Document rBndGR3Ld6rox9RYMRxwQBvDe
:434
CHAPTER 17 ;
1952 Guide
-from Table 3 is 0.875.. Solving 0.875 X 0.00383 ==. 0.00335. Making a further, cor
rection for the heating.value,
,
. .0:00335 X
= 0.00328 gal per 1000 Btu per hr calculated heat loss per degree-
day,
'
'`
"
. From Table 2, the total normal degree-days for Toledo are 6269. Since U is expressed in 1000 Btu, N is equal to 240. Substituting in Equation 4 .
F = 0.00328 X 6269 X 240 = 4930 gal.
'
Estimating Coal or Coke Consumption
/ Coal or coke consumption estimates'are made by following exactly the same:prbcedure as for oil. Valuesof U;are given in Table 6 which only apply to an inside design temperature of'70'F and an outside design tem perature of 0 F. A correction must be made for other conditions by use of
Table 4. Unit Fuel Consumption Constants (17) fob Gas* Based on 0 F Outside Temperature, 70 F Inside Temperature
Hot Wateb
'Steam
Wabm Aib ! -
Heating Vai*ue of
Gas Btu peb Cu Ft .
500 535 .800 .'
` 1000
Cu Ft Gas per Degree-Day per Sq Ft EDR
Up to 500
Sq Ft
0.149 0.139 0.094 0.075
500 to 1200 Sq Ft
0.142 0.132 0.087 0.071
Over 1200 Sq Ft
0.134. 0.126 0.085 0.068
Cu Ft Gas per Degree-Day per Sq Ft EDR
:
Cu Ft Gas per-DegreeDay per 1000 Btu
Hourly Design Heat Loss
Up to 300
Sq Ft
300 to .,.700
Sq Ft
Over'
. 700 Sq Ft
Gravity
Fan Systems
0.254 0.237
0.159 0.127
0.242. 0.226 0.151
0.121
0.231;
0.216 0.144
0.116
0.896 0.840 0.560 .
0.449
0.861 0.805 0^538 0!431
1 Therm
Gas Consumption- in Therms per Degree-Day
,100,000
Btu
0.000743 0.000709 0.000675 0:00127 0.00121 0.00116 0.00450
0.00430
{ Abstracted from Comfort Heating, American Gas Association, 1938 and 5 percent added for operation without night reduction of temperature.
the multiplying factors in Table 3. Data in Table .6 are based on 12,000 Btu per lb coal, and for other heating values of coal they must be multiplied by the ratio of 12,000 divided by the heating value of fuel used.
Example 6: A building in Scranton, Pa. has a calculated heat loss of 240,000 Btu
per hr based on an inside design temperature of 70 F and an outside design temper ature of --10 F. What will be the estimated normal seasonal anthracite or coke . consumption for heating if 13,000 Btu per lb fuel is burned in a hand-fired boiler, wifh automatic control, at a seasonal efficiency of 80 percent, and what part of the itotal will be-used during November, December, and January?
' . Solution: Front-Table 6, U is 0.0444 of coal or coke per 1000 Btu per. hr heat loss per degree-day. Correcting for the outside design temperature of --10 F from Table .3, the value of U is 0.875 X 0.0444 = 0.0389. From Table 2, 7) is 6218 and from the
problem, N is 240.
1 Substituting in1 Equation 4,
`
F = 0.0389 X 240 X 6218 = 58,100 lb.
Fuel used over any period is, according to the theory of the degree-day, propor tional to the number of degree-days during the period. From Table 2, the average numbers of. degree-days for November, December, and January in Scranton are 717, 1074, and 1162 respectively, a total of 2953. The yearly total is 6218, so that during
these three months the estimated consumption is
-.
* 2053' -- X 58,100 = 27,600 lb. 6218
.
Estimating Fuel Consumption for Space Heating
435!.
Table 5. Unit.Fuel Consumption* .Constants ({/) for OiLb Based on 0 F Outside Temperature, 70 F Inside Temperature
' Unit
Gal Oil per Sq Ft Steam Radiator..........
Efficiency in Percent
70 80
0.00105
0.00092
Gal Oil per Sq Ft Hot Water Radiator....
0.00066
0.00058
Gal Oil per 1000 Btu Der Hour Heat Loss
0.00437
0.00383 - ;
* Based on a heating value of 141,000 Btu per gallon.
b Abstracted by permission from Degree-Day Handbook (Second Edition, 1937), by C. Strock and C. H. B.
Hotchkiss. Seven percent added for operation without night reduction of temperature and change to heat* ing value of 141,000 Btu per gallon.
Per degree day.
*
Estimating Steam Consumption
In 'estimating steam consumption the efficiency is generally assumed: at 100 percent. If for low-pressure steam an average heating value of 1000. Btu-per pound of steam is used, no correction is necessary. In comparing values from different cities, correction should be made for design temperar ture (see Table 3) when the unit figures are in terms of-heat loss but not ' when the values are in terms of building volume or floor space.
Where the heat loss is calculated in Btu per (hour) (degree difference in temperature) the simple.Equation 5 may be used: -
where
' -
: 1000 .
...
.-
,(5)
. ... '
: F = pounds of steam required for estimate period,: , H = calculated heat loss, Btu per (hour) (degree difference). 24 = hours in one day.
D = number of degree-days for the period of estimation. 1000 = Btu delivered per pound of steam condensed.
In this method the. number of degree-days automatically tikes care of average inside and outside temperature difference. When degree-days are taken from Table 2, an average inside temperature of approximately 70 F is assumed throughput the period, If ah average inside temperature other
. . Table 6. Unit Fuel Consumption* Constants (U) fob CokLb Based on 0 F Outside Temperature, 70 F Inside' Temperature-
Unit
--
40
Efficiency in Percent
50 - 60
- 70
.:so <
Lb Coal per Sq Ft Steam Radiator.... 0.0216 0.0172 0.0143 0.0123. 0.0108
Lb Coal per Sq Ft Hot Water Radiator.. 0.0135 0.0108 0.0091 0.0078 0.0068
Lb Coal per 1000 Btu per Hour Heat 0.0889 0.0717 0.0592 0.0507 0.0444'
. amhcu uu a uwuug value ui u,uw otu per pound.
" Abstracted by permission from Degree-Day Handbook (Second Edition. 1937), by C. Strock and C. H. B.
notchkiss. . Eight percent added for operation without night reduction of temperature.
'.c Per degree-day.- "
..." . *