Document raVaJkrBoqpKBYB7nvNN1G6V

American Society of Heating and Ventilating Engineers Guide, 1935 the top floor, that the length of run from the tank to the farthest fixture is 200 ft, equiva lent length of fittings 100 ft, and the pressure required at the fixture is 7 lb. The 30-ft head is equal to a static pressure of 0.43 X 30 or 12.9 lb per square inch and to maintain a pressure of 7 lb at the highest fixtures the drop allowable in pressure is 12.9 -- 7.0 lb or 5.9 lb. As the total equivalent run is 300 ft, this is a drop per 100 ft of 1.97 lb, or practically 2 lb. Therefore, all risers and mains from the top floor back to the Table 4. Typical Calculation of Pipe Sizes on Down-Feed Riser with Flush Valve Water-Closets and Urinals Floor of Bldg. Fixtures --Gpm-- on PER Floor Fixture Riser No. 1. (See Fig. 4) Maximum Probable' Probable Fixtures Use Fixtures Gpm (per cent) Gpm ____ -- Probable Allowable Riser Drop Gpm J/B per 100 Ft In. 1st I S. S. 2nd 1 S. S. 4 4 3rd 1 S. S. 4 3 4th 10 Lav. 3 13 6tb 4 W. C. 50 2 U. 40 6 3 Lav. 3 16 4 100 4 ` 100 4 12 80 30 42 45 200 80 280 40 9 51 45 44 4 8 10 10 19 19 112 22 134 30 X 30 X 30 . X 30 1, . 30 2 6th 4 W. C. 50 2 U. 40 12 3 Lav. 3 19 7th 4 W. C. 50 2 U. 40 IS 3 Lav. 22 3 200 80 560 25 9 60 42 200 80 840 18 9 69 40 140 25 165 -- 151 28 179 30 2 <- 30 2X 8th 4 W. C. 50 2 U. 40 200 80 24 1120 15 3 Lav. 3 9 168 25 78 40 31 199 -- 24 tank must be sized on the basis of a drop of 2 lb per 100 ft. Tables 4, 5, 6 and 7 show the schedule for Risers No. 1, 2 and 3 with the maximum possible flow taken from Table 1, the percentage of use at the peak taken from Fig. 1, and the maximum probable flow at the peak worked out for each portion of the riser, the riser sizes being taken from Table 2 as far as possible and from Fig. 3 where the amounts exceed the values given in this table; a drop of 30 lb per 100 ft is used except on the riser from the top floor back to the tank where 2 lb per 100 ft is the allowable limit. The reduction in pipe size which would occur if flush tank water-closets were used on the top floor and only 3 lb pressure used on the fixtures is given in Tables 8 and 9. 608 Chapter 35--Water Supply Piping This illustrates why flush tank closets so frequently are substituted on the uppermost floor when a house tank is the source of water pressure: If it is now assumed that Riser No. 1 is to be fed from the bottom and the minimum street pressure is 75 lb with the top fixture of the riser 80 ft above the main, the problem Table 5.' Typical Calculation of Pipe Sizes on Down-Feed Riser with Flush Valve Water-Closets.and Urinals................... Riser No. S. (See Fig. 4) Floor Fixtures of on . Bldg. - _ Floor - Gpm Maximum Probable Probable Probable Allowable per Fixtures Use .Fixtures - Riser-- Drop Fixture- Gpm (per cent) Gpm Gpm Lb per 100 Ft Pipe . SizeIn. 1st 1 W. C. 50 2nd 2 W. C. 50 1 U. 40 4 1 Lav. 3 3rd 4 W. C. 50 2 U. 40 10 3 Lav. 3 4 50 100 100 40 190 50 3 100 200 80 470 30 9 12 70 50 50 95 3 98 141 8 149 30 IX 30 IX 30 2 4th 4 W. C. 50 2 U. 40 16 3 Lav. . 3 7 200 80 750 20 9 21 70 150 14 164 30 2 5th 6 W. C. 50 300 22. 4 Lav. 1050 3 12 15 11 33 48 157 - 16 173 30 2 6th 6 W. C. 50 300 28 4 Lav. - 1350 3 12 12 15 45 . 45 7th 6 W. C. 50 34-~4 Lav. 3 19 300 1650 . 12 57 - 10 42 8tb 6 W. C. 50 300 40 4 Lav. 1950 3 -12 23 69 9 40 162 20. 182 30 2 165 ................ 24 189 30 ..... 2X 175 ... - ... -- 27 202- 2" :>4 would be solved by determining the maximum rate of flow in each portion of the riser as shown in Table 10 and then finding the allowable drop which can be used per 100 ft. The 80 ft of riser height will use up .- 0.43.1b X 80 = 34.4 lb ,v