10.Chapter
Chimneys and Draft Calculations
where
Dt = theoretical draft intensity created by pressure transformer, inches of water. hi = draft loss due to friction in pressure transformer, inches of water. hp = draft loss through the fuel bed, inches of water. fcB = draft loss through the boiler and setting, inches of water. liBr = draft loss through the breeching, inches of water. hv = draft loss due to velocity, inches of water. hsd = draft loss due to bends, inches of water. he = draft loss due to contraction of opening, inches of water. ho = draft loss due to enlargement of opening, inches of water. hE = draft loss through the economizer, inches of water. hR = draft loss through recuperators, regenerators, or air heaters, inches of water.
The left hand member of Equation 14 represents the total amount of
available draft created by the pressure transformer, that is, the natural draft chimney, Venturi chimney, or fan, and is equal to the theoretical intensity less the internal losses incidental to operation. The right hand
i t-
member represents the sum of all of the various losses of draft throughout
the entire boiler plant installation outside of the pressure transformer itself. The left hand member expresses the available intensity and is :
analogous to the head developed by a centrifugal pump in a water works
system, while the right hand member expresses the required draft in
tensity and is analogous to the total dynamic head in a water works v system. For a general circulation of gases
V
where
Da = Dt
Da -- available draft intensity, inches of water.
(15) v
i
y
Dr = required draft, inches of water.
i :.
The draft loss through thefuel bed (hp), or the amount of draft required to effect a given or required rate of combustion, varies between wide limits and represents the greater portion of the required draft. In coal-fired installations, the draft loss through the fuel bed is dependent upon the following factors: (1) character and condition of the fuel, clean or dirty; (2) percentage of ash in the fuel; (3) volume of interstices in the fuel bed, coarseness of fuel; (4) thickness of the fuel bed, rate of combustion; (5) type of grate or stoker used; (6) efficiency of combustion.
; 'v
There is a certain intensity of draft with which the best results will be obtained for every kind of coal and rate of combustion. Fig. 8 gives the intensity of draft, or the vacuum in the combustion chamber required to burn various kinds of coal at various rates of combustion. Expressed in
other words, these curves represent the amount of draft required to force the necessary amount of air through the fuel bed in order to effect various rates of combustion. It will be noted that the amount of draft increases as the percentage of volatile matter diminishes, being comparatively low for the lower grades of bituminous coals and highest for the high grades and small sizes of anthracites. Also, when the interstices of the coal are large and the particles are not well broken up, as with bituminous coals, much less draft is required than when the particles are small and are well
r j\ sPi
|` I
h
196
with bituminous slack and the small sizes of anthracites. In
brokeniup.
loss through the fuel bed increases as: (1) the per-
generai, ui ;ie matter diminishes; (2) the percentage of fixed carbon
centage oi ^ ^lickness of the bed increases; (4) the percentage of ash increase; w thg voiume of the interstices diminishes.
m?ea Wine the preliminary assumptions for the draft loss through the due allowances should be made for a possible future change in
the grade of fuel to be burned and also in the rate of combustion. A value
tautr l Recommended Minimum Chimney Sizes for
ffiBM Am
Furnace Capacitt
inSqInor Leader
PlPB
Steam
BOILEB Capacitt
Sq Ft
or Radi* ATION
iooo
590 690 900 900 1,100 1J00 1,940 2; 130 2,480 3,150 4,300 4,600 5,000 5,570 5,580 6,980 7,270 8,700 9,380 10,150 10,470
Hot Water Hbatbb Capacitt Sq Ft or Radi
ation
973 1,140 1,490 1,490 1,820 2,800 3,200 3,520 4,090 5,200 7,100 7,590 8,250 9,190 9,200 11,500 12,000 14,400 15,500 16,750 17.250
Nominal Dimen sions op Fibs Clat
Lining in Inches
Rectangular Flub
Actual Inside Dimensions of Fire Clay
Lining
in Indies
Actual
Area 8q In.
8^x13 7 xllH 81
13x13 11)4x11)4 127 8Mx 18 6)4 x 16)4 110
13x18 11)4 x16)4 183
18x18 15)4x15)4 248 20x20 17)4x17)4 298
20x24 24x24
17x21 21x21 24 x24b
357 441 576
24 x 286 672 28x286 784 *
30 x 306 900 28x326 896
Round Flub
Inside Diam eter of
lining
in Inches
Actual
Area Sq In.
10 79
12 113 15 177
18 254 20 314
22 380 24 452
27 573
Height in Ft Above Grate
35
40
45 50
55 60 65
This table is taken from the A.S.H.V.E. Code of Minimum Requirements for the Heating and Venti lation of Buildings (Edition of 1929).
^Dimensions are for unlined rectangular flues.
should be selected for this loss which will represent not only the highest rate of combustion which will be encountered, but also the grade of coal which has the greatest resistance through the fuel bed and which may be burned at a later date.
In powdered-fuel and oil-fired installations, there will be no draft loss through the fuel bed since there is none and, consequently, this factor becomes zero in the general draft equation. All other factors being constant, the height of the chimney in installations of this character will he less than the height in coal-fired installations, and in the case of mechanical draft installations the driving units need not be as large since the head against which the fan is to operate is not as great in the former as in the latter.
197