INSTRUMENT' FUNCTION OUTLINE
DEPARTMENT
246
TITLE . #3 Still Receiver
SHEET
' 1 OF 4
WRITT'EN"BY"B'ia^Tey' TgjTE
Level ControlLOOP NUMBER-
.
& Alarm
' CLASSIFICATIONLCA-25_____
4/28/6 9 REAL BY '
DATE_ REV .NO,
1.0 ' NEED FOR LOOP
.
1.1
This loop is needed to insure that the receiver tank does
not overflow or run dry, either one of which would disrupt
the pressure conditions in the distillation system.
DESCRIPTION OF LOOP
.
'
'1.1.1- . Function
The function of this loop is to control the level in the still
. receiver, to sound an alarm on hi or low level, and to activate
interlock solenoid.
.
1.1.2 System Performance Required .
' The level should be maintained, -t 5" of set point. .
1.1.3 Accomplishment of Function
.
The level in the tank is sensed by a level transmitter which
.
sends a 3-15 psig air signal to a level controller. The
level controller compares this signal with a set point and
sends a 3-15 psig air signal, to a control valve to throttle,
flow from receiver. The transmitter also sends an air signal
to a dual unit pressure switch which activates an alarm on
.
high or low level.
To prevent loss of vacuum in receiver, an interlock closes
control valve when the receiver pump is shut down, or there
v.
is a loss of power to it.
PCB-ARCH-EXT0373973
INSTRUMENT FUNCTION OUTLINE
'
TITLE Still Receiver Level Contr. & Alarm
DEPARTMENT LOOP NUMBER
SHEET____
2OF_______________4________________________ CLAS S IF I CAT I ON
2
. '
COMPONENT AND CALIBRATION DATA `
246____
-0-2-S--LCA-25
OPERATING DATA
. .
A. LT-25 Level Trans. & Controller
LC-25
.
.
Location: 14' level, over tank
.
.
508
Air Supply: 20 psig
Output: 3-15 psig (Trans. &
Contr.)
Action: Inc. input
1 . Inc. output
' MECHANICAL DATA
A. Fisher Gov. Level Trans.
#2500T~249BP & Level Contr.
#2516 W/Piped & Mtd. Air Set
4" R.F. Fig. 316 SS Body
316 SS Displacer; l~l/8" O.D.x 63"
.
Lg.
Displacer
. .
'
.
Ext. Length: 14"
.
. Prop. Eand: 10-200%
Calibration Pull: 0-3# 11 oz
Serial No.: 4464407
.
'
Zero Setting:
.
Span:
.
IPMO: 127
.
Torque Tube 1K4493-000A
B. LV-25 Control Valve.
Location: Gnd. level, NE of
tank 508
Input: 3-15 psig
Action: Air to open
` .
Fails close
B. . .
.
Fisher Gov. Control Valve #667-BF
Actuator Size 30 Travel 3/4"
1" 150# Fig. 316 SS Body
3/4" 316 SS Micro-Flute Trim
Teflon Packing, Skirt-Top Guiding
IMO: 45
IPMO: 126
Packing Set: 1U2546-0101
'
Valve Plug: 2J7335-3507"
Seat Ring: 1R1262-3507
Serial: 4435030
Spare Valve St. Code: 07=75671
C. LSA-25 Pressure Switch
Location: Panel
Input: 3-15 psig
FCT: Hi & Low Level Alarms
.
SPDT Contact/115 V., 10 A.
High level alarm sounds at
55" from bottom bend line (90%)
Low level alarm sounds at 12" from bottom bend line (10%)
C. Barksdale Dual Unit Pres. Switch
#D2T-H18
Bronze -Diaphragm, 1/4" IPS
Range: 0-18 psig
Conduit Conn.: 1/2" NPS
Setting Trips at 4.2# on drop .
Setting Trips at 13.8# on rise
Stores Code: 44-73246
4 PCB-ARCH-EXT0373974
INSTRUMENT FUNCTION OUTLINE
S i
i-3 H v-3 H o 73
T
X)
D
)j / ! o REV
iz-is-h6\Aonrb sot. valve tPa/irsa* asomi, CU'
V'-'h
DATE0
A.PP'0.
FOR COWS". DSSCniTTICfJ -
~
cl "f|
KOrfSANTO COMPANY
..
! jj
Ifl
(!) iTti;/ 2-5oa ITv` 2-515
71 ` MO
/7\ Sis
a
i
1 (!> 7.
i 0 y-
-
/\ \/ UT/'.C 7.6 LT/UC. SO
*.o. HO. 1COO-3 20.1 o ias
iS.'A oua . iO.l 0055
IT
LSH/L&i. - 25 l.SK/ LC-.L - SO
0
t-V 7. 5 LV- SO
BILL 0"
'
OESCOiPTIOM
GISHER -GOV. " 7SOOT - T.r-3 o'? TRAWSUITTsS C' 25!(b COMTaO'-LUS1 >Jy/PiPS[3'"? MT` O. AiS? SVJY EA.x'X'iDW.c DOT-HIO DUAL
OMIT PS-iTi'S5U:?5 SWITCH riSHER - OOV. '' feCoT - Tj.'r 1", COivftWOL V^.uvs: HOR l-io HLGjS
0 7 - 510- 1- AIlP -I'/'T 0 ; SI7- 1- AHP -1 Y-J"
MATERIAL
xt.nK HO. QUA!*
0
7-b N 4-7
0 i z-jro
Z-S/7
DESCRIPTION
CENTRAL ENGINEERING DEPARTT5ENT, ST. LWIS. UI3SOGRI
tiiiiVVUij^-3w
MONSANTO COMPANY CONFIDENTIAL - Thie I'low.nc the conti-
~
dential property of Mono into Company mnt! ta to be ut X3 only by
utKorilcxl
and in th* interest ef Mon**nto. It must b*
recounted for; ehefl not be reproduced m wbo'e or out *ithoot hin written prrmtsfcion
from Uor.aanto: and must ba returned to fctensanto'a Central
Department at
any time open raqvort, biA In any event at completion of tKe work or job. The recipient
aprepe to to'tp co-nfidantial. and to require hr* litnt nnployea to tum confidential, the
ir.fornwti* contain** Ivareon. DiacloiiAe vf ttv IrrfoiToal ion Corrtni-ved ha/con oKtll t<a msde
'ly to tfps rornono wtvs require JL
informctian far their wvh on rJonnanto'a wojovta.
j C1V-3IOT3 ORGANIC
SCHEMATICS
SHEET 4
INSTKl'KpsT SCHEMATIC DIAGRAM LOOP HO.. LCA -_Vb d LC.VSO
function `^TK.U &5CE>VS?V;~CQMT R. <5 AuARt/,
CK2CMO
SCALE
AS-POQUSO *& CAta HAMV.&ElS |d-30 (.V^cLOr-w-t-t-r&Sy
&<* iSTTlM ruTiir^--
C.E.A. KO.
i icc^o
-WT3
Snzwcc NO.
IQ' reiNTS jojco to sab-cr
*4X, 811.00-j. Sur ly '7/7, 7 2-y- 7
246
DEPARTMENT
r
t-
PCB-ARCH-EXT0373975
INSTRUMENT FUNCTION OUTLINE '
DEPARTMENT246
TITLE
Sti11 Receiver Level Control LOOP NUMBER________025
SHEET
4
WRITTWEY ~
OF
4
' CLASSIFICATION
DATE'__JREV*BY '
DATE
LCA-25 REV.NO.
3.0 OPERATION OF LOOP
3.1 . NORMAL OPERATION
The operation of this loop is to maintain a constant level
in the still receiver. Will activate an alarm if the level
is too high or too low. Normal set point is 9# instrument
air.
High level is 55" from bottom bend line (90%).
Low level is 12" from bottom bend line (10%).
.
3.1.1 Start Up Instructions
Align manual valves and check air supply. Start receiver
" transfer pump. The level controller on the receiver tank
will allow continuous pump out without dead-heading the
pump.
.
'
.
1
3.1.2 Shut Down Instructions
Shut down receiver transfer pump and close manual valves.
'3.1.3 Manual' Operations
..
,
Place level controller on "Manual" and regulate air to
control valve.
.
.
3.2 ABNORMAL OPERATIONS
3.2.1 Air Failure
Air f.ailure to this loop will cause level in receiver to build up because auto valve in transfer line fails closed
3.2.2 Power Failure
.
- Power failure to this loop will cause loss of alarm and control if failure is to receiver transfer pump.
3.3
INTERLOCKS
One shut down.of still receiver it, will shut auto valve.