Document rxzaeEdNrRe949jB3DV64yaZv
. ;-.r:
working at the mezzanine floor was wearing an approved
. other local mechanical exhaust at this floor appears to be ade-
i l^. L, - *
V: breeders are still without adequate local mechanical exhausts. ,:e\ur, according to Mr. Milner the company is working cn them.
Ti.-;r'- is a back drafting hood 23" x 13" for weighing of lead at the :-"orr,d floor. The top and two sides cf the hood are enclosed with a face velocity cf ISO fpm which is considered to be adequate.
An excessive amount of asbestos dust is produced when "Lodige" mixer is started. The lab report dated March 25,1974 shews a count of 2.4 fibres/cc higher than the TLV of 2 fibres/cc.
The dry mix discharge from "Lodige" is provided with a down draft rec tangular hood 36" x 8" exhausting at the rate of 400 cfm.
Ireform Machines: The two preform machines are provided with hoods for dumping and loading operations. These hoods are 18" x 9" each exhausting at the rate of 900 cfm. However, there is no hood for weighing and hand scooping.
The men working at these machines wear respirators. The fibre counts at these machines have been low.
tollinr machines: There is no local mechanical exhaust for dumping of mix into the hopper for the rolling machine. A small amount of asbestos dust was found to be disseminating into the general area.
A new hand roll machine was in operation during the visit. According to Mr. Milner this machine has been in operation for about 6 months due to a new contract and is not expected to run for more than 3 months. There is no local mechanical exhaust for the machine. The man does not wear a respirator.
Finishing Department: This department has several saws, grinders, and drills. Some of those checked for local mechanical exhausts are as follows:
FAME OF OPERATION OR EQUIPMENT
Do all Band Saw (Cutting brake
lining strip)
Strip I.D. Grinder* (18" wheel)
Scrip O.D. Grinder*
X-rMu:; Roller
S' 1 ;
i ; Mi
TYPE OF HOOD
(DIMENSION)
FACE VELOCITY FPM
Back drafting (4" x 3")
800
Back drafting (3" x 6")
Do\m draft (12" x 3")
no exhaust
J
Down draft (5" x C")
600 800
800
AIR VOLUME CFM 67
75 200
167
SPNY 001352