American Society of Heating and Ventilating Engineers Guide, 1928
Chimneys recommended for larger boilers 15 to 250 hp. are propor tioned in accordance with the report made by a joint Committee of the American Boiler Manufacturers Association and Stoker Manufacturers Association and approved by these organizations. The sizes are given in Table 2.
Table 2. Height of Stack for Average Installations (Sea Level) Forced Draft Stokers
100 0.15 0.18 0.10 0.43
80
150 0.15 0.4
0.10 0.65 112
200 0.15 0.65 0.10 0.90 145
250 0.15 0.9 0.10 1.15 178
300 . 0.15 1.20 0.10 1.45 220
Diameter of Chimney in Inches for Horizontal Return Tubular Boilers
Nominal H. P.
15 20 25 30 35 40 50 60 75 90 100 115 125 150 175 200 210 225 250
100% Rating
13 14 16 17 18 19 20 21 23 25 26 27 28 30 32 33 34 35 36
150% Rating
14 16 18 19 20 21 23 24 26 28 29 31 32 34 36 38 38 40 41
200% Rating
17 18 20 21 22 23 25 27 29 31 33 34 35 38 40 43 44 45 47
Height of Stack in Feet--For Sea Level and
60 deg. fahr. Outside Temp. Assumed Fric tion Loss in Stack 0.1 in. per 100 ft.
Draft at
100%
Base of Stack Rating
150% Rating
200% Rating
0.12 0.15
0.20 0.25
0.30 0.35 0.40 0.45 0.50 0.55
0.60 0.65 ____ ____
___
21 22 25
26 28 30
35 37 41
43 46 51
52 56 61
60 65 71
69 74 81
78 84 91
86 93 101
95 102 111
104 112 122
112 121 132
___ :__
___ ___
.
____
_______ --
___
Data on Which Tables are Based
Rating............ Efficiency___ CO,................
100% 65% 8%
150% 65% 9%
200% 63% 10%
Stack Temp, deg. fahr................. 450 500 550
Lbs. of Gas................ . 85 77- 73
Average Friction Loss Through Boilers
Per Cent Rating.............
100
150
200
250
Loss Ins., Water............. 0.1to0.3 0.2to0.6 0.3 to 0.9 0.5 to 1.4
300 0.7tol.9
", Friction loss through boiler varies according to construction. For Furnace Draft.--Allow 0.15 for forced draft. For Natural Draft 0.35 in. or higher should be used
depending upon rate of combustion and fuel used. For Breeching Friction Loss.--Allow 0.05 in. for each right angle bend and 0.1 in. per 100 ft. of length.
Cross sectional area should be 20 per cent larger than that of stack.
162
Chapter VII--Steam and Hot Water Heating Boilers
Height of Stack in Feet For Sea Level and 60 deg. fahr. Outside Temperature and 0.1 in. Friction Loss per 100 ft.
Total Draft Required In. for Furnace Boiler and Breeching
Per,Cent of Boiler Rating 100 150 200 250
300
0.3 56
0.4 74 69
0.5 93 86 81
0.6
111 103
97
0.7 130 120 113 108
0.8 148 138 129 123
0.9 155 145 139 132
1.0 172 161 154 147
1.1 190 177 170 162
1.2 194 185 176
1.3 209 200 191
1.4 226 2i6 206
1.5 231 221
1.6 236
1.8 265
Assumed Flue Gas Temp................... 500 550 600 650 700
Correction for Altitude
Height Above Sea Level (Ft.)
Ratio Increase in Diameter
0 1,000 2,000
4,000
6,000 8,000 10,000
1.000 1.015 1.030 . 1.063
1.096 1.130 1.165
Ratio Increase in Height
1.000 1.046 1.097 1.205 1.321 1.456 1.612
The principal factors which affect the loss of . draft through the fuel bed according to J. G. Mingle,1 are:
1. Character of fuel burned,
2. Amount of fuel burned per square foot of
grate surface per hour, or the rate of com
bustion.
-
The loss of draft through the boiler is affected mainly by:
1. Type and size of boiler, 2. Rate of operation.
The required height of a chimney is affected by the following:
1. Character of fuel burned, 2. Rate of combustion,
1 Draft and Capacity of Chimneys.