ST. VINCENT INFIRMARY LITTLE ROCK, ARKANSAS
MAYO MEMORIAL MEDICAL CENTER MINNEAPOLIS, MINNESOTA
For the past seven years, the Gypsum Association has conducted extensive re search on the performance of lath and plaster ceiling systems. The purpose of this research was to develop plaster con structions that would provide a high degree of crack resistance. The phase dealing with small suspended ceilings is now virtually complete.
At the outset, it was determined from field experience that some 21 "variables" should be studied for their possible influ ence on performance. Since each variable was studied in a group of 3 ceilings, the final program included 62 such groups, requiring 186 ceilings.
The time element for conducting such a large-scale program in a laboratory was considered unacceptable. Furthermore, there was merit in making the study under job conditions, provided accurate controls and evaluation were possible.
So, the "laboratory was taken to the job" ... to three large hospital projects, carefully selected for similarity as to con struction, room size, etc.
NEW SCHUMPERT MEMORIAL SANITARIUM SHREVEPORT, LOUISIANA
2
SGP 0003071
S'** < t t} njTMi. I
W(
PLASTER PERFORMANCE
A studv of the essential variables was duplicated in each of the three hospitals, separated geographically to provide some evaluation of the effect of climate. Except where noted, all lathing and plastering in this program was in accordance with the American Standards Association Standard Specifications A42.1 and A42.4 for Gypsum Plastering and Interior Lathing and Furring.
Since completion of plastering, the ceilings have been examined periodically and are still under observation. Although it is quite pos sible that future observations may slightly alter the current evaluation, definite trends and patterns have been established.
It should be emphasized that the conclusions here reported are based only upon the results of this study which is confined to suspended ceilings in rooms up to 20 square yards. It is reasonable to expect, however, that many of these observations are undoubtedlv pertinent to other lath and plaster constructions.
CEILING SCHEDULE SAND FLOAT 66 CEILINGS TROWEL FINISH 120 CEILINGS
LATH
Gypsum
PERIMETER
Restrained
Gypsum Metal Metal
Unrestrained Restrained
Unrestrained
AGGREGATE & PROPORTIONS
Wood Fiber (Neat) & 1:3 Sand
T-.2 - 1:3 Sand 1:2- 1:3 Perlite 1:2 - 1:3 Vermiculite
Same as above Same as above Same as above
From these extensive studies, it was found that the principal variables which affected resist ance to cracking were:
types of finish coats basecoat aggregates plaster to aggregate ratio tvpe of lath presence or absence of perimeter
restraint
PERFORMANCE RATING SCALE
Relative performance with respect to cracking is expressed on a scale of 10. This rating reflects the actual measured length of objectionable cracking per unit area of ceiling. A rating of "10" represents best performance, with virtually no cracking, while a rating of "0" represents the most extensive crack ing. The several ratings in this report have been calculated to show the effect of a particular funda mental variable, such as "restrained" versus "unre strained" construction. That rating, for example, was arrived at bv averaging the amount of cracking in the "restrained" ceilings, averaging the cracking
in all the counterpart "unrestrained" ceilings, and expressing the comparative result on the standard scale of 10.
Obviously, a single figure such as this cannot fully describe the condition of a ceiling without further qualification. In certain cases, the type of cracking was such as to make successful patching or conceal ment almost impossible. Conversely, some ceilings showed cracking that was readily covered with nor mal decoration (paint). This cracking was consid ered non-objectionable and was not included in calculating the results.
SGP 0003072
GYPSUM ASSOCIATION
THE EFFECT OF FINISH COATS
Of the 186 ceilings studied, 120 were finished with gypsum gauging-lime putty trowel finish, 60 with Keene's cement-lime putty sand float finish, 3 with
prepared gypsum trowel finish and 3 with hard Keene's cement-lime putty trowel finish.
I KEENE'S CEMENT-LIME PUTTY SAND FLOAT FINISH
This finish, consisting of 100 pounds of Keene's ce ment, 130 pounds of dry hydrated lime and 600 pounds Ottawa silica sand, was applied to 60 ceilings over gvpsum basecoat plasters aggregated with various pro portions of sand, vermiculite and perlite (also wood fiber scratch coat) on both gypsum lath and metal lath; also to ceilings with restrained and unrestrained perimeter construction. In all cases, these ceilings
developed an average of less than 5 inches of cracking per ceiling, with a rating of 10 points on the compara tive scale.
This phase of the test program thus shows that ceilings finished with Keene's cement-lime putty sand float finish have uniformly excellent resistance to cracking, in conjunction with any or all of the various plastering systems included in this series of 60 ceilings.
II TROWEL FINISHES
Another 120 ceilings were finished with gypsum gauging-lime putty trowel finish. In addition, 3 ceilings were finished with prepared gypsum trowel finish and 3 with Keene's cement-lime putty trowel finish. The results
obtained with the gypsum gauging-lime putty trowel finishes, in combination with each of the other princi pal variables, indicate a performance rating of 8.2 as compared to the rating of 10 for Keene's cement-lime putty sand float finishes.
THE REMAINDER OF THIS REPORT is devoted to ceilings having gypsum gauging-lime putty finish coats and to certain variables that affect performance of those ceilings. Composite ratings were calculated to show the over-all effect of certain variables as follows:
ll-a Plaster Aggregate and Proportioning
The opposite table is a summary of strength test data from 310 2-inch cube specimens made on the various projects. A minimum of 5 cubes was taken at the mortar box at each sampling. The tabulated figures represent the average compressive strength in pounds per square inch of all of the cubes made for each of the various aggregates and proportions thereof.
Composite performance ratings have been calculated from the results obtained with different groups of ceil ings (84 in all) in which the plaster aggregates and proportions are the only variables. That is, any one test group includes a number of ceilings in which the fol lowing types of plaster were applied over metal lath, and an approximately equal number of ceilings in which the same plasters were applied over gypsum lath. Here again, the composite figures represent a lumping of the results to show the over-all effect of a particular vari able; in this case the aggregate and its proportioning:
The excellent rating obtained with the strongest plaster combination, neat wood fiber scratch coat and sanded brown coat, illustrates the important effect of plaster strength in improving crack resistance.
AVERAGE COMPRESSIVE STRENGTH (psi) OF PLASTERS USED
TYPE OF PLASTER
Gypsum-Wood Fiber Gypsum-Sand Gypsum-Perlite Gypsum-Vermiculite
PROPORTIONS NEAT 1:1 1:1 Vl 1:2 1:2 Vl 1:3
2173 887 550
901 716 679 521 448 683 433 407 284
PERFORMANCE RATINGS
SCRATCH COAT
Neat Wood Fiber 1:2 Sand 1:2 Perlite 1:2 Vermiculite
BROWN COAT
1:2. or 1:3 Sand 1:3 Sand 1:3 Perlite 1:3 Vermiculite
RATING
10.0 8.9 8.1 6.3
In general, it can be concluded from these data that resistance to cracking is closely related to the strength of the basecoat plaster.
4 SGP 0003073
PLASTER PERFORMANCE SUMMARY of RESEARCH
il-b Metal Lath and Gypsum Lath
The relative performance characteristics of metal lath and gypsum lath are approximately equal when float finishes are used. However, when smooth trowel fin ishes are used their relative performance characteristics arc indicated bv the following composite ratings based on data from 73 ceilings. A trowel finish was used on all; but they included such variables as plaster aggre gate and proportion, as well as unrestrained and re strained perimeter construction.
PERFORMANCE RATINGS
Gypsum Lath Metal Lath
RATING
9.4
6.8
A marked superiority is thus shown for gypsum lath in the constructions represented bv these composite ratings, particularly when strengths of basecoat plasters were in the lower range.
||-c Restrained and Unrestrained Perimeter Construction
The term "'restrained perimeter construction" indicates that corncrite was placed in the perimeter angles of ceilings having gypsum lath. In the case of metal lath ceilings, it indicates that the ceiling lath was turned down at the wall, making the lath and plaster continu ous in the angles. The term "unrestrained perimeter construction" means that continuity of both the lath and the plaster at the ceiling and wall intersection was broken by plaster stops or other mechanical devices. Thus, freedom of movement was provided between ceiling and wall surfaces to minimize transfer of stresses.
Composite ratings have been calculated to permit a direct comparison of 24 unrestrained ceilings with 24 restrained ceilings (all from the same project), each set comprising the same variables of plaster base and plas ter aggregate. The superior performance of the unre strained construction is shown by these over-all ratings:
It must be concluded that ceilings with unrestrained perimeters are more resistant to cracking than those which are restrained. This is particularly evident where strengths of the basecoat plasters are in the lower range.
Methods Of Perimeter Unrestraint Used On Research Projects.
PERFORMANCE RATINGS
Unrestrained Perimeter Restrained Perimeter
RATING
9.0
6.6
ll-d Vermicuiite Aggregated Basecoat Piaster
The series of 15 ceilings consisting of gypsum gauginglime putty trowel finish, vermicuiite aggregated base coat plasters on metal lath and restrained perimeters, produced a composite performance rating of 1.8. The cracks were unusually wide and badly offset, beyond reasonable repair, and complete replacement of the ceilings was required.
Another series of ceilings, similar in all respects, except that gypsum lath was used, yielded a composite rating of 9.3. However, the rating was 3.8 for those ceilings
where the plaster was applied by the two coat method, but similar in other respects. These two coat ceilings also were replaced.
From the data it must be concluded that ceilings with vermicuiite aggregated basecoats applied to metal lath, or to gypsum lath by the two coat method, yield low performance ratings when gypsum gauging-lime putty trowel finishes are used; and that very good perform ance mav be expected when such basecoats are applied bv the three coat method to gypsum, lath.
SGP 0003074 GYPSUM ASSOCIATION
RECOMMENDATIONS FOR PLASTER PERFORMANCE
WITH RESPECT TO CRACK RESISTANCE
The Gvpsum Association has prepared certain observa tions and recommendations intended to provide the designer with information that will permit him to pre dict ultimate performance of lathing and plastering systems with a much higher degree of accuracy. They are presented as guideposts and are based upon the data acquired from the Association's recently completed research project, and volumes of the industry's research and recorded field experience, all as related to crack resistance of plaster.
Important though it is, the proper selection of systems and materials must be supported by adequate construc
tion details and definitive specifications. The contractor and mechanic must know precisely what is wanted. Further, competent field inspection is highly impor tant to assure the designer of compliance with his expressed intentions.
These guideposts are not intended to be all inclusive. Nevertheless, the basic design principles that influence performance are quite clear. A knowledge of their rela tive contributions to performance will more accurately reflect the degree of integrity that is expected of the plaster surface. The important design principles and their interrelationship are here enumerated.
THE FINISH COAT OF PLASTER
As used in combination with various lath and plaster systems, the finish coats of plaster exhibit a wide range of performance. Hence, selection of the finish coat becomes very important.
Sand Float Finishes (Keene's cement or gypsum gauging with lime putty and sand) as compared to smooth trowel finishes provide a much higher factor of safety against cracking. They require a lesser degree of rigidity and strength in the lath and basecoat plaster, and we recom mend the use of such finishes for maximum crack resist ance. The description of the basic sand float finishes are found in paragraphs 7.40, 7.50, 7.60 of the American Standards Association Specification A42.1, 1955.
Acoustical Plasters and certain texture finishes are known to be highly resistant to cracking and are considered to be equal to sand float finishes in that respect.
When vermiculite basecoat plaster is used over metal lath, or over gypsum lath by the two coat method (double-up), only sand float finishes or acoustical plasters are recom mended.
Smooth Trowel Finishes such as gypsum gauging-lime putty require a much higher degree of rigidity and strength in the lath and basecoat plaster for good visual perform ance. When the use of high strength basecoat plasters is impractical, consideration should be given to the elimina tion of restraint at the perimeter angles or the selection of a more rigid lath such as gypsum lath, or both, to the degree that is shown in the accompanying table (P. 8). They help to compensate for the lower strength of some basecoat plasters.
The resistance of gypsum gauging-lime putty trowel fin ishes to cracking, particularly to check cracking, can be increased by the addition of fine aggregate. The use of not less than Vi cubic foot of fine silica sand or perlite to each 100 pounds of gauging plaster or Keene's cement, increases the factor of safety in trowel finishes.
The Gypsum Association recommends the fine aggregate proportioning with gauging plaster or Keene's cement when gypsum-lime putty trowel finishes are applied over lightweight aggregate basecoats.
THE PIASTER BASE
The rigidity of the base to which the plaster is applied is an important factor in crack prevention. Under com parable circumstances gypsum lath usually provides a higher degree of resistance to cracking than does metal lath. Under certain conditions the selection of lath is not critical, but when the design calls for a plaster
basecoat in the moderate to low range of strengths, a smooth trowel finish or restrained perimeters, the selec tion of the lath often becomes a determining factor in resistance to cracking. The relationship of these vari ables of design, as they affect visual performance, are shown in the accompanying table (P. 8).
SGP 0003075 6
PLASTER PERFORMANCE
RECOMMENDATIONS
THE PLASTER BASECOAT
Under comparable circumstances crack resistance is closely related * to the strength of basecoat plasters, the higher ranking basecoat strengths generally providing a higher degree of resistance. The strongest basecoat plaster is wood fiber scratch with sanded brown, fol lowed in order by basecoats with sand, perlite and vermiculite aggregate, proportioned as indicated below. If good performance is to be expected of intermediate or low strength plasters, extreme care must be directed
to selection of the finish coat and lath, and to the pos
sible need for elimination of restraint at the perimeter angles. Experience and research prove the case for strong basecoat plasters where a high J< grct of surface integrity is to be realized.
For these reasons the Gypsum Association recommends the following proportioning of aggregate to plaster, regardless of whether it is aggregated on the job site or in the factory:
a. Not more than 2 cu. ft. of lightweight aggregate to 100 pounds of gypsum, ex cept over masonry where the propor tioning should not exceed 3 cu. ft. of lightweight aggregate per 100 pounds of gypsum. This proportioning is at variance with, and yields a stronger plaster than that permitted by Section 3.00 of Amer ican Standards Association Specification A42.1, 1955.
CEILING PERIMETER CONSTRUCTION
Integration of walls and ceilings at the perimeter angles becomes very significant under some circumstances. Differential movement is always a factor, its extent being governed by the building's rigidity and the cli matic changes. The performance of lath and plaster depends upon the extent of such movement and the ability of the wall and ceiling surfaces to move inde pendently without transfer of undue stresses from one to the other, and other factors such as the finish coat, the lathing base and the strength of the plaster. It is believed, however, that restraint in the vertical angles
b. Not more than 2 cu. ft. of sand (12 shovels) for scratch coat and not more than 3 cu. ft. (18 shovels) for brown coat to 100 pounds of gypsum; except over masonry where proportioning should not exceed 4 cu. ft. of sand per 100 pounds of gypsum; and except over gyp sum lath for two coat application where proportioning should not exceed 2V2 cu. ft. of sand (15 shovels) per 100 pounds of gypsum.
of lath and plaster systems is less significant than in the perimeter angles of ceilings, and that performance in partitions is dependent primarily upon the other factors.
We recommend that serious consideration be given to the use of details that will help to eliminate restraint (continuity of lath and plaster) in perimeter ceiling angles where differential movement is anticipated, par ticularly where trowel finishes are indicated or the rigidity and strength of the lath and basecoat are in the moderate to lower range.
LARGE CEILINGS
In addition to perimeter consideration, large unbroken ceiling areas should be divided by relief joints. The
maximum recommended distance between such joints is 60 feet with a maximum undivided area of 2400 sq. ft.
SGP 0003076
GYPSUM ASSOCIATION 7
RELATIVE PERFORMANCE OF LATH AND PLASTER SYSTEMS
WITH RESPECT TO CRACK RESISTANCE
It must be recognized that performance of lath and plaster systems, like many other building constructions, cannot be predicted with complete accuracy. However, it is believed that a more accurate prediction can now be made, and that a knowledgeable and intelligent selection will more nearly provide the required visual characteristics of the plaster surface.
To assist the designer in this matter the accompanying table shows the anticipated relative performance of numerous lath and plaster constructions. It has been compiled from the recently acquired research data, volumes of other research, and the industry's long labo ratory and field experience. Except as noted herein it is based upon full compliance with the provisions of
American Standards Association Specification A42.1-4, 1955.
Obviously, plaster performance is affected by several factors, other than the basic variables considered in these recommendations, such as extreme weather con ditions, lack of ventilation, thermal shock, unusual framing, etc. The standard precautions with respect to such factors should always be observed.
In compiling the table of Relative Performance, the absence of such unusual conditions is assumed. The table represents the Gvpsum Association's best judg ment of the relative resistance to cracking of the prin cipal systems of lathing and plastering.
PERFORMANCE
EXCELLENT
RESTRAINED CONSTRUCTION
LATH BASE
PLASTER BASECOAT
FINISH COAT
GorM
WF F
UNRESTRAINED CEILING CONSTRUCTION
LATH BASE
PLASTER BASECOAT
FINISH COAT
G or M
WF F
GorM
SF
G
S or P
F
G or M
WF T
G ST
M SF
GOOD
GorM WF T
G2
S or P
F
G pF
G VF
G ST G2j^| S F
M PF G2 orM S T
G VF
G
P or V
T
G2 orM p F
M VF
G2 orM S T
G pT
ACCEPTABLE
G2 or M V F
G2 V F
G
VT
G2 orM P T
G2 orM p T
NOT RECOMMENDED
G2 or M
V
G--Gypsum Lath - 3 Coat Plastering G2--Gypsum Lath - 2 Coat Plastering M--Metal Lath - 3 Coat Plastering WF--Neat Wood Fiber Scratch and Gypsum Sanded Brown
T G2 orM
S--Sanded Plaster P--Perlited Plaster V--Vermiculited Plaster F--Sand Float Finish T--Smooth Trowel Finish
-1.
.. ' N V- "A
V
T
NOTE: All proportioning of basecoat and finish coat plaster as recommended herein.
GYPSUM ASSOCIATION * 201 N,, Wells Street Chicago 6, Illinois
SGP 0003077
Recommended Practices for Construction of Ceilings With Gypsum Lath, Metal Lath and Plaster
GENERAL For normal job conditions the Gypsum Associa tion recommends that lath and plaster be applied in strict accordance with the following specifications:
A42.4 Standard Specifications for Interior Lathing and Furring Gypsum Association's "Recommended Specifications--Gypsum Plastering. " These specifications reflect minimum require ments for normal job conditions and are inadequate for abnormal or unusual job conditions, such as: 1. Unventilated attic or plenum space. 2. Insulation supported by the lath prior to plastering. 3. Lath supported by edge clips only under high humidity conditions. 4. The wetting of gypsum lath before plaster ing or wetting the scratch coat over metal lath. 5. The use of excessive water in the plaster mix. 6. Excessive aggregate proportioning in the plaster mix. 7. Thin basecoat plasters. 8. The use of water in darbying plaster. 9. Slow setting plaster. 10. Application of acoustical plaster to wet basecoat plaster. For these unusual conditions the Gypsum Associ ation recommends that the minimum requirements of these specifications be supplemented by the fol lowing procedures:
VENTILATION The space above the ceiling shall be ventilated so that the ratio of total net free ventilating area to the area of the ceiling shall not be less than 1 to 150. Location of vents shall provide positive venti lating action. If ventilation does not meet this requirement, plaster shall be applied by the threecoat method.
\
INSULATION Where insulating batts, blankets, blown wool, or fill insulation is installed over the gypsum lath prior to the application of the basecoat plaster, the mois ture evaporating from the plaster may condense within the insulation or on the underside of the vapor barrier. Therefore, wherever possible, insula tion should be installed after the plaster has set and dried. When insulation is installed before plastering, three-coat work is recommended and the scratch coat should be allowed to partially dry before applying the brown coat.
CLIPS When the lath is attached to ceilings by clip; providing edge support only, three-coat work is required; and, under conditions of high humidity, the scratch coat should be allowed to partially dry before applying the brown coat. Under high humid ity conditions, the use of butt clips and center board clips to further reinforce the lath attachment is preferred.
WET LATH Wetting of lath prior to plastering reduces suc tion of the lath and reduces plaster strength. The lath. (or the scratch coat) shall never be wetted before plastering.
PLASTER--WATER RATIO Basecoat plaster slump should not exceed 4 inches when tested in a 2" x 4" x 6" cone at the mixer. This slump standard is based on plaster mixes which should never exceed proportions recommended by the Gypsum Association.
AGGREGATE PROPORTIONING The use of high aggregate ratios reduces plastei strength. Aggregate proportions shall meet the re quirements of those recommended by the Gypsum Association.
SGP 0003078
LP 163
4
Recommended Practices for Construction of Ceilings
With Gypsum Lath, Metal Lath and Plaster
BASECOAT THICKNESS Application of a thin basecoat plaster seriously reduces the strength of the ceiling. The basecoat plaster shall be applied to full thickness as required by "Recommended Specifications--Gypsum Plaster ing" especially where an acoustical plaster finish is used.
WATER DARBYING Use of water in darbying plaster increases the water-plaster ratio and reduces plaster strengths. Water should never be used for darbying and only sparingly for floating.
SLOW SET PLASTER The setting time of plaster shall not exceed 4 hours. Faster set can be obtained by adding small amounts of ground raw gypsum to the plaster mix. Or, a controlled fine spray of 5% aluminum sulfate solution can be applied to the plaster after applica tion on the ceiling to obtain a faster set.
ACOUSTICAL PLASTER Acoustical plaster should never be applied to a wet basecoat. The basecoat plaster shall be dry prior to application of acoustical plaster. If suction of the basecoat plaster must be adjusted to properly receive the acoustical plaster, care shall be exer cised to avoid the use of excessive water.
I
SGP 0003079
For ALT, PLANT MANAGERS
BESTWALL GYPSUM COMPANY
April 10* 1963
Paoli Laboratory
Subject?
Recommended Practices for Construction of Ceiling with Gypsum Lath & Plaster Co C. Shuttleworth/md
Attached please find two copies of the Gypsum Association bulletin, covering recommended practices for plastering on gypsum lath on ceilings0
Please keep one of these and give the other one to your Quality Supervisor*
Attachment