Document qyv0DgzdJwv3ykw9zXeX8Opk
BE
THE CHLORINE INSTITUTE, INC. 342 MADISON AVE., NEW YORK, N.Y. 10017
X
-
212 682-432*
NOVEMBER 3, 1978
TO PLANT SAFETY COMMITTEE; PACKAGING COMMITTEE; AND PSC RESPIRATORY EQUIPMENT TASK FORCE
FROM ; JAMES. H. DOYLE
SUBJECT:- OSHA CITATION RE. RESPIRATORY PROTECTION VIOLATIONS
The ATTACHED two-examples of recent OSHA citations Issued as Information Items that are cause for-concem to producers, packagers, and consumers of chlorlne.-
-1
The Mead Incident was particularly surprising In that.It would appear that the. regional OSHA office Is establishing a precedent In the decision that full-
facepiece respirators are the minimum acceptable protection for chlorine releases. The Institute reacted to the citation as noted In the ATTACHED cor respondence. Whether the protests registered will prove effective in obtaining a-concession by.the regional OSHA office remains to` be seen.
The-other citation further Illustrates the strict application of OSHA regula- '
tlons once an incident occurs. Deficiencies in chlorine detectors, written stan dards for respirator use and inspection, and chlorine exhaust and scrubbing systems are Items which would cause problems for many chlorine handling facil ities.- _;
-Arrecommended reference to members needing to become more-familiar with OSHA'"*" vim inspectors* evaluation method is Program Directive-#300-9v For the cost of reproduction, copies. oT this directive, which covers the OSHA Standard Method for determination of respiratory protective program acceptability,-can be ob tained from the Institute offices. This document is issued to OSHA field per sonnel as a guide in administering the respiratory^regulations contained in 29 CFR 1910.134.
<
! JHD/kss._ L__^ enclosures-- -
' 1 .............
1
1` `
^-T**?** `'W.-.-r S \9 '
''
1* . _
-
MHHilS
THE CHLORINE INSTITUTE, INC- 342 MADISON AVE., NEW YORK, N.Y. 10017
.-'Sfe .
3ST*
212-682-4324
Melvin E. Clark, President J. Roger Hlrl, Vice President Robert L Mitchell, Jr.. Executive Director Edmund J. Laubusch, Technical Manager
September 21, 1978
Hr. Thomas E. Levenhager*
Area 01 rector, OSHA
U.S. Department-of Labor
"
Federal Office Building, Room 634
200 North High Street
Columbus, OH 43215
V. -- Jt.- *%:.
Be: Chlorine Ledk/Miad Corp, ;
... and StSooriepodSere^-^k,.
. . ...... ... =..,_.jr r....
r-
. v-:-:,, >.>-xstss i&ieir^-kxu ,J.% ' f.
Dear Mr. Levenhagen:
`t;-
We appreciate the materials on the subject file- which you have-sent/
us, most recently on September 5th.- -
-=r
As you know, the mission of our. Institute Is to promote safety^T^ theS^^^^'f manufacture, transfer, packaging and use of chlorinei-- Whlle our memberships^ does not encompass chlorine consumers such as the Mead Corporation-/.Cexcludlng^- " .* ' wt* 7 ^-producers whose output Is for captive -use), our servlces-extend.to-anyonerjuc:se -'Concerned with chlorine safety. It Is, therefore, essential: tha^otiii:pmiuce-^r
in such matters truly reflects an industry.consensus^-^at wel 1 jas/`tha^piiir>^.^/' understanding of statutes and regulations derived therefrom be;coFrectri'~ ?"
We have read the contents of M 4463*513 and the .associated notice of'contest/^
as related to 29CFR192&.103(a) [Regulations for Construction! .;Quc Inters 1
pretation of Table 4, anent contaminants immediately dangerous. to^ l ife or- .
health. Is that it provides for mouthpiece respirators as enviable personal V
protection means for escape purposes. We do not interpret that in such- - - -
.c!rcumstances-_provislop.for full facepiece respirators, is mandatedi^FTnF^ -
fact, it Is theTuniversal position of the chlorine industry, basedon^ltxi^:?""
years of experience and evaluation, that the. mouthpiece, respIratofelSr-Vastiy^:;
superior to the full facepiece respirator In affordIng-effectlve ancbImmedlate;
protection In the event of an emission during the course of normaTjwork ' ~ "
operations. Our reasons include; . ;
^
.t
* Facial features. In addition to hair and spectacles, make an:,:"Zr. adequately tight fit of facepiece respirators essentlaljy impossible.
* Donning time for full facepiece respirators, particularly for the untrained and inexperienced, is too long for workers exposed-to.____ ___ ._ high chlorine concentrations;
C 003462
& Continued...
4
I Oceaputioatl Safety tad Hsmith Adauautrmtraa
!1
OohsBhta Am Oific--Region V ; Federal Offle* Bldg., Room 634
t 200 North High Street
1
Cohmsbu*, Ohio 43219
2: October 19, 1978'
t 1<
\
Mr. Edward J. Laubusch, Technical Manager The Chlorine Institute, Inc. 342 Madison Avenue New York, NY 10017
Dear Mr. Laubusch:
I found your letter on the use of respiratory protection in areas of chlorine exposure very interesting. Your letter, as you recall, was in reference to an OSHA Citation (M4463-513) for violation of 29 CFH 1926.103 (a) You stated in your letter that your interpretation of Table E-4 under this section does not mandate the use of full-facepiece respirators.
Examination of Table E-4 reveals that under the "Hazard" column, chlorine ~
falls under the classification of "Gas and vapor contaminants immediately ' .1' .
I dangerous to life and health". The respirator requirement for this - --
`J hazard category does, indeed, permit the use of a self-rescue mouthpiece s.
respirator for escape purposes. However, it is a recognized hazard that--%.
2 !
chlorine gas is highly irritating to the eyes. This fact is further . ' -1."--supported by the National Institute for Occupational Safety and Health'^-'' -' -I
(NI0SH) Recommended Standard for exposure to Chlorine: (HEN Publication
No. (NIQSH) 76-170), and OccuDational Diseases: A Guide to Their Recog- . 1
nition (D-HSW Publication No. (NIOSH) 77-181)7
?\-r' -
The reason OSHA has required, in this particular citation, full-facepiece
* I respirators is for eye, as well as, respiratory tract protection.: Escape^^ -
i from the area of a chlorine leak may be seriously hindered by the irritating" ~ '
effects of chlorine in the eyes.
... . 1. ;7 .. .T' '
Your considerations you have expressed are, in some situations, valid but in
the case of chlorine, I believe full-facapiece respirators to be the best-
means of protection.-
_
.Should you have any further comments or questions on this subject, I would
be happy to discuss them with you.
... . .
....... .
Sincerely,
^pyj-Thomas E. Levenhagen Area Director
ncrS419%)
SDEidh
A
j?-
C"003463
y
- a-. ; **!- .>;*? .
!tl .lilt \ i Hi
'.- .a
.>..f ,
.* ?
t-.
' *<*
Octobar 31* 1978
ii
. t *'
**'* *
Hr. Peter Schmitt tl.S. Department of Labor Federal Office Building *
200 North High Street Columbus, OH 43215
Rou 634
Dear Hr. Schmitt:
Thank you for your letter of October 19, 1978 In response to ours of September 21 to Hr. Levenhagen concerning OSHA Citation HW63-513.
While there certainly can be no debate that chlorine in sufficient concentrations, Is a lachrymator, we believe more significant In this Instance Is the excellent warning property of chlorine at concentrations well below that which could
.< cause any serious human physiological discomfort or disturbance. The character-'*
Istlc odor threshold for chlorine Is generally accepted-to be about 0.35 ppm and even lower among more sensitive Individuals; that level, as you are aware. Is considerably below the current TLV of 1 ppm. As concentration levels Increase, the intensely Irritating effect of the gas makes It unlikely that any person will remain In a chlorine ^contaminated atmosphere unless he Is unconscious or trapped*.-
It Is noted that you cite the NIOSH Criteria Document for chlorine to support,
at least In part, your posture relative to the citation of Issue. (Incidentally,
while the document Is In the public domain. It has never been published In the
Federal Register for pub! 1c Input, and of course no ralemaking procedure to amend
29CFR1910.1000 has ever bean proposed.) The institute Is In disagreement with
much of the material therein contained. Including the sensory-based, recommended
0.5 PP celling value for occupational exposures to chlorine (In lieu of the 1 ppm
time-weighted average.) Notwithstanding, the chlorine criteria apply `fonly to tha
processing, manufacture, use and handling of chlorine...and any extrapolation
beyond occupational exposures Is not necessarily warranted.'*
**'.
In your latter, you state 'The reason OSHA has required. In this particular citation, full-faceptece respirators Is for eye, as well as, respiratory tract protection." And you add that "Escape from the area of e chlorine leak may be seriously hindered by the frratatlng effect of chlorine In the eyes." We dis
agree with your reasoning for these reasons. In addition to those cited In our letter of September 21:
Continued...
* --
C 003464
'
| | I 1
I ..I
1
Mr. Peter Schmitt U.$. Department of Labor
Page -2-
#
- |f, as Is a fact* HIOSH approves of mouthpiece respirators even *for escape purposes only," why should the Head occurrence entail any more restrictive requirements? That Is to say. In any cat** astrophle escape situation, the possibility of lachrymatlon effects
exists.
While we have no expertise In the general matter of OSIIA 1926 '* standards applicable for construction, we would suppose that such
appropriate head and eye protection regulations as necessary would be appltcab1e-*or otherwise Implied under the general duty clausa. And on that basis, goggles providing eye protection from Irritants' ' (Including chlorine) would probably have been required.
Especially In tight spaces (la. In a boiler as was the case In the Head contractor Incident), not only would full facepiece respirators - -* be impractical as to bulk and Impediment, but they might very welt-, have become damaged and Inoperative, as well as contributing other safety hazard potential.
Again, Industry experience In the matter of chlorine emissions and protection therefrom Is contrary to your opinion as to the relative merits of escape ys.' facepiece respirators. Please refer to the enclosed repttnf;, "Quantitative, fit Testing of Personnel Utilizing a Mouthpiece Respirator."
In our Judgement, your position. In effect, proposes that full facepiece respirators should be providedrand used, even for. escape purposes, wherever- ' and whenever there exists the potential for a chlorine leak'. That, we believe,. Is tantamount to a blanket requirement wherever chlorine Is manufactured^ "packaged, transferred, stored and used. Ve respectfully disagree, both In principle and In your Interpretation of the OSHA standard.
Very truly yours. THE CHLORINE INSTITUTE, INC
Edmund J. Laubusch EJL/deb Enclosure.
i,
ri
*? .-v- A
*, a m Z-i
' . * * */* . .J*it V'vt - -**v.*r".
'.r
T :
'it'. . Ct;
.V
:.*?
* e r.
> * fw
c.< i V
.f
* V^.<
% . ,& e, A.*
t ,*
C 003465
Tie Enjckerbocker News
ALBANY, N. Y. D 60.813
_ OCT 181978
.
Area firm
in wake of. gas leak
By ERIC FREEDMAN
occurred. '
,.
' i.
'"T" Tha U.t Occupational Safety and In addition, the agency found the
Health Administration has fined Man* company had no written standard aner-- ....
- sing Paper Co. of Green Island $1,500 , ating procedure far the usp of retpira. , -
. following a chlorine gas leak that hospj- too.- that some respirators were not '
p talized 21 personslast Aug. 22.
stored properly and were covered with
; The administration found four seri-
-r cits violations of safety and health re* r- qnxrements, including an inoperablet 'ddorine detector and no respiratory
tools, and that respirator* aimarW
and gas
tighly
inspected at least once a month,
required.
The citation also charged the com* ,
- J employees. The firm, a 'division, of pany fails to have suitable emergency-:;
r Hammermill Paper Co., still has time facilities for workers to flush their eyes '
to challenge the citation and penalty. . and drench their bodies in case of .
The leak happened about 10:30 a.m. chemical contamination. The agency '
^ . ..
said led to the evacuation of 200 area residents from their homes near the . George Street plant Eighteen Manning employees and three other persons in
also found chlorine gas was not carried . awav by an exhaust system and was not neutralized before being discharged '
Into the atmosphere,- /
~ the neighborhood were taken to Chlorinera corrosive, is used by j
I Samaritan and St Mary's hospitals in Manning as part of a bleaching process -
Troy.
. '
in papermaking.
s . .;
' - The administration charged Man* At low levels, the gas can causa a ;
ning Paper failed to provide a safe stinging and burning sensation of the
'. place to work. In particular, the dta* eyes, nose and throat, nosebleeds,
* tion mentioned two emergency chlorine headaches and skin irritation. /.
' detectors that were not routinely and In higher concentrations, it can
_ adequately inspected, tested and main? cause lung damage, and exposure to pfoined. One detector did not work at all. excessive levels may be fatal, accord- ..
r in the blyscb bouse, where the leak' ing to chemists,,^
1
C 003466
?
OCCUPATIONAL SAFETY AND HEALTH
(ii) Goggles that can be worn over correc tive spectacles without disturbing the adjustment of the spectacles.
(iii) Goggles that incorporate corrective lenses mounted behind the protective lenses.
(4) Every protector shall be distinctly marked to facilitate identification only of the manufacturer.
1910.133()(3)<ii)
STANDARDS AND INTERPRETATIONS
(5) When limitations or precautions are
indicated by the manufacturer, they shall
be transmitted to the user and care taken
to see that such limitations andprecautions
are strictly observed.
l
(6) Design, construction, testing, and use of devices for eye and face protection shall be in accordance with American National Standard for Occupational and Educational
Eye and Face Protection, Z87.1-1968.
3910.134--SSSPiRATORY PROTECTION
(a) Permissible practice.
(1) In the control of those occupational dis eases caused by breathing air contaminated with harmful, dusts, fogs, fumes, mists, gases, smokes, sprays, or vapors, the pri mary objective shall be to prevent at mospheric contamination. This shall be accomplished as far as feasible by accepted engineering control measures (for example, enclosure or confinement of the operation, general and local ventilation, and substitu tion of less toxic materials). When effective engineering controls are not feasible, or while they are being instituted, appropriate respirators shall be used pursuant to the following requirements.
(2) Respirators shall be provided by the employer when such equipment is neces sary to protect the health of the employee. The employer shall provide the respirators which are applicable and suitable for the purpose intended. The employer shall be responsible for the establishment and maintenance-of a respiratory protective program which-shall include the require'ments outlined in paragraph (b) of this sec tion.
(3) The employee shall use the provided respiratory protection in accordance with instructions and training received.
governing the selection and use ofrespirators shall be established.
(2) Respirators shall be selected on the basis of hazards to which the worker is exposed.
(3) The user shall be instructed and trained
in the proper use of respirators and their
limitations.
.' .
(4) Where practicable, the respirators'
should be assigned to individual workers for their exclusive use.
(5) Respirators shall be regularly cleaned
and disinfected. Those issued for the exclu sive use of one worker should be cleaned after each day's use, or more often if neces sary. Those used by more than one worker shall be thoroughly cleaned and disinfected after each use.
(6) Respirators shall be stored in a conven ient, clean, and sanitary location.
(7) Respirators used routinely shall be inspected during cleaning. Worn or
deteriorated parts shall be replaced. Res-_
pirators for emergency use such. as_self=-- containecT devices_sKali__ be_ thoroughly inspected at~least once a month and after" - each'useT--1
(b) Requirements for a minimal acceptable program.
(8) Appropriate surveillance of work area conditions and degree of employee exposure or stress shall be maintained.
(1) Written standard operating procedures
339
1910.134(b)(8)
C 003467
f910.134(b)(9) STANDARDS AND INTERPRETATIONS
OCCUPATIONAL SAFETY AND HEALTH
(9) There shall be regular inspection and evaluation to determine the continued effectiveness of the program.
(2) Breathing air may be supplied to
respirators from cylinders or air compres sors.
(10) Persons should not be assigned to tasks requiring use of respirators unless it has been determined that they are physically able to perform the work and use the equip ment. The local physician shall determine what health and physical conditions are pertinent. The respirator user's medical status should he reviewed periodically (for instance, annually).
(11) Approved or accepted respirators shall be used when they are available. The respirator furnished shall provide adequate respiratory protection against the par ticular hazard for which it is designed in accordance with standards established by competent authorities. The U.S. Depart ment of Interior, Bureau of Mines, and the U.S. Department of Agriculture are recog nized as such authorities. Although respirators listed by the U.S. Department of Agriculture continue to be acceptable for protection against specified pesticides, the U.S. Department of the Interior, Bureau of Mines, is the agency now responsible for testing and approving pesticide respirators.
(c) Selection of respirators.
Proper selection of respirators shall be made according to the guidance of American National Standard Practices for Respiratory Protection Z88.2-1969.
(d) Air quolity.
(i) Cylinders shall be tested and main tained as prescribed in the Shipping Con tainer Specification Regulations of the Department of Transportation (49 CFR Part 178).
(ii) The compressor for supplying air shall be equipped with necessary safety and standby devices. A breathing air-typecompressor shall be used. Compressors shall be constructed and situated so as to avoid entry of contaminated air into the system and suitable in-line air purify ing sorbent beds and filters installed to further assure breathing air quality. A receiver of sufficient capacity to enable the respirator wearer to escape from a contaminated atmosphere in event of compressor failure, and alarms to indicate compressor failure and overheat ing shall be installed in the system. If an oil-lubricated compressor is used, it shall have a high-temperature or carbon monoxide alarm, or both. If only a high- temperature alarm is used, the air from the compressor shall be frequently tested for carbon monoxide to insure that it meets the specifications in subparagraph (1) of this paragraph. .,
(3) Air line couplings shall be incompatible' with outlets for other gas systems to pre- ' vent inadvertent servicing of air line respirators with nonrespirable gases or oxygen.
(1) Compressed air, compressed oxygen, liquid air, and liquid oxygen used for respi ration shall be of high purity. Oxygen shall
meet the requirements of the United States Pharmacopoeia for medical or breathing
oxygen. Breathing air^stiafl meet at leastthe requirements of the specification for Crude D breathing air as described in Com pressed Gas Association Commodity Specifi cation C-7.!~11HJ(>. Compressed oxygen shall not be used in supplied-air respirators or in open circuit self-contained breathing apparatus that have previously used com pressed air. Oxygen must never be used
with air line i espii alors.
(4) Breathing gas containers shall be
marked in accordance with American
National Standard Method of Marking Port
able Compressed Gas Containers to Identify
the Material Contained-, Z4S.1-1954;
Federal Specification BB-A-1034a, June 21,
1968, Air, Compressed for Breathing Pur
poses; or Interim Federal Specification
GG-B-00675br April 27, 1965, _ Breathing
Apparatus, Self-Contained. _ --
-
(e) Use of respirators.
(f) Standard procedures shall be developed for respirator use. These should include all
1910.134(e)(1)
340
A C 003468
V5-
OCCUPATIONAL SAFETY AND HEALTH
information and-guidance necessary for their proper selection, use, and care. Possi ble emergency and routine uses of respirators should be anticipated and planned for.
(2) The correct respirator shall be specified for each job. The respirator type is usually specified in the work procedures by a qual ified individual supervising the respiratory protective program. The individual issuing them .shall be adequately instructed to insure that the correct respirator is issued. Each respirator permanently assigned to an individual should be durably marked to indicate to whom it was assigned. This mark shall not affect the respirator performance ir. any way. The date of issuance should be recorded.
(3) Written procedures shall be prepared covering safe use of respirators in danger ous atmospheres that might be encountered in norma! operations or in emergencies. Per
sonnel shall be familiar with these proce dures and the available respirators.
(i) In areas where the wearer, with failure
of the respirator, could be overcome by a toxic or oxygen-deficient atmosphere,
at least one additional man shall be pres
ent. Communications (visual, voice, or
signal line) shall be maintained between
both or all individuals present. Planning
shall be such that one individual will be
unaffected by any likely incident and
have the proper rescue equipment to be
able to assist the other(s) in case of emer
gency.
.
(ii) When self-contained breathing
apparatus or.hose masks with blowers are used in atmospheres immediately dan gerous to lifor health, standby men must > be present with suitable rescue equip ment.
(iii) Persons using uir line respirators in atmospheres immediately hazardous to
life or health shall be equipped with .safely harnesses anti safely lines for lift ing or removing persons from hazardous atmospheres or other and equivalent pro visions for 1 hit fescue of persons from hazardous atmospheres shall he used. A standby man or men with suitable self-
1910.134(e)(1)
STANDARDS AND INTERPRETATIONS
contained breathing apparatus shall be at the nearest fresh air base for emer gency rescue.
(4) Respiratory protection is no better than
the respirator in use, even though it is worn
conscientiously. Frequent random inspec tions shall be conducted by a qualified
individual to assure that respirators are
properly selected, used, cleaned, and ma.n-
tained.
.^
(5) For safe use of any respirator, it is essen
tial that the user be properly instructed in its selection, use, and maintenance. Both
supervisors and workers shall, be so
instructed by competent persons. Training
shall provide the men an opportunity to
handle the respirator, have it fitted prop
erly, test its face-piece-to-face seal, wear it
in normal air for a long familiarity period,
and, finally, to wear it in a test atmosphere. A"
(i) Every respirator wearer shall receive
fitting instructions including demonstra
tions and practice in how the respirator
should be worn, how to adjust it, and how
to determine if it fits properly,, Res
pirators shall not be worn when condi tions prevent a good face seal. Such condi tions maybe a growth ofbeard, sideburns,
a skull cap that projects under the
facepiece, or temple pieces on glasses.
Also, the absence of one or both dentures can seriously affect the fit of a facepiece. The worker's diligence in observing these
factors shall be evaluated by periodic
check. To assure proper protection, the
facepiece fit shall be checked by the wearer each time he puts on- the
respirator. This may be done by following
the manufacturer's facepiece fitting
instructions.
.
(ii) Providing respiratory protection for individuals wearing cqrrective glasses is a serious problem. A proper seal cannot be established if the temple bars of eye . glasses extend through, the sealing edge
of the full facepiece. As a temporary measure, glasses with short temple bars or wit limit temple bars may be taped to the wearer's head. Wearing of contact lenses in contaminated atmospheres with a respirator shall not. be allowed; Systems have been developed for mbuntiogcoi rec-
l,J10.13`l(e)(5)(ii)
c 003469
* 1910.134(e)(5)(H)
OCCUPATIONAL SAFETY AND HEALTH
STANDARDS and interpretations
' . . -yi or.odi-^ii :
tive lenses inside full facepieces. When a
workman must wear.corrective lenses as
part of the facepiece^he facepiece and.
lenses shall be fitted'by 'qualified in
dividuals to provide good vision, comfort,
and a gas-tight seal. ' 1
(iii) if corrective spectacles or goggles are
required, they shall be worn so as not to
affect the fit of the facepiece. Proper
selection of equipment will minimize or
avoid this problem. -
7
bands, valves, connecting tube, and canis ters. Rubber or elastomer parts shall be inspected for pliability and signs of deterioration. Stretching and manipulat ing rubber or elastomer parts with q mas saging action will keep them pliable and flexible and prevent them from taking a set during storage.
(iv) A record shall l>e kept of inspection dates and findings for respirators main tained for emergency use.
(f) Maintenance and care.of respirators.
(1) A program for maintenance and care of respirators shall be adjusted to the type of plant, working conditions, `and hazards involved, and.shall include the following basic services:
(i) Inspection for defects (including a leak check),
(ii) Cleaning and disinfecting,
(iii) Repair,
(iv) Storage
Equipment shall be properly maintained to retain its original effectiveness.
(2)
(i) All respirators shall be inspected
routinely before and after each use. A
respirator that is not routinely used but
is kept ready for emergency use shall be
inspected after each use and at least .
monthly to assure, that it is in satisfactory
workingconclitipib^^fr.^r
- . '---rfg-r - !l "5"
_
...
(ii) Si*lf-c>nlaiiu>iEllrialhing apparatus
shall he inspected monthly. Air and
oxygen cylinders shall lie TuIIy charged
according to the manufacturer's instruc
tions. It shall be determined that the reg
ulator and warningdeviees function prop
erly.
(iii) Respirator inspection shall include a check of the tightness of connections and the condition of the facepiece, head-
(3) Routinely used respirators shall be col
lected, cleaned, and disinfected as fre
quently as necessary to insure that proper
protection is provided for the wearer. Each
worker should be briefed on the cleaning
procedure and be assured that he will
always receive a clean and disinfected
respirator. Such assurances are of greatest
significance when respirators are not
individually assigned to workers. Res
pirators maintained for emergency use-
shall be cleaned and disinfected after each
use.
-
(4) Replacement or repairs shall be done only by experienced persons with parts designed for the respirator. No attempt shall be made to replace components or to make adjustment or repairs beyond the manufacturer's recommendations. Reduc ing or admission valves or regulators shall be returned to the manufacturer or to a trained technician for adjustment or repair."
(S)
(i) After inspection, cleaning, and neces sary repair, respirators shall be stored to protect against dust, sunlight; , heat, extreme cold, excessive moisture, or damaging chemicals. Respirators placed at stations and work areas for emergency use should be quickly accessible at all times and should he stored'in compart ments built for the purpose. The compart ments should be clearly ' marked. Routinely used respirators, such as dust respirators, may be placed inplastic bags; Respirators should not be stored in such places as lockers or tool boxes unless they are in carrying cases or cartons.
19 I0.i34ff)( 5 )(i)
342
c 003470
OCCUPATIONAL SAFETY AND HEALTH
(ii) Respirators should be packed or stored .so that the facepiece and exhalation valve will rest in a normal position and function will not In impaired by the elastomer set ting in an abnormal position.
(iii) Instructions for proper storage of emergency respirators, such us gas masks and self-contained breathing apparatus, are found in "use and care" instructions u-uaHy mounted inside the carryingcase
(g; Identification of gas mask canisters.
(1) The primary means of identifying a gas mask canister shall be by means of properly worded labels. The secondary means of iden tifying a gas mask canister shall be by a color code.
(2) All who issue or use gas masks fal.ing - within the scope ofthis section shall see that all gas mask canisters purchased or used by them are properly labeled and colored in accordance with these requirements before they are placed in service and that the labels and colors are properly rnainr tained at all times thereafter until the canisters have completely served their pur pose. ;
(3) On each canister shall appear in bold let ters the following:
(')--
Canister for.................................................................. (Name for atmospheric contaminant) or Type N Gns Mask Canister
(ii) In addition; essentially the following wording shall appear beneath the appro priate phase on the canister label: "For
1910.134(f)(5)(H)
STANDARDS AND INTERPRETATIONS
respiratory protection in atmospheres containing not more than ......... per cent by volume of.......................................
(iii) All of the markings specified above should be placed on the most conspicuous surface or surfaces of the canister.
(4) Canisters having a special high-effi
ciency filter for protection against
radionuclides and other highly toxic par
ticulates shall be labeled with a statement
ofthe type and degree ofprotection afforded
by the filter. The label shall be affixed to-
the neck end of, or to the gray stripe which
is around and near the top of, the canister.
The degree of protection shall be marked,
as the percent of penetration of the canister
by a 0.3-micron-diameter dioCtyl phthala'te
(DOP) smoke at a flow rate of 85 liters per
minute.
..............
v.
(5) Each canister shall have a label warning.,
that gas masks should be used only in.
atmospheres containing sufficient oxygen
to support life (at least lp percent by
volume), since gas mask canisters are only
designed to neutralize or remove contami
nants from the air,.
____ : ___
(6) Each gas mask canister shall be painted' a distinctive color or combination of colors indicated in Table 1-1. All colors used shall
be such that they are clearly identifiable by the user and clearly distinguishable from one another. The color coating used shall
offer a high degree of resistance to chipping, scaling, peeling, blistering, fading, and the effects of the ordinary atniospheres to which they may be exposed under normal conditions of storage and use^ Appro
priately colored pressure sensitive tape, may be used for the stripes. '
343
1910.134(g)(6)
c 003471
*
1910.135
* T------------------------------------------------
STANDARDS AND INTERPRETATIONS
OCCUPATIONAL SAFETY AND HEALTH
Table 1-1
Atmospheric contaminants to be protected against
Acid gases---------------------------------------------------Hydrocyanic acid gas
Chlorine gas--------------------------- _-------------------
Organic vapors_____________ Ammonia gas Acid gases and ammonia gas
Carbon monoxide... Acid gases and organic vapors Hydrocyanic acid gas and chloroplcrln vapor.
Acid gases, organic vapors, and ' ammonia gases.
Radioactive materials, excepting tritium and noble gases.
Particulates (dusts, fumes, mists, fogs, or smokes) In combination with any of the above gases or vapors.
All of the above atmospheric contaminants. _
Colors assigned*
White.
White with %-lnch green stripe completely
around the canister near the bottom. .
White with % "Inch yellow stripe completely
around the canister near the bottom.
Black.
Green.
Green with Vfc-inch white stripe completely
around the canister near the bottom.
Blue.
Yellow.
Yellow with V4-lnch blue stripe completely
around the canister near the bottom. Brown.
Purple (Magenta).
Canister color for contaminant, as designated above, with Vi "Inch gray stripe completely around the canister near the top.
Red with %-inch gray stripe completely around the canister near the top.
"Gray shall not be assigned as the main color for a canister designed to remove acld3 or vapors.
Note: Orange shall be used as a complete body, or stripe color to represent gases not included In this table. The user will need to refer to the canister label to determine the degree of protection the canister will afford.
1910.135--OCCUPATIONAL HEAD PROTECTION
Helmets for the protection of heads of occu pational workers from impact and penetration from falling and flying objects and from limited electric shock and burn shall meet the
requirements and specifications established in American National Standard Safety Requirements for Industrial Head Protection,
Z89.1-19G9.
1910.136--OCCUPATIONAL FOOT PROTECTION
Safety-toe footwear for employees shall meet tin* requirements ami speeifications in
American National Standard for Men's Safety-Toe (''outwear, Zll.l-liMil.
1910.136
344
C 003472
FOR RESPIRATORY PROTECTION
the wearer in carrying out hi3 work should be considered in respirator selection.
Air-purifying respirators present minimal in
terference with tfigyveareris movement. Sup-
plied-air respirato^with trailing hoses severely
restrict the area tiSs; wearer can cover and pre
sent a potential hazard where the trailing hose
can come in contact with machinery. Self-con
tained breathing apparatus present a size and
weight penalty which may restrict climbing and
movement in tight places.
_
The wearer's work rate determines his res piratory minute volume, maximum inspiratory flow rate, and inhalation and exhalation breath
ing resistance. The respiratory minute volume is of great significance in self-contained and air line respirators operated from cylinders since it determines their operating life. Useful life under moderate work conditions may be one-third that under rest conditions.
Peak airflow rate is important in the use of constant-flow air-line equipment. The air-supply rate should always be greater than the peak inspiratory flow rate to maintain the respiratory enclosure under positive pressure;
High breathing resistance of air-purifying respirators under conditions of heavy work can result in distressed breathing.
6.5.3 Vision. All facepieces .will restrict, to some degree, the wearer's vision. This may in crease accident potential. Other problems in clude wearing of prescription glasses and fogging of the respirator lens (see 9.1,9.2, and 9.3).
65.4 Communications. Effective speech com munication may be required in jobs for which the respirator is being selected. Section 9.5 pro vides information in this subject..
65.5 Temperature.Extremes. The ability to cope with stress caused by temperature ex tremes is especially important in emergency situations when opljdiminediafely available res
pirators can b*y|^jgge 95'and 9.4 for further details onuseto|3i^grator iBrtemperature ex-
tremes.-gaSL'.jgss-Saj^gr-;'---55*----
65.6 Eye Protection. Where required, fullfacepiece respirator eyepieces and eye protection worn with half-mask facepieces-shall meet the pertinent requirements of American National Standard Practice for Occupational and Educa tional Eye and Face Protection Z87.1-1968.
6.6 Employee Acceptance and Face Fit. These factors are of prime importance in respirator
selection. The wearer's acceptance of a particu lar respirator depends on the lack of facepiece discomfort, interference with vision, weight of the device, breathing resistance, and individual physical condition and psychological factors. The ability to form a good facepiece-to-face seal depends on respirator design and facial features, and is usually the most important factor in obtaining proper protection with an air-puri fying respirator, particularly of the half-mask type. See 7.5 for a.discussion.of face-fit tests and procedures.
7. Use of Respirators
7.1 Operating Procedures. Standard proced ures shall be developed for respirator use. These should include all information and guidance necessary for their proper selection, use, and care. Possible emergency and routine uses of respirators should be anticipated and planned for. i
75 Issuance of Respirators. The correct res pirator shall be specified for each job. The res pirator type is usually specified in the work pro cedures by a qualified individual supervising the respiratory protective program. The individual issuing them shall be adequately instructed to insure that the correct respirator is issued. Each respirator permanently assigned to an individual should be durably marked to indicate to whom it was assigned. This mark shall not affect the respirator performance in any way. The date of issuance should be recorded.
7.3 Use in Dangerous Atmospheres. Written procedures shall be prepared covering safe use of respirators in dangerous atmospheres that might be encountered in normal operations or in emergencies. Personnel shall be familiar with these procedures and the available respirators.
In areas where the wearer, with failure of the respirator, could be overcome by a toxic or oxygen-deficient atmosphere, at least one addi tional man shall be present. Communications (visual, voice, or signal line) shall be maintained between both or all individuals present. Plan ning shall be such that one individual will be unaffected by any likely incident and have the proper rescue equipment to be able to assist the other(s) in case of emergency. See 6.3.1 and 6.3.2 for guidance on selection of respirators for use in dangerous atmospheres.
23
C 003473
*
Z83.2
AMERICAN NATIONAL STANDARD PRACTICES
7.4 Training and Education in- Proper -Use.
For safe use of any respirator, it is essential that
the user be properly instructed in its selection,
use, and maintenance. Both supervisors and
workers shall be so instructed by competent.
persons.
"
Minimum training shall include the following?
(1) Instruction in the nature of the hazard, whether acute, chronic, or both, and an honest appraisal of what may happen if the respirator is not used.
(2) Explanation of why more positive con trol is not immediately feasible. This shall in clude recognition that every reasonable effort is being made to reduce or eliminate the need for respirators.
(3) A discussion of why this is the proper type of respirator for the particular purpose.
(4) A discussion of the respirator's capabil ities and limitations.
(5) Instruction and training in actual use Of the respirator (especially a respirator for emergency use) and close and frequent super vision to assure that it continues to be properly used.
(6) Classroom and field training to recog nize and cope with emergency situations.
(7) Other special training as needed for spe cial use.
Training shall provide the men an oppor tunity to handle the respirator, have it fitted properly, test its facepiece-to-face seal, wear it in normal air for a long familiarity period, and,
finally, to wear it in a test atmosphere.
7.5 Facepiece Fit Tests and Procedures. Every respirator wearer shall receive fitting in structions including demonstrations and prac tice in how the respirator should be worn, how to adjust it, and how to determine if it fits properly. Respirators shall not be worn when conditions prevent a good face seal. Such con ditions may be a growth of beard, sideburns, a skull cap that projects under the facepiece, or temple pieces on glasses. Also, the absence of one or both dentures can seriously affect the fit of a facepiece. The worker's diligence in ob serving these factors shall be evaluated by
periodic checks. To assure proper protection, the facepiece fit
shall be checked by the wearer each time heputs on the respirator. This may be done by
following the manufacturer's facepiece-fitting instructions such as these two simple field tests:
(1) Positive Pressure Test Close the exhala tion valve and exhale gently into the facepiece. The face fit is considered satisfactory if a slight positive pressure can be built up inside.the facepiece without any evidence of outward leakage of air at the seal. For most respirators, this method of leak testing requires that the wearer first remove the exhalation valve cover and then carefully replace it after the test.
(2) Negative Pressure Test. Close off the inlet opening of the canister or cartridge(s) by covering with the palm of the hand(s) or by replacing the seal(s), inhale gently so that the facepiece collapses slightly, and hold the breath for ten seconds. If the facepiece remains in its slightly collapsed condition and no inward leakage of air is detected, the tightness of the respirator is probably satisfactory.
Potential users of respirators should also be required to test their facepiece fit by wearing the respirator under realistic test conditions. 4 concentration of 100 parts per million isoamyl, acetate vapor (obtained by vaporizing 17.3 milli liters of isoaroyl acetate for each 1,000 cubic feet of room volume) may be prepared in a special chamber, a small plastic enclosure, or in a vacant room. If the person wearing the respirator can enter and remain in this test atmosphere without detecting the odor of isamyl acetate, he has a good fit If he detects the odor, he should retreat to fresh air, readjust the facepiece, and repeat the test If leakage is still noted, it can be concluded that this particular respirator will not protect the wearer. The wearer should not continue to tighten the headband straps until they are un comfortably tight, simply to achieve a gas-tight face fit. If fitted too tightly, the wearer will not wear the respirator or will wear it fitting com fortably loose and will not have a gas-tight seal.
Particulate-filter respirators can frequently be adapted for use with chemical cartridges and may also be tested for face fit in isoamyl acetate^
To check the fit of a respirator equipped with a high-efficiency particulate filter, an irritant' smoke tube (glass tube 12 centimeters long by 1 centimeter diameter, filled with stannic chlor ide-impregnated pumice) produces a very irritating smoke when air is blown through it. The smoke is directed at the facepiece seal and leakage is indicated by irritation of the throat and lungs. (When testing half-mask facepieces.
24
I
C 003474
FOR RESPIRATORY PROTECTION
Z88.2
do not direct the smoke into the eyes and in struct the wearer to keep.his eyes closed during the test.) Freshlj^fcrjrfuced smoke particles from this tube ran^^mm-less than 0.1 to 3 mi crons in diametegia||tfffea tube is scored at
each end for easy brStkitigSA squeeze bulb with a short rubber tube aspirates air through the tube; visible smoke is immediately formed by contact with moisture in the air. The irritant is hydrochloric acid absorbed on the particulate. A similar smoke is produced with a sulfur, trioxide or titanium tetrachloride tube.
Several methods of determining facepiece fit are described in detail in the Respiratory Pro tective Devices Manual, published by the Amer ican Industrial Hygiene Association and the American Conference of Governmental Indus trial Hygienists in 1963. .
. 8. Maintenance and
Care of Respirators
8.1 General. A program for maintenance and
care of respirators shall be adjusted to the type
of plant, working conditions, and hazards in
volved,- and shall: include the following basic
services:-
~-
(1) inspection for defects, (including a leak check) - .
(2) cleaning'and disinfecting
(3) repair
' ^ -:r
(4) storageT
--
. Equipment shall be properly maintained to
retain its original effectiveness.
8.2 Inspection. All respirators shall be inspected
routinely before and after.each use. A respirator
that is not-routinely'Used but is kept ready for
emergency use shalLbe inspected after each use
and aHeasfmonth]y3aa*SU|&that it is in satis-
factory,workin'g"c^3^wB$fe;^'.
: Self-containedj^SS|^^apparatua shall be
inspected ftobthj^Bl^ampoxvgen cylinders
shall be fuUyfch^^^^^^mg to the manu
facturers instructions. lt"shall be determined
that the regulator and warning devices function
properly?-vTM
^
Respirator inspection shalfinclude a check of
the tightness of connections and the condition
of the facepiece, headbands, valves, connecting
tube, and canisters. Rubber or elastomer parts
shall be inspected for pliability and signs of de
terioration. Stretching and manipulating rubber
or elastomer parts with a massaging action will keep them pliable and flexible and prevent them from taking a set during storage.
A record shall be kept of inspection dates and findings for respirators maintained for emer gency use.
8.3 Cleaning and Disinfection. Routinely used respirators shall be collected, cleaned, and dis infected as frequently as necessary to insure that proper protection is provided for 'the wearer. Each worker should be'briefed on the cleaning procedure and be assured that he will always receive a clean and disinfected respira tor. Such assurances are of greatest significance when respirators are not individually assigned to workers. Respirators 'maintained for emer gency use shall be cleaned and disinfected after each use.
The following procedure is recommended for cleaning and disinfecting respirators:
(1) Remove any filters, cartridges, or canis-. ters. I
(2) Wash facepiece and breathing tube in i cleaner-disinfectant or detergent solution (seer; following paragraphs). Use a hand brush to fa cilitate removal of dirt.
(3) Rinse completely in clean, warm water.
(4) Air dry in a clean area.
(5) Clean other respirator parts as recom- _ mended by manufacturer.
(6) Inspect valves, headstraps, and other parts; replace with new parts if defective.
(7) Insert new filters, cartridges, or canis ters; make sure seal is tight.
(8) Place in plastic bag or container for stor age.
Cleaner-disinfectant solutions are available that effectively clean the respirator and contain a bactericidal agent. The bactericidal agent is generally a quaternary ammonium compound. The respirator may be immersed in the solution, rinsed in clean, warm water, and air dried.
Alternatively, respirators may be washed in a. liquid detergent solution, then immersed in: 1) a hypochlorite solution (50 parts per mil lion of chlorine) for 2 minutes; 2) an aqueous iodine solution (50 parts per million of iodine) for 2 minutes; or 3) a quaternary ammonium solution (200 parts per million of quarternary ammonium compounds in water with less than 500 parts per million total hardness).
25