Document rDbd33wvVa7Ky0rmNbrrxo9G

422 Chapter 17 1953-Guide x Example S: Determine if a 13-ft, 8 x 8-in. nominal-size flue is sufficient for a coal-. x heating unit rated at 0.03 in. of water draft at 400 F inlet temperature, fuel rate being 10 lb per hr of bituminous coal; with 10 percent CO,. Solution: From Fig. 9, a flue-gas rate of approximately 180 lb per hr is obtained. The available draft for a 180 lb per hr fuel rate, and-an inlet temperature of 400 F, obtained from Fig. 6, is 0.056 in: of water. This indicates that the chimney is ade quate. The selection of chimney areas for liquid- and solid-fuel-burning devices is difficult because of the variability in efficiency of different models, the possibility that soot on the fining will restrict the chimney area, and the variation in combustion air requirements of different solid fuels. Figs. 6 and 7 show that a given chimney produces a maximum available draft and a maximum efficiency for some intermediate mass flow rate for any selected inlet flue-gas temperature. For mass flow rates lower than the optimum the greater cooling of the gases in the chimney causes lower available draft, whereas for mass flow rates above the optimum the greater friction losses reduce the available draft. A chimney for a given heating system should probably be designed to operate at its point of maximum efficiency and maximum available draft for its full rated output.- A chimney would have an accelerating effect10 on the combustion rate of a solid-fuel burning device if it were operating to the left of the optimum point in Fig. 6 because an additional increment in mass'flow rate would increase the available draft a small amount and tend to increase the mass flow still more. On the other hand, a chimney operating to the right of the optimum point in Fig. 6 would tend to decelerate the combustion rate for any small increase in mass flow rate. Data are not complete for the selection of proper chimney areas for heating plants of different capacities, but some information on the effect of cross-section area on the capacity of masonry chimneys is provided by recent tests8'11 on several chimneys with liners having nominal outside dimensions: 9 in. diameter, 12 in. diameter, 9X9 in., and 9 X 13 in. These tests showed that for flue gas rates up to 200 lb per hr, and entering flue gas temperatures from 200 to 1000 F, the 9-in. round liner provided an available draft equal to, or greater than, that produced by the other three larger liners. When the flue gas rate was increased to 320 lb per hr, the three larger liners produced a little more draft than the smallest one for entering flue gas temperatures above 600 F. Other data9 show that metal chimneys with an internal diameter of 6 in. should not be used for mass flow rates greater than 130 lb per hr. Table 2 shows approximate values of the mass flow rates and flue-gas velocities at the chimney inlet that produce the maximum available draft for masonry chimneys8 of several conventional sizes and with an effective height of 15 ft. This table shows that a 9-in. round chimney is best suited to mass flow rates from 130 to 170 lb per hr, a 9 X 9-in. chimney performs best for flow rates from about 200 to 300 lb per hr, and a 9 X 13in. and 12 in. round chimneys are best suited to flow rates above 300 lb per hr. These results were obtained with clean chimneys, so that conclusions about chimney areas require some modification if soot deposits are taken into consideration. Soot deposits in chimneys reduce the effective area of the finer and may in some cases entirely close the passage. Soot deposits are likely to be greater in the horizontal passages in the heating plant, the breeching, and the smokepipe, than in the vertical chimney finer. An increase in the liner diameter of one inch above that required for a clean chimney will probably make adequate allowance for soot deposits in all but the worst ^Chimneys and Draft Calculations- 423 .cases. Where smoky combustion is likely to occur and the mass flow rates On a clean chimney basis approach those listed in Table 2, the next larger commercial size-liner should be used. Smoky combustion with oil-burning .devices, particularly with vaporizing oil burners, is likely to be caused by inadequate draft which is often due to insufficient chimney height. -For coal,, inadequate chimney height or chimney area may be a contributing cause, but smoky combustion with coal is related to fuel characteristics and firing methods. . Therefore, an increase in chimney area will usually not cure smoky combustion of a coal-burning device, but can be expected to lengthen the interval between cleanings. New standard sizes of clay flue finings were recently developed' by the industry and approved by the American Standards Association, in order to effect economies that can be derived from coordination of the dimensions of building materials. These linings are known as modular clay flue \ '' Table 2. Appboximate Flue-Gas Flow Rates for Maximum Available Draft in Masonry Chimneys Nominal External Liner Dimensions Internal Area op Liner, . Sq In 200 Flue Gas Temperature at Chimney Inlet, Fahr. 600 1000 200 600 1000 Mass Flow Rate, LB/HR Flue Gas Velocity, at Chimney Inlet, FPM 12 in. Dia. 9 in. x 13 in. 38.5 49 78.5 77 170 150 130 215 306 334 290 Above Above 320 320 295 Above Above 320 320 175 175 150 150 250 - 300 400 6UU finings, and the dimensions and tolerances are summarized in .ASA .Stand ard A62.4-47. As the effective areas of these liners are somewhat, smaller than those of the corresponding finings used previously, they cannot be used in certain municipalities where building codes specify minimum areas based on the older dimensions. DRAFT REQUIREMENTS OF APPLIANCES Typical flue-gas temperatures and drafts required at rated output for several kinds of domestic heating appliances12 are contained in Table 3. Chimney height and chimney area for cast iron boilers are specified in the / = B = R Testing and Rating Code of the Institute of Boiler and Radiator Manufacturers. Mechanically-fired devices such as oil burners and stokers are equipped with blowers, and therefore, the chimney is not required to overcome the resistance of the fuel bed or burner. Nevertheless, a draft in the firebox, of about 0.03 in. of water, is considered desirable so that any small openings in the firebox or flue passages will result in leakage of air inward, and not leakage of combustion products outward. Firebox leakage should be kept to a minimum, however, since such leakage adversely affects heating plant efficiency. Difficulty in obtaining enough draft for natural draft appliances is likely to occur for attic installations or in one-story houses without basements. Automatic oil-burning space heaters, floor furnaces, and warm air furnaces employing natural-draft vaporizing burners require a draft, of 0.06 to 0:08 in. water for outdoor temperatures of 60 F. Taking into account the prob-