548 CHAPTER 25
V, Flo. 5. .Remote Flooh Ttpb Room
., :.;
Unit AibConditionbb -
... 1950 Guide
Unit Air Conditioners and Unit Air. Coolers
549
should be used if face velocities exceed 500-to 530 fpm, unless adequate means of catching the droplets are provided.
When air is drawn upward through dehumidifying coils, as . in spine
vertical units, water is entrained within the fins and held"in suspension..
This increases the resistance pressure against which the blower operates,
and results in wide variation in air volumes handled between dry and wet
coil conditions. Some unit manufacturers have so designed vertical
units that the air passes through the coils horizontally in order to over
come this 'difficulty.
..................
Heating Coils. Heating coils of unit air conditioners are'usually con-' ventional blast coils, and can be obtained with or without non-freeze steam distribution features. They usually match the cooling coils in, face area, and are one or two rows deep depending on the heating requirements: Where; coils-ate selected for hot water and have'more than two rows of tubes, the air resistance and the space requirements of the total number of, rows of cooling andheating coils should be carefully checked.
'Humidification. Spraytype 'humidifiers are -Usually used-in-remote
systems, but in some cases' pan type humidifiers or steam humidifiers
are also used. Some condensation on the inside of the unit casing may
occur with possible water damage if the unit is located in a cold space
without adequate insulation: Spray type humidifiers- should be located
so that nQ carryover of moisture.occurs.' . !
,
Filters;v; It is almost axiomatic-that all Units, should have filters. Some small Suspended units of T ton capacity or less, with.low coil face velocities and propeller fans, are equipped.,.only with lint screens or operate without filters, butin them-thfe coils 'must be.periodically,.cleaned and there is con
stant danger of clogging of, the drain, with the possibility of water damage. Filters used are usually 'of the throw-away type, .although cleanable filters are available for most of the: larger , units, y: Care should.be taken to insure adequate filter surface, since the cross-sectional area of the unit-is seldom adequate for filter area. V-shaped or staggered filter arrange ments: are quite commonly used to increase filter area.
Motors. In some units where the motor is-mounted inside, adequate access for maintenance and clearance for tightening belts are imperative. When motors are mounted in this manner, the heat equivalent of the motor input must be. added to the heat load to be absorbed by the system, and this requires a -lower exit air temperature at the coils. '. Usually, however, the motor is located outside of the casing where it is'readily, accessible for service. In .this case, only.the.brake horsepower, required by the fan is
, transformed into heat to'be included in the load calculations:"'.j
iln- either -application,- motors should .be. selected with .adequate-horse power to handle the design volume of- air against the -resistance of the system when the coils -are. wet, and then checked against the possible horsepower requirements for the increased volume of air obtained when the
coils are dry:. ..
.
; . : . :, ,
7; y. SOUND ISOLATION i
Both suspended and vertical floor mounted units can transmit vibra
tion through the supports. Wherever such transmission of sound might be objectionable, tlie: supports should be isolated-through rubber-in-shear or'other sound deadeners (for design of suitable sound deadeners see sec tion Controlling Vibration from Machine Mountings in Chapter 40).
1
tlti