CHAPTER 15
1955 Guide
For burning rates from 100 to 1200 lb coal per hour H = 0.03 B + 24
where
H = minimum setting height, inches, measured from dead plates to crown sheet for steel boilers. For cast-iron boilers height may be i H..
B = burning rate .coal per hour, pounds.
Standards for minimum firebox dimensions and base heights have been formulated by the Stoker Manufacturers Association as shown in Fig. 11.*
In considering these recommendations, it should be understood that they show the average recommended minimum. There are many factors effecting the proper application of stokers to various types of. boilers and furnaces, and, in certain instances, setting height or firebox dimensions shown in the standards may be modified without impairing performance. Such modification will depend upon the experience of the installer or de-
Automatic Fuel Burning Equipment
369
or hot water heating System, a piping and pick-up factor of 1.33 is commonly used in sizing the stoker, but this factor should be increased at times due to unusual conditions.
The heat delivery from the stoker of the siriallest household type to the largest industrial unit can be regulated accurately with fully automatic controls. The smaller heating applications are controlled normally by a thermostat placed in the building to be heated: Limit controls are supplied to prevent excessive temperature or pressure from being developed in the furnace or boiler, and refueling controls are used to maintain ignition during periods of low heat demand. Automatic low water cut-outs are recorrimended for use with all automatically-fired steam boilers. : (See Chapter 39.)
DOMESTIC OIL BURNERS
Fig. 11. Suggested Minimum Firebox Dimensions and Base Heights
For reference in selecting or designing boilers and furnaces for stoker firing. - Dimensions shown are for net inside clearance at grate level using coal with heating value of not less than 12,000 Btu per pound. Under certain conditions smaller fireboxes will permit satisfactory performance but these dimensions are preferred normal minimums.
signer with a particular stoker, the type of fuel used, arid the construction
of the boiler or furnace.
,
Installation of stokers (particularly smaller sizes) on the side of the
boiler or furnace will sometimes facilitate clinker removal.
'
Rating and Sizing Stokers
The capacity or ratirig of small underfeed stokers is usually stated as
the burning rate in pounds of coal per hour. Codes for establishing uni
form methods of rating anthracite and bituminous coal stokers have been adopted by the Stoker Manufacturers Association.*
The Association also has adopted a uniform method of selecting stokers
that is published in convenient tables and charts.* The required capacity
of the stoker is calculated as follows:
..
Load (Btu per hour) Heating value of coal (Btu per pound) X overall efficiency of
stoker and boiler or furnace
Stoker burning rate eoa^per hour)11
In determining the total load placed on a stoker-fired boiler by a steam
oil for the combustion process; atomization, and vaporization. The simpler types of burners depend upon the natural chimney draft for supplying the air for combustion. Other burners provide mechanical air supply or a combination of atmospheric, arid mechanical. Ignition is accomplished by an electrical spark or hot wire, or by an oil or gas pilot. Some burners utilize a combination of these methods. Continuously operating burners may use manual ignition. Burners of different types operate with lumi nous or non-luminous flame. Operation may be intermittent,, continuous
"nth high-low flame, or continuous with graduated flame.
Classification of Burners
. Domestic oil burners may be classified by type of design or operation
into the following groups: pressure atomizing or gun, rotary, and vapor
ing or pot. These are further classified as mechanical draft, and natural
draft.
Pressure Atomizing (Gun Type) Burner
Gun type burners are usually designed to bum No. 1 or 2 grade fuel:oil. Iney may be divided into two classes: high-pressure and low-pressure