Document rO0rZbGo99yBro4n8BxJ394E
c
PPG INDUSTRIES, INC. INDUSTRIAL CHEMICAL DIVISION
TAKE CHARLES, LOUISIANA
LD-1121D
CONTINUING PROGRAM OF MONITORING ATMOSPHERIC CONTAMINANTS WITHIN THE LAKE CHARLES PLANT
Distribution
W. Graybill H. J. Hoenes, Jr. H. B. Loveo'oy D. Duncan M. Davis C. A. Burns M. G. Burns T. Taylor R. Kaspar E. McVicker W. Chapman C. P. LeBlanc Central Files - G.O. Technical Files (6) Author Laboratory File
by
Mark Wood
May 12, 1972
Key Words
Occupational Environment Atmospheric Contaminants Montaire Sampler MSA Universal Pump Andersen Mini Sampler Electrostatic Precipitation Unico Gas Detector Mercury Vapor Detector OSHA Heat Stress ACGIH Asbestos Fibers Wet Bulb Globe Temperature
c
LABORATORY DEPARTMENT' MARK WOOD
c
TECHNICAL REPORT MAY 12, 1972
CONTINUING PROGRAM OF MONITORING ATMOSPHERIC CONTAMINANTS WITHIN THE LAKE CHARLES PLANT LD-1121D
ABSTRACT
The tables composing this report are continuations of occupational environ ment surveys started early in 19^9 and contain data from all plant areas from November 1971 to May 1972.
INTRODUCTION
The periodic investigation of employee's occupational environments initiated in 1969 is described in detail in LD-1121. This report is an addendum and contains tabulated data collected from November 1971 through May 1972.
DISCUSSION
The methods and sampling times stated in previous reports have not been changed. Two additional surveys are included in anticipation of more rigid regulations. The first addition. Table 11, is airborne asbestos with regard to diaphragm cell manufacturing and maintenance insulators. The second, Tables 12 and 15, is heat stress analysis in Mercury Circuit and Diaphragm Areas.
Airborne asbestos samples were taken with personnel monitoring equipment pulling an air sample through a membrane. The membranes were sent to Barberton for sizing and counting of the asbestos particles.
Heat stress measurements were accomplished using natural wet bulb,-dry bulb, and globe thermometers as outlined in the "Notice of Intent to Establish" section of the 1971 American Conference of Governmental Industrial Hygienists booklet. For each job classification where men work in high heat exposures, a threshold limit value is obtained from their energy output. The exposure is expressed as degrees wet bulb-globe temperature. WBGT takes into consideration variables such as radiant heat and evaporative effect due to air currents and humidity.
Since some threshold limit values have been changed, a new tabulation of these values is appended.
Results of these surveys, tabulated by areas, are appended. Table 7 on sodium chlorate has been removed.
Author:
MW:rw
Approved: C. P. LeBlanc
Date
| BB 0000176 |
rc
LD-1121D/4
Threshold Limit Values of
Airborne Contaminants and Physical Agents (Existing within the Lake Charles Plant)
Contaminant_____ Ammonia Chlorine Hydrogen Chloride Lead
Mercury Methyl Chloroform Perchlorethylene Phosgene Sodium Hydroxide Trichlorethylene Vinyl Chloride
Mineral Dusts Nuisance Dust Asbestos Silica Pigments
Heat Stress
T.L.V. Concentration
50 ppm (intended change - 25 ppm)
1 ppm
5 ppm 0.20 mg/M3 (intended change -
0.15 mg/M3)
0.05 mg/M3
550 ppm 100 ppm 0.1 ppm
2 mg/M3
100 ppm
500 ppm (intended change 200 ppm)
10 mg/M3 20 m.p.p.o.f. (intended change - 5 fibers > 5 p/ml) 6 mg/M3 (adopted by PPG Industries, Inc.)
See graph - page LD-1121D/5
From 1971 Edition, Threshold Limit Values of Airborne Contaminants Adopted by ACGIH (American Conferences of Governmental Insustrial Hygienists).
j BB 0000 177J.
c(
LD-1I21D/5
pi'ioposep U/Mis FOK HA7-- vJOU K STRFi ( Source. ; ACGtfH -tf?/
100 200 ' 300 400 500
kcal / hr.
BB 0000178 1
\
TAELE 1 OCCUPATIONAL ENVIRONMENT AIR MONITORING
Area
Monitored Personnel
Date-Time
Contaminant Concentration Conditions
lercury Cell Circuit Cell Operator 5-15-72 (A.M.)
Chlorine
l/2 ppm
-
Cell Auxiliary
Operator
Ditto
Chlorine < 1/2 ppm
-
Cell Repairman Ditto
Chlorine <l/2 ppm
-
Cell Cut-Out Man
Ditto
Chlorine
l/2 ppm
**
Cell Operator 5-15-72 (A.M.)
Cell Auxiliary
Operator
Ditto
Mercury Mercury
0.05 mg/M3 0.10 mg/M3
Numerous Cells being Cut Out
Ditto
Cell Repairman Ditto
Mercury
<0.05 mg/M3
Ditto
Cell Cut-Out Man
Ditto
Mercury
0.10 mg/M3
Ditto
Method Monitaire Sampler Ditto Ditto Ditto Monitaire Sampler
-
L D -I1 2 1 D /6 BB 0 0 0 0 1 7 9
l-- 1 l Ii
l i l l
t
l I l i ll i- 1
l
Iitev. '0/69)
Laboratory Lunch Room No. of People Rest Room Locker Room
MERCURY 1:1 AIR
ACCRY CEIL
(llg in ics7
0.008
o.o4o
6_____ 0.020
0.013
Control Room Cffice Motor Control
Area Maintenance 13.8 KV Sw. Gr. *
0.012 0.010 0.026
0.013 0.003
16 0.006
Date: ll/l6/71 thru^J/772 (Average of 33 surveys)
Ha Stack Area < 0.003
Open Cells
__I
Relative Humidity
Temperature
-
Maintenance Lunch Room
< 0.003
If
LD-1121D/7
t
1 I
cr
t
I J
t CO *
II
ICt
Io
Io1
1-i
1 CO I I c-1 I>
I- t
Surveys taken with J-W Lemare Mercury 'Sniffer, Model MV-%.
L - Ground Floor
TABLE $ OCCUPATIONAL ENVIRONMENT AIR MONITORIMG
Monitored Personnel
Date-Time Contaminant Concentration Conditions Method
Liquefaction Operator
3-17-72 (A.M.)
Brine Treatment Ditto Operator
Chlorine
< 1/2 ppm
Chlorine
< l/2 ppm
Liquefaction Operator
Brine Treatment Operator
3-17-72 (A.M.) Ditto
Ammonia
< 5 ppm
Ammonia
< 5 ppm
Monitaire Sampler Ditto
Monitaire Sampler Ditto
Al'L
Caustic PI; it
l-- i i1 1 tr 1 11 tt !1 lo1 lo1 t1 io1 !l f to 1 11 1-- 1
TABLE 4 OCCUPATIONAL ENVIRONMENT AIR MONITORING
Monitored Personnel
Date-Time
Contaminant Concentration Conditions
DH Operator
3-16-72 (A.M.)
Chlorine
< l/2 ppm
"A" Evaporator
Operator
Ditto
Chlorine
< 1/2 ppm
Filter Operator
Ditto
Chlorine
1/2 ppm
Lead Operator Ditto
Chlorine
< l/2 ppm
*
DH Operator
3-16-72 (A.M.)
"A" Evaporator
Operator
Ditto
Filter Operator
Ditto
Lead Cperator Ditto
Ammonia Ammonia Ammonia Ammonia
< 5 ppm < 5 ppm < 5 ppm < 5 ppm
Caustic Bird Area
4-20-72 (A.M.)
NaOH Mist
0.2 mg/fP
PELS/Anhydrous
Operator
3-17-72 (A.M.)
PELS Shipping 4-03-72 (A.M.) Packer
Chlorine Chlorine
< l/2 ppm < l/2 ppm
Method Monitaire Sampler
Ditto
Monitaire Samp -r Ditto
Monitaire Sampler
Ditto Ditto Ditto
Water Scrubber/ Atomic Absorption Sodium Anal.
Monitaire Sampler
Ditto
_L1
.Area
Diaphragm Cell Circuits
I
TABLE $ OCCUPATIONAL ENVIRONMENT AIR MONITORING* I
Monitored Personnel
Date-Time
Contaminant Concentration Conditions
Tender, Circuits 1,2
3-14-72 (P.M.)
Chlorine
l/2 ppm
Tender,
Circuits 5,6
Ditto
Chlorine
l/2 ppm
Tender
Circuits J,d
Operators
Ditto Ditto
Chlorine Chlorine
1/2 ppm 1/2 ppm
Method Monitaire Sampler Ditto Ditto Ditto
\-- i
1l I cr i
IDI II
1OI Io( I OI
ICI
II
I CO t
I La I I1 I-- I
IOrt*
Ht) HO
TABLE 6 OCCUPATIONAL ENVIRONMENT AIR MONITORING
Area
Diaphragm Cell Repair and Manufacturing
Monitored Personnel
Late-Time
Lead Pot Area 3-14-72 (No. 3)
Lead Pot Area (No. 3)
Ditto
Contaminant Concentration Conditions
Lead
0.05 mg/M3
Removing graphite chips.
Lead
< 0.05 mg/M3 Pouring Lead
Lead Pot Area (Ko. 6)
Solder Wiping Area
Ditto Ditto
Lead Lead
<0.05 mg/M3 Pouring Lead
<0.05 mg/M3 Wiping
Solder Wiping Area
Ditto
Lead
<0.05 mg/M3 Not Wiping
.
Method MSA Universal Rarrp vith Fb Kit Ditto
Ditto Ditto Ditto
Repairman at Mastic Area
3-14-72
Chlorine
< l/2 ppm
Monitaire Sampler
l Ii-- t * i1
ti to1
|o
1 ol lot
1
1
-IX
*
i:i
Repairman at Acid Dipping Area
5-11-72 (A.M.) 5-11-72 (A.M.)
Ditto
Hydrogen Chloride
Hydrogen Chloride
Hydrogen Chloride
< 1 ppm 2 ppm 10 ppm
Submerging cathodes. Raising cathodes.
MSA Universal Test Kit
Ditto
Draining cathodes. (Respirator in use.)
Ditto
t)
t
Ha
i?
%
.rea 'over-houses
Monitored Personnel
"A" Watch Engineer
"A" Utility Operator
"B" Watch Engineer
TABLE 8 XCUPATIOML ENVIRONMENT AIR MONITORING
Date-Time 4-3-72 (A.M.)
Contaminant Concentration Conditions
Chlorine
< 1/2' ppm
Ditto Ditto
Chlorine
<1/2 ppm
Chlorine
< 1/2 ppm
Method Monitaire Sampler
Ditto Ditto
LD-1121D/12
BB 0 0 0 0 1 9 5
I-- I II
1 I I I I I l 1I I
it
-.rea
Silica Pigments (See note for
locations of sampling.)
Monitored Personnel C
D E F
TABLE 9
OCCUPATIONAL ENVIRONMENT AIR MONITORING
Date-Time 3-14-72 (A.M.)
Ditto Ditto Ditto
Contaminant Concentration Conditions Method
Particulates 1.7 mg/M3
No activity
Particulates 4.3 mg/M3 Particulates 42.3 mg/M3 Particulates 28.8 mg/M3
Bagging and loading. Bagging and loading. Ditto.
Electrostatic precipitation.
Ditto
Ditto
Ditto
Sampling
3-14-72 (A.M.)
personnel
wearing Midget
Cascade Impactor
while sampling
ahove points -
1 hour.
Total Particulates 21.6 mg/M3
Respirable
'
Portion
11*5 mg/M3
or 531o
respirable
Andersen Mini Sampler
(Wind - SW at 5 mph)
Furnace Building .5-15-72 (Mid-day) Upper Floor South Entrance
NaOH Mist
4.0 mg/M3
Water Scrubber/ "AA" Sodium Analysis
a a
ro H a *5
SILICA PIGMENTS AREA. PARTICULATE AIR SAMPLING LOCATIONS
lU-0121D/i4
Downstairs in Frit Reactor area of Furnace Building
Upstairs, over the south end of the furnace in Furnace Building
North-East corner of the Pigments Shipping Building where trucks and "boxcars are loaded
Center of Pigments Shipping Building, under North-South conveyors
On the Bagging Platform between Baggers in Pigments Shipping Building
Center of Lower Roadway leading out the west door of Pigments Shipping Building, adjacent to Bagging Area and Hopper Car Loading
\ BB 00001
Area
Organics Area (See nap for
sample locations)
'Monitored Personnel
1 thru 8
TABLE 10 OCCUPATIONAL ENVIRONMENT AIR MONITORING
Date-Time 4-13-72
Contaminant Concentration Conditions
Phosgene
None detected.
12 raph South wind.
Method
Unico Gas Detection Tubes.
1 thru 8
4-13-72
Methyl
None detected.
Chloroform
12 mph South wind.
Ditto.
1 da 1 1 C3 t 11 1Ol 1o1
1o1 1o1 1--1 1 (X 1 i oa 1 i1
t-- t
t-i fici
L_J
P ro H a
vHn
\rea Organics
t-- l fI
t l t I I I I l
i-- i
QB 0000 189
Monitored Personnel 1
2 5` 5 6 7 8
3
4
TABLE 10 - (COHT'D.) OCCUPATIONAL ENVIRONMENT AIR MONITORING
Bate-Time 4-13-72
Contaminant Concentration Conditions
Per/Tri
10 ppm
12 mph South Wind
Ditto Ditto Ditto Ditto Ditto Ditto
Ditto Ditto Ditto Ditto Ditto Ditto
10 ppm < 10 ppm < 10 ppm < 10 ppm < 10 ppm < 10 ppm
Ditto Ditto Ditto Ditto Ditto Ditto
4-13-72 Ditto
Vinyl Chloride
Ditto
None Detected 12 mph South Wind
Ditto
Ditto
p
Method
Unico Gas Detection Tubes
Ditto
Ditto
'"'N
Ditto
Ditto
Ditto
Ditto
Ditto Ditto
9i/<nsn:-<ri
(
Organics Area Points
LD-1121d/i7