TABLE 36-A
A GUIDE TO VENTILATION RATES FOR TYPICAL INDUSTRIAL EQUIPMENT Federal, State, or Local Regulations Should Be Followed Where Higher Ventilation Rates Are Required
Operation
Abrasive blast rooms (sand, grit, or shot)
Abrasive blast cabinets
Asbestos Carding Spool winding
Type of Hood
Ventilation Air Flow
Usual Transport Velocity
(fpm)
Tight enclosure with air inlets (usually in roof)
Tight enclosure with access open ings
60-100 fpm downdraft (long rooms of tunnel proportions 100 fpm crossdraft)
20 air changes per minute but not less than 500 fpm through all openings
3.500 3,500
Enclosure Local hoods
800 elm per machine SO cfm per spool
3,000 3,000
Bagging Open bag top
Barrels-Drums (filling or removing matenal by scoop)
Booth or enclosure (provide spillage hopper)
Local hood
Paper bags-- TOO cfm per sq ft open area
Cloth bags-200 cfm per sq ft open area
100 cfm/sq ft of container cross section
3.500 3.500 3,500
Booth
100 fpm at face
3,500
Belt conveyors
Hood at transfer point
Belt speeds less than 200 fpm--350 cfm per foot of belt width, but
not less than 150 fpm through open area Belt speeds over 200 fpm--500 cfm per foot of belt width but not less than 200 fpm through open area
3,500
Remarks
Many codes specify mini mum down draft of 80 fpm
See references for details and other operations
Hood with 1-in slot ex tending 120 to 180 deg container Does not con fine spillage
Confine spillage--also recom mended for container up setting