Document ry2RMBvMn4Zq9JbVn671wYXq
1022
CHAPTER 48
1952 Guide.
-Table 6. Computation op Branch Size in Example 2
Fixtures No. and Kind
Fixture Units (From Table 2 and Note c)
Demand
(From Fiol 2) Gpm
3 x 6 = 18 } (2 x 2) = 3 i (3 x 1) = 2.25
23.25
38;
Pipe Site ` (From Fig.
4) In.
the computed pipe sizes for the fittings. For the purposes of this example assume
that the total equivalent length of the pipe fittings U 50 ft.
Then the permissible pressure loss per 100 ft of equivalent pipe is 12 X 100/(100 +
50) = 8 psi.
. ..
Assuming that the corrosive and caking properties of the water are such that'Fig.
4 for fairly rough pipe is applicable, a 2 in. building main will be adequate.
The sizing of the branches of the building main, the riserSi and fixture branches
follow the principles outlined. For example, assume that one of the branches of the
building main carries the cold water supply for 3 water closets, 2 bath tubs, and 3
lavatories. Using the permissible pressure loss of 8 psi per 100'ft, the size of branch
determined from Table 2 and Figs. 1 and 4 is found to be 1H in. Items entering the
computation of pipe size are given in Table 6.
COOLING WATER PIPING
. Water i3 veiy frequently used in refrigeration systems, cooling towers and other similar installations. In,designing the piping system of such
installations, the principles of hydraulics, as,:already outlined, are- em
ployed. Nevertheless, there are several practical items having particular application to cooling installations. They are Outlined in; the following
paragraphs, and it is important that the designer be familiar with them.
In choosing pipe material, the problem of corrosion should be kept in mind to prevent defects in the system. If the water does not have drastic corrosion characteristics, wrought iron or steel piping may be used; other wise, galvanized steel piping may be preferred. If sea water is used as the
circulating medium, it is advisable to use alloys such as admiralty metal in pipe and tubing. In refrigeration condensers where water is the cooling medium, iron pipe is commonly employed.
In regard to assembly, cast-iron flanges or welded joints are to be pre
ferred to screwed joints wherever possible.
*
- Valves used in circulating systems may be of the globe, gate, or angle
Table 7. Pipe Sizes for Cooling Towers*
Rated Tons op Reprig.
Cooling Water GPM
Pipe Sizes (No minal Inches)
. Inlet to Tower
. Outlet from Tower
3 to 5 7 to 15
20 25
35 50
10 to 18
20 to 45 65
86 115
170
if
2
2i 2i 3 3
M. 2
3 4 4' 4
75 100 150
200
250
225 300 450 600
750
5 6 56 58 68
8 '8
Water Services
1023
types.' If water is the circulating medium, brass valves are usually used. However, if the circulating medium is an electrolyte, such'as brine, then it is preferable to use valves made of the same material as the piping itself.
The friction loss in. the piping may be determined from Fig. 4 for fairly rough pipe. If the coolant is brine, a correction for the proper , density must be made. Experience indicates that'in sizing piping for codling sys tems, a pressure drop of the order of 2 to 3 psi per ItiO ft of pipe lengjth, and a fluid velocity of 3 to 8 fps, yield most economical results.
In the-case of cooling towers, the amount of circulating water is about 3 gpm per ton of refrigeration, when based on a design wet-bulb tempera-
Table 8. Maximum Daily (24-Hr) Requirements for Hot Water in Gallons
Apartments and
Private Homes
No. or Rooms
1
1
2
3 4 5. -
67
8 9
10 11
12
13 14
15 16
17 18
19 20
'60 70
80 90 . -. 100 120 140 160 180 200 ' --* ' -- -- -- -- -- -- --
--
--
Numbeb or Bathrooms .
23 4
^ .
--
120 . 140 160 180 200 220 240 260 280 300 -- -- --
-- -- ---
--
__ __
---
200 220 240 1 260 280 300 325 350 375 400
-- - --
-- --
--
__ _. __ __
__
250 275 300 340 380 420 460 500 540 580 620 __
'--
5
-
__ __ __ __ __ __ __ __ __
450 500 550 600 650 - 700 750 800 850
Hotels
Room with basin......... ........... ............ ..............................................................1' 10
Room with b&th---transient.............................................................................
60
Room with bath--resident.............................................................................................. 60
2 Rooms with bath..............................
80
3 Rooms with bath............................................................................
Public shower..................................................................................................................... 200
Public basins......................................................................................................................... 150
Slop sink___'............................. .................
........... .................... ............... 30
Office Buildings
White color worker (per person) Other workers (per person)........
Cleaning per 10,000 sq ft___
Hospitals-
IPer bed
2.0 4.0 30.0
80-100
tore of about 76 F. Table 7 gives pipe sizes frequently used for various sizes of cooling - towers, assuming a hot-water temperature of 95. F and a cold-water, temperature of 85 F.2
ESTIMATING HEATING LOAD AND STORAGE CAPACITY
The maximum daily and the maximum hourly hot water demand form the basis for the selection of the heater and the storage tank.
In general, two thirds of the total daily water consumption is hot water. For residential dwellings, a design value of about 20 to 30 gal per capita per day may be assumed, but it should be remembered that, the hot water used will depend on the number of rooms and the number of bathrooms in
100