Document r6erB11ZLn0Yo8K2gV91JaLMq
560
CHAPTER 21
1957 Guide
its total equivalent length by the actual friction loss per foot at design flow. The circuit friction pressure drop is the summation of individual section pressure drops.
Calculation of Actual Friction Loss for Example 1
Sec tion
Flow Mbh gpm
Friction
Loss
Pipe'
FT/100 FT Sub in.
mi/ft
(Fig. 3) (Fig. 3)
Fittings
Type
Equiv
FT**
Pipe Length
ft
Total Equiv
Length of Pipe
Ft
Friction Loss
Calculation MI
FT
BC 43.5 4.35
CD 36.0 3.6
DE 30.0 3.0
EF 25.0 2.5
FG 18.0 1.8
GN 0.8 0.08
NO 41.8 4.18
OB 50.0 5.00
1.5 180 1.0 120 2.5 300 1.8 210 1.0 120 -1.2 150
1.4 170 1.9 230
1 ell
2.4
. ----
H 1 ell
1.9 ,
. S4 --
--
- H-
--
--
M 3 ells
3.6
1 H tee
3.4
1 1 in. tee 4.8
1 Rad. V
3.6
1 ell
2.5
1 3 ells
7.6
2 tees
10.0
2 Gate 2.5
Valve
1 Flow 50.0
Valve
1 Boiler
: 7-s
14 15 8 10 14. 8
31
38
16 0.16 X 1.5
0.24
16 X 180 2880
15 0.15 X 1.0
0.15
15 X 120 1800
10' 0.10 X 2.5
0.25
10 X 300 3000
10 0.10 X 1.8
0.18
10 X 210 2100
14 0.14 X 1.0
0.14
14 X 120 1680
23 6.23 X 1.2
0.26
23 X 150 3500
34 0.34 X 1-4
0.48
34 X 170 5780
116 1.16 X 1.0
2.20
116 X 230 26700
Convector friction Iosb*. ..
1200 0.10
Total Friction Loes
* Data obtained from manufacturers' catalogs. ** See also Tables 2 and 3 and Fig. 7.
Ml e milinnhty
If the total friction loss as determined does not agree with the pump head, some pipe size changes will be necessary to obtain closer agreement. The slight differ ence in head calculated by milinches and by feet of head is due to use of only 2 sig nificant figures for the latter. This is well within the accuracy required.
As would be expected the calculated head of 4.02 ft is different from the 4.7 ft esti mated. This is due to two factors: (1) the difference between the actual and esti mated number of fittings and (2) the differences between actual and estimated losses in the different sections as the friction losses were generally below the average fric tion loss assumed.
The lrin, pump initially selected would be entirely satisfactory for the installation and would produce a flow slightly in excess of 5 gpm. A procedure to determine the actual flow and head capacity of the pump and system is discussed under Circulating Pumps.
One-Pipe System, Description and Design
The one-pipe system, Fig. 10, has a single main for both supply and re turn. Special fittings installed at the connections to radiation risers or runouts generate the head necessary to produce flow through the heating unit. In this system the main or circuit loop does not change size,from the first to the last radiation unit. The amount of water flowing in the main is constant, except at points where some of it is by-passed through radiation. Since the water temperature in the main drops progressively, some designers consider it necessary to increase the size of heat-transmitting surface ac-
.Hot'Water Heating Systems
'
561
cordingly by using a progressively lower design water temperature in sizing the heating units. Most one-pipe heating systems are designed, however, on the basis of a single design water temperature. Generally,, the theo retical increase, in heat-transmitting surface,is heeded only when the sys tem is operating at full design output. A water temperature drop in the main of 20 deg or less minimizes the capacity reduction effect.
In comparison with a two-pipe system, the one-pipe system:
1. Permits simpler piping due to the use of one main of uniform size, . 2. May be more acceptable when pipe is exposed in occupied spaces. 3. Is very adaptable to small systems or to individual loops in large systems,
either horizontal or vertical, as a part of a two-pipe system, or to obtain zone control in large combination systems.
4. May be lower in installation cost. 5. Has a Bimpler problem in regard to water flow adjustment.
Continuing the comparison with two-pipe systems some disadvantages of one-pipe systems are:
1. The amount of water which can be by-passed by a one-pipe fitting or fittings is limited by the economics of design and the head applied. The fittings are not gen erally used to provide the water flow necessary for large air-handling units having a high pressure drop.
2. The pump head required is slightly higher than, that required for a two-pipe reversed-retum system of similar flow requirements.
3. If the progressive increase of radiation size as temperature drops is taken into account, a design complication and additional cost factor are encountered. ,
4. The main flow design temperature drop should not exceed 20 deg.
Design of a One-Pipe System
The basic design premise of a one-pipe system is that the pressure drop of the one-pipe fitting, or fittings, at the required main flow, be equal to or greater than the radiation circuit pressure drop at its required flow. The system may be divided into two or more loops for smaller main pipe' sizes Md pumps. Main and radiation circuit temperature drops may be dif-