inside of each personnel fire doors with an exposed fusible link. This problem exists mostly throughout Building No. 502.
10. Repair the three fire doors located in Building No. 541. One door is missing the top catch, the other two are difficult to open.
Since
Robert L. Moser, II Chemical Loss Prevention Representative
RLM/vt
CC: Mr. John McNamee Alexander and Alexander of Houston 5851 San Felpe P.0. Box 27128 Houston, TX. 77227-7128
Mr. David Hatch Risk International services 3560 West Market Street Suite 315 Akron, OH. 44313
Mr. Paul Gaydos B.P. Goodrich Company 6100 Oak Tree Blvd. Cleveland, OH. 44131
Mr. John Fletcher B.F. Goodrich Company P.0. Box 400 Pedricktown, N.J. 08067
i\5
g
g
BFG50814