Document rBZaakJ8pbNE3bLEnDVzEzrGJ

TLCMOHt> MW7t AUSA COOK lit Xay 13, I960 H Sand k Co*, Xne* 250 V. 57th Street Hew tor*, H.I* 10019 C^cr Gentlemen: Subject: Central Aireonditioning Plant, Spce* #19375-H Oar Req. # 235#01 Because the question of saddle insulation was brought up several days ago, and because objection was raised to the fact that the polystyrene material being used is not the ; ?self-extinguishing type, we request that a revision be ' made in our subaittal with regard to the saddle and hanger ' insulation* Ye request permission to use calcium silicate material at these points* On piping installed in saddles at floor level, we would Install altered segments in Daxcel 161S Poamastik as ve have done to date with the styrofoam* ' This would then be properly sealed as described in our May 9, 1964 letter to the Gaorge A* fuller Co* On piping Installed on hangers off the floor, we would Install ealelua silicate set in place using the fire resistance Jacket specified for the vapor barrier* By accepting this change, the owner would be assured of a fire resistive material whioh would meet both the density requirements and the com pressive strength for hanger insulation* There would be no change in contract price for this change* cry truly yours a j