990 CHAPTER 48 1950 Guide Fig. 8. Indirect Water Heater heating tubes are used, one end of the tube is usually expanded into a floating head to take care of expansion. The coils should be capable of easy withdrawal for inspection and for removal of scale. Instead of steam, the heating medium may also be hot water inside the tubes. Another method of transferring heat from a heating boiler to the domestic water is illustrated in Fig. 9. The water heater is generally a cast-iron shell within which there is located a spiral copper coil. Hot water from the boiler circulates inside the shell and around the coil, and returns to the boiler, while domestic water from the storage tank circulates inside the coil. The storage tank should be installed with the bottom of the tank as far above the boiler as possible. Horizontal, storage tanks of less than 18 or 20 in. diameter are not recommended because of the difficulty of preventing the hot . and cold water from mixing, and especially is this an important consideration when large quantities of water are withdrawn. In Fig. 10 the heat transfer surface is placed inside the boiler instead of in a separate vessel, but otherwise the operation .is similar to that of Fig. 9. This arrangement with vertical tank is commonly used for small domestic installations. Sometimes the heating element is located inside of the larger type fire tubeboilers andsmall residential boilers. In this casethe heat transfersurface is in the form of a number of straight copper tubes with rear U bends or a floating head, inserted through a special opening in the boiler. While the coil may be placed in the steam space above the water line of a steam boiler, it is usually placed below the water line. Long coils of small diam- Water Services. 991 eter tubing, immersed in the water, are widely used without storage tanks. The rate of flow through the coil is limited by the friction loss in the coil and by fittings and restrictions, so that the water attains the desired temperature in one passage through the coiL This arrangement is fre quently found in oil burner installations where the heating boiler,'either steam or hot'water type, is used to supply hot water during the summer. A thermostatic three-way mixing valve is frequently used to maintain a uniform temperature of the hot water supply to the plumbing fixtures. In order to reduce clogging by precipitated solids, water heating plants sometimes develop steam in a closed circuit, transferring the heat through a tubular heater to the domestic water. The water in the primary heater, exposed to the .high temperature of the fire, is repeatedly used and hence, has no appreciable-tendency to deposit scale, while the domestic water, heated by steam at a much lower temperature than that of the fire, also exhibits a much reduced tendency to precipitate dissolved salts. COMPUTING HEAT TRANSMITTING SURFACE The area of the inside surface .of a heating coil may be determined from Equation 1. 0 X 8.33(( - td A =.- PX(. (1) where A = surface area of coil, square feet. | Q = quantity of water heated, gallons per hour. (, = hot water outlet temperature, degrees Fahrenheit. 1, = cold water inlet temperature, degrees Fahrenheit. U -- coefficient of heat transmission, Biu per (hour) (Bquare foot) (degree Fahren heit logarithmic mean temperature difference). For copper or brass coils U = 240 (steam) and 100 (hot water); For iron coils U = 160 (steam) and 67 (hot water). la -- logarithmic mean of the difference between the temperature of the heating medium and the average water-temperature, and is approximately. t. - t. > temperature of the heating medium, degrees Fahrenheit. Equation 1 may be used to check the heating coil ratings under tempera tures other than those stated in the manufacturer's published ratings; Example 6. What area of copper transfer surface will be required to heat 70 gal of water per hour from 40 to-180 F with boiler water at 220 F? Solution. . (180 + 40)1 70 X 8453(180 --`40) ^ ' `"`L220------- i--J-110 A-------- IocTxTTo--"7;428qf\ For instantaneous submerged heaters the surface required will depend upon (1) the velocity of water in the tubes, (2) the boiler water tempera ture, (3) the inlet' water temperature, (4) the outlet water temperature, (5) the cleanliness of the coil surface, and (6) the condition of the boiler /