American Society of Heating and Ventilating Engineers Guide, 1930 trol of the system later. In general, it is safe to say that where audiences are involved, the heating installation must have sufficient capacity to bring the building up to the stipulated inside temperature before the audience arrives. In industrial plants, quite a different condition exists, and heat sources, if they are always available during the period of human occupancy, may be substituted for a portion of the heating installation. In no case should the actual heating installation (exclusive of heat sources) be reduced below that required to maintain at least 40 deg. fahr. in the building. The following allowances may be made when required: Table 44. Heat Emitted by Persons per Hour at Different Room Temperatures H - Heat emitted by man at rest per hour. HI = Heat emitted by man at light labor per hour. . Ha = Heat emitted by man at average labor per hour. Hh = Heat emitted by man at hard labor per hour. ff = Heat Energy = ^Fo9t-_Pou"|| Pg!Lh"r^ = 84 B.t.u., 168 B.t.u. and 252 B.t.u. respectively for light, average and hard labor. T = Room Temperature. H = 13.2 (98.6 - T) Heat due labor = T E- Hl, Ha, or Hh = 13.2 (98.6 - T) plus Root! Temp. Deg, Fahr. 30 40 50 60 68 70 75 80 85 90 905 773 642 509 404 378 312 246 180 114 Heat Emitted bt Mans B.t.u. per Houb at ------------------------------ ;------------------------------ ^ Condition Required 84ligBh.tttt. Labar 1A6l8vaebBrao.kgrue, 25L2HaaBbro.dtru. Excess and Shortage in Hrat Emission 931 807 684 559 461 436 375 313 251 189 954 838 723 606 518 491 438 375 322 259 981 Increasing Humidity. t. 874 Heavy Clothing for Reduction or Preven 768 tion of Radiation. 660 575 Normal Condition. 554 501 Decreasing Humidity. 447 Air Currents for Producing Evaporatidn 394 of Perspiration. 342 For children use one-half of table values. Motors and the machinery which they drive, if both are located in the room, convert all of the electrical energy supplied into heat, which is retained in the room if the product being manufactured is not removed until its temperature is the same as the room temperature. / If power is transmitted to the machinery from the outside, then only the heat equivalent of the brake horsepower supplied is used. In the first case the B.t.u. supplied per hour = or horsepower 2,546, and ^ Efficiency of motor in the second case B.t.u. per hr. = b.hp. X 2,546, in which 2,546 is the B.t.u. equivalent of I hp. hour. In high-powered mills this is the chief source of heating and is frequently sufficient to overheat the building even in zero weather, thus requiring cooling by ventilation the year round. . .. , For intermittent heating allow 10 per cent additional for rooms heated; 74 'v. Chapter 2--Heat Losses'from Buildings in the day time only, and for longer intervals of several days or more, add 25 per cent *n determining minimum heating requirements, and size of plant. EXAMPLES OF HEAT LOSS COMPUTATIONS FACTORY BUILDING. (See Fig. 9). 1. Location.......................................................................................................Philadelphia, Pa. 2. Lowest outside temperature. (Table 3).......................................... -- 6 deg, fahr. 3. Base temperature: In this example a design temperature 10 deg. fahr. above lowest on record iJnUsStetMaUd oV*f 15 dwevDg.. fahr. is u....s...e...d.............H....e....n....c...e.....t.he base temp# erature = (- 6 + 10) = + 4 deg. fahr. 4. Direction of prevailing wind (during Dec., Jan., Feb.).........................Northwest 5. Breathing-line temperature (5 ft. from floor)^............................... .60 deg. fahr. . G Inside air temperature at roof: The air temperature just below roof is higher than at the breathing line. Height of roof is 16 ft., or it is 16 -- 5 = 11 ft. above breathing line. Allowing 2 per cent per foot above 5 ft., or 2 X 11 = 22 per cent, makes the temperature of the air under the roof = 1.22 X 60 = 73.3 deg. fahr. 7. Inside temperature at walls: The air temperature at the mean height of the walls is greater than at the breathing line. The mean height of the walls is 8 ft. and allowing 2 per cent per foot above 5 ft., the average mean temperature of the walls is 1.06 + 60 = 63.6 deg. fahr. By similar assumptions and calculations, the , mean temperature of the glass will be found to be 64.2 deg. fahr. and that of the doors 61.2 degfahr. 8. Average wind velocitv (Table 3)................................................... 11.0 miles per hour 9. Overall dimensions (See Fig. 9). .120 x 50 x 16 ft. 10. Construction-. Walls--12-in. brick, with H-in- plaster applied directly to inskje surface. Roof--3-in. stone concrete and built-up roofing. Floor--5-in. stone concrete on 3-in. cinder concrete on dirt. Doors--One 12 ft. x 12 ft. wood door (2 in. thick) at each end. Windows--Fifteen, 9 ft. x 16 ft. single glass double-hung windows on each side. 11. Transmission coefficients: Walls--(Table 12). .......................................................................... U = 0.277 Roof--(Table 32)--.............................................................................. U = 0.610 Floor--(Table 31)................................ ................................................. U = 0.521 . Doors--(Table 36)i................................. .............................................. U = 0.382 Windows--(Table 36) ...................................................................... U = 1.13 12. Infiltration coefficients: Windows---Crack assumed He in. The leakage per foot of crack for an 11-mile wind velocity is 92.7 cu. ft. per hour, for a plain window. (By interpolation from Table 39, Part II.) The heat equivalent per hour per degree is 92.7 X 0.075 X 0.24 = 1.67 B.t.u. Doors--Assume infiltration loss through door crack twice that of windows or 2 X 1.67 = 3.34 B.t.u. 75