Document r60kv0yGzp797JZMpN9em6r4G
Individual shop inspection is required for minia ture boilers in the same manner as for power boilers.
After obtaining the stamp to be used when min iature boilers are to be constructed to conform with this section of the Pennsylvania (ASME) Boiler Code, o 3+0tc inspector, or an inspector employed regularly by an insurance company and who is qualified under the rules of the Common wealth of Pennsylvania to inspect boilers, shall be notified that an inspection is to be made; and -he sholl inspect such boilers during construction and after completion.
Manufacturers of miniaturo boilors built for use in Pennsylvania shall be required to register their names and addresses with the Department of Labor and Industry.
A manufacturer of miniature boilers for use in Pennsylvania shall immediately forward to the Department of Labor and Industry a data report (on forms to be furnished by the Department), one report for each lot of boilers manufactured in series but not to exceed one hundred, when boilers are built for stock.
Any boilers built for immediate shipment to a definite location, a separate data report shall be filed immediately with the Department giving the name and address of the purchaser of the boiler.
Where a boiler is shipped for resale the name and address of the purchaser/user, if located in Pennsylvania, shall be immediately reported to the Department.
(B) Section 5, Paragraph A-62 was amended to read as follows:'
"Where repairs are necessary which in any way aftect the working pressure or satety ot a boiler
10 j
an inspector commissioned by the Department of Labor and Industry shall be called for consulta tion and advice as to the best method of making such repairs and after such repairs are made they shall be subject to final inspection and approval by an inspector commissioned by the Depart ment of Labor and Industry.
"Where repairs are made by means of riveted patches the instructions set forth in the Adminis trative Section of the Appendix covering this subject shall be applied in so far as they affect design, calculations, material, workmanship and test."
(C) Paragraph H-61 and I l-l 14 were amended by addi tion of the following paragraph:
"In the case of single pass boilers the lowest per missible water level for low pressure heating boil ers of the fire tube type shall be the same as re quired in paragraph P-291 ot the Power Section. For multipass boilers the top row of tubes shall be completely submerged at all times."
(D)Revisions relative to jurisdiction of Department.
(1) Revision of Paragraphs P-331 and P-332, also L-81 (c) by deleting the words "municipal in spectors".
(2) Revision of Section I, paragraph (b), by de leting the following: "those operating in cities having boiler inspection departments estab lished prior to January 14, 1923".
(3) Revision of Section I, paragraph (j), by delet ing "such boilers being not located in a city
tidviuy o boiler inspection department now
established by ordinance."
(E) Rule P-332, sixth paragraph was amended by addi tion of the following;
"and a facsimile of such stamping shall be for-