American Society of Heating and Ventilating Engineers Guide, 1929
engineer and must be well built to sustain such a heavy load and the height is such as to produce considerable draft to offset unfavorable weather conditions, etc. Chimneys in this class produce about 0.00945 in. of theoretical draft per foot of height in zero weather with 600 deg.
in the stack. Chimneys recommended foj larger boilers 15 to 250 hp. may be pro
portioned in accordance with the report made by a joint Committee of the
Table 3. Chimney Sizes for Low Pressure Heating Boilers and Warm Air Furnaces
Warm
Air Furnacb Capacity
in
Lbader Pips
Sq. In.
Steam Boiler Capacity
Sq- Ft. OF
Radia
tion
Hot Water Heater Capacity
Sq. Ft.
of
Radia
tion
Nominal Dimen
sions
of
FireClay| Lining In.
Rectangular Flue
Actual Inside
oiDimensions Fire Clay Lining In.
Actual Area
Sq. In.
Effec tive Area
Sq. In.
Round Flue
Inside Diameter
of Lining
In.
Actual
Area Sq. In.
Height in Ft. from Grate-
790 1000
590 690
900 900
1100 1700 1940 2130 2480 3150 4300 4600 5000 5570 5580 6980
7270 8700 9380 10150 10470 11800 14700 17900
973 1140 1490 1490 1820 2800
3200 3520
4090 5200 7100 7590 8250 9190 9200 11500
12000 14400
15500 16750 17250 19500 24300
29500
8)4x13
13x13 8)3x18
13x18
18x18 20x20
20x24 24x24
7x11)4
11)4x11)4 6)4x16)4'
11)4x16Yi
15)4x15)4 17)4x17)4
17x21 21x21 24x24*
24x28* 28x28*
30x30* 28x32*
81 70
127 99 110 100
183 156
248 195 298 234
357 278 441 576 380
672 468 784 531
900 616 896 635
10
12 15
18 20
22 24
27
30 33 36
79
2C
113 3&29*
177
254 314
380 452
573
707 855 1018
Dimensions below are for unlined rectangular flu?s.
American Boiler Manufacturers Association and Stoker Manufacturers Association and approved by these organizations. The sizes are given
in Table 4. Chimneys for Oil Fuel.'--The requirements for stacks for oil fuels are
entirely different from those connected to coal-fired boilers, as there are certain losses through the boiler proper that are eliminated. Gas tem peratures entering the stacks are lower for a given capacity, and the volume of gas is less than with coal. The cross-sectional area of the stack may therefore be less. In most instances this may safely be taken as
i From Marks- Mechanical Engineers Handbook.
152
Chapter VI--Chimneys
w ______ __ ____ -- V..A.C ivouiu ue iurnisnea lor coal-hred boilers. In determining the height, care must be taken to design a stack that will give a sufficient draft for the maximum requirements of the boiler, but not more. In this way the efficiency is safeguarded, and the danger of a draft such as to pull through too large an excess of air is eliminated.
Table 4. Height of Stack for Average Installations (Sea Level) Average Draft Losses vnth Forced Draft Stokers
Per Cent Rating. ...... .. Draft Furnace.......................
Friction Loss (Boiler)............ Friction Loss (Breeching)... .
Total Draft Reauired............ Height of Stack (Ft.) .
100
0.15 0.18 0.10 0.43
80
112
200 0.15 0.65 0.10
0.90 145
250 U. 15 0.9 0.10
1.15 178
300
0.15 1.20 0.10 1.45 220
Diameter of Chimney in Inches for Horizontal Return Tubular Boilers
Nominal H. P.
15
20 25 30
35 40 50 60 75 90 100 115 125 150 175 200
210 225 250
-
100%
Rating
13 14 16 17 18 19 20 21 23 25 26 27 28 30 32 33 34 35 36
150% Rating
14 16 18 19 20 21 23 24 26 28 29 31 32 34 36 38 38 40 41
200% Rating
17 18 20 21 22 23 25 27 29 31 33 34 35 38 40 43 44 45 47
Stack in Feet--For Sea Level and 60 DEG. fahr. Outside Temp. Assumed Fric tion Loss in Stack 0.1 in. pkr 100 ft.
Draft at Base of Stack
0.12 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65
100%
Rating
21 26 35 43 52 60 69 78 86 95 104 112
150% Rating
22 28 37 46 56 . 65 7484 93 102 112 121
200%
Rating
25 30 41 51 61 71 81 91 101 111 122 132
Rating............ Efficiency_ CO,...... ......."
100%
65%
8%
150% 65%
9%
200%
63%
10%
Stack Temp, deg. fahr... ............
Lbs. of Gas...............
Friction loss through boiler varies according to construction.
450 500 550 85 77 73
'For Furnace Draft.--Allow 0.15 for forced draft. . For Natural Draft 0.35 in. or higher should be used
depending upon rate of combustion and fuel used.
For Breeching Friction Loss.--AUbw 0.05 in. for each right angle bend and 0.1 in. per 100 ft. of length. .
Chimneys for still greater horsepowers are given by Tables 5 and 6.
Table 7, adapted from one calculated by C. R. Weymouth (Trans. A. S.M. E., Vol. 34, 1912) and based on actual test data, will be found
to give satisfactory results under the assumed conditions as given for stacks with oil-burning boilers. ...
i53