Document rxdry9q8gpyLkmqL3adedJDxq
Heat Cabinets
The Trane Company
Let Crosse, Wis.
Sec Pumps, page 766; Unit Heaters, page 679; Heating Specialties, pages 838, 839.
BRANCHES IN ALL PRINCIPAL CITIES
TRANE CONCEALED HEATING
Concealed Heating is recog nized as the modern method of distributing heat in homes, apart ments, office and public buildings. Trane as a pioneer in this field has developed the Concealed Heater and simplified the in stallation until the job of setting the unit in the wall and making the piping connections is com paratively 'easy.'" "Th'e installa tion can be made in about the same time it requires to set a radiator.
One of the big advantages of Trane Concealed Heating is in the adjustable stack which con nects the heating element with the outlet grille. This feature has entirely removed the neces sity of minutely measured wall openings and does away with the difficulty of making the installation. -The stack has a wide height range which gives a variety of capacities in a single unit.
%, % %Trane Concealed Heaters are made in three widths-- 3 5 and 7 in. The first
two fit in 2 x 4 in. and 2 x 6 in. walls respectively without furring. The heaters are made in the following lengths: 22, 30, 36, 42, 48, 54 in.
The grilles--the only part of the installation which can be seen--are cast aluminum in the Standard and Dutch Colonial Style. The Stamped Steel Style Grille is also available.
Heat Control can be obtained either through the use of a damper on the outlet grille or by a valve on the heating element. Heater is always accessible for inspection and can easily be removed without interfering with the plastering. Trane Heat Cabinets are ideal for homes already built where the owner wishes to have the advantages of convec tion heat but does not want to make the installation be tween the walls. Price compares favorably with cast iron radiator and shield.
654
The Trane Company
Heat Cabinets
Capacities of Trane Unit Heaters
AT 5 LB. STEAM PRESSURE FOR 60 CYCLE AND DIRECT CURRENT ONLY
Power--60 Watts--0 h.p.
No. 12 High Speed
1500 R. P. M.
485 C. F. M.
Inlet Air Temperature
50"
60"
70
Temperature Rise
88"
83"
78
Final Temperature
138"
143"
148"
B.t.u. Per Hour
46,000
43,400
40.600
Pounds of Con densate Per Hour
47
45
42
So. Ft. E.D. R.
192
161
170
MPower--160 Watts-- h.p.
Inlet Air Temperature .
50
60"
70"
Temperature Rise
69"
65"
62"
No. 15 High Speed
1140 R. P. M.
Final Temperature
119"
125"
132*
B.t.u. Per Hour
92.000
66,600
81,500
1280 C. F. M.
Pounds of Con densate Per Hour
96
' 90
85
Sq. Ft. ELD. R.
383
361
340
Power--240 Watts--% h.p.
Inlet Air Temperature
50*
60"
70"
Temperature Rise
66"
63*
59"
No. 18 High Speed
1140 R. P. M.
Final Temperature
. 116"
123.
129"
B.t.u. Per Hour
147,500
139.000
130.800
2060 C. F. M.
Pounds of Con densate Per Hour
153
. 145
136
Sq.Ft. EL D. R.
615
579
545.
Power--260 Watts--K h.p.
Inlet Air Temperature
50"
60"
70"
Temperature Rise
68"
64"
60"
No. 24 High Speed
1140 R. P. M.
Final Temperature
118'
124"
130"
B.t.u. Per Hour
212,100
200,000
188.400
2910 C. F. M.
Pounds of Condensate Per Hour
221
208
196
Sq.Ft. ELD. R.
885
834
785
Power--660 Watts--M h.p.
No. 24-A High Velocity
1140 R. P. M.
4070 C. F. M.
Inlet Air Temperature
50"
60"
70"
Temperature Rise
63
59"
56"
Final Temperature
113"
119"
126
B.t.u. Per Hour
275.000
260,000
244,000
Note.--AH air volumes based on dry air at 70 F.
655
Pounds of Con densate Per Hour
286
270
254
Sq.Ft. ELD. R.
II50"
1085
1020