Document qmdNaMbDVEqvy6VygGaKK1ewM
American Society of Heating and Ventilating Engineers Guide, 1936
2. The estimated maximum heat in Btu per hour required to supply water heaters or other apparatus to be connected to the boiler.
3. The estimated heat emission in Btu per hour of the piping connecting the radiation and other apparatus to the boiler.
Estimated Maximum Load: Construed to mean the load stated in Btu per hour or the equivalent direct radiation that has been estimated by the purchaser to be the greatest or maximum load that the boiler will be called upon to carry. (A.S.H.V.E. Standard Code for Rating Steam Heating Solid Fuel Hand-Fired Boilers--Edition of April, 1932.)
The.estimated maximum load is given by8:
4. The estimated increase in the normal load in Btu per hour due to starting up cold radiation. This percentage of increase is to.be based on the sum of Items 1, 2 and 3 and the heating-up factors given in Table 2.
Table 2. Warming-up Allowances for Low Pressure Steam and Hot Water Heating Boilers^. bic
Design Load (Representing Summation op Items 1,2, and 3,d
Btu per Hour
Equivalent Square Feet of Radiation^
Up to 100,000 100,000 to 200,000 200,000 to 600,000 600,000 to 1,200,000 1,200,000 to 1,800,000
Above 1,800,000
Up to 420 420 to 840
840 to 2500 2500 to 5000
5000 to 7500 Above 7500
Percentage Capacity to Add fob Washing Up
65 60 .
55 50
45 40
'
This table is taken from the A.S.H.V.E. Code of Minimum Requirements for the Heating and Venti
lation of Buildings, except that the second column has been added for. convenience in interpreting the design,
load in terms of equivalent square feet of radiation.
.
bSee also Time Analysis in Starting Heating Apparatus, by Ralph C. Taggert (A.S.H.V.E. Transac
tions Vol. 19,1913); Report of A.S.H.V.E. Continuing Committee on Codes for Testing and Rating Steam
Heating Solid Fuel Boilers (A.S.H.V.E. Transactions, Vol. 36. 1930); Selecting the Right Size Heating
Boiler, by Sabin Crocker (Heating, Piping and Air Conditioning, March. 1932).
n
This table refers to hand-fired solid fuel boilers. A factor of 25 per cent oyerdcsi&n load is adequate when oil or gas are used as fuels.
d240 Btu per square foot.
Other things to be considered are:
5. Efficiency with hard or soft coal, gas, or oil firing, as the case may be. 6. Grate area with hand-fired coal, or fuel burning rate with stokers, oil, or gas.
7. Combustion space in the furnace.
_
8. Type of heat liberation, whether continuous or intermittent, or a combination of
both. 9. Miscellaneous items consisting of draft available, character of attendance, pos
sibility of future extension, possibility of breakdown, headroom in the boiler room. ;
Radiation Load
The connected radiation (Item 1) is determined by calculating the heat losses in accordance with data given in Chapters 5, 6 and 7, and'dividing by 240 to change to square feet of equivalent radiation as explained in Chapter 30. For hot water, the emission commonly used is 150 Btu per square foot, but the actual emission depends on the temperature of the medium in the heating units and of the surrounding air. (See Chapter 30.)
Although it is customary to use the actual connected load in equivalent square feet of radiation for .selecting the size of boiler, this connected load usually represents a reserve in heating capacity to provide for infiltration in the various spaces of the building to be heated, which reserve, however,
-' `
440 V
Chapter 25--Boilers
is not in use at all places at the same time, or in any one place at all times; For a further discussion of this subject see Chapter 6.
. Hot Water Supply Load When the hot water supply (Item 2) is heated by the building heating
boiler, this load must be taken into consideration in sizing the boiler. The
BOILER DATA--
OUTPUT, SQ. FT. EQUIVALENT STEAM RADIATION (240 BTU PER SQ. FT.)
CRATE AREA, SQ.FT. 16.0 HEATING 5URFAC;SQ.FT. 254
fuel-bituminous s/a-LUMP AMALYS*IS- VOLATILE MATTER 34.66/^
WEIGHT, LB. FUEL CAPACITY. LB.
FUEL AVAILABLE, LB. FUEL DEPTH,IN
0160 651
414 JO
FIXE CARBON ASH , . SULPHUR MOISTURE
55-44 0.67 2*66. 3-00
BTU PER LB.
IS.6JS
Fig. 1. Typical Performance Curves for a 36-in. Cast-Iron Sectional Steam Heating Boiler, Based on the A.S.H.V.E. Code for Rating Steam
Heating Solid Fuel Hand-Fired Boilers
allowance to be made will depend on the amount of water heated and its temperature rise. A good approximation is to add 4 sq ft of equivalent radiation for each gallon of water heated per hour through a temperature
range of 100 F. For more specific information, see Chapter 35.
Piping Tax (Item 3)
It is common practice to add a flat percentage allowance to the equivalent connected radiation to provide for the heat loss from bare and covered pipe in the supply and return lines; The use of a flat allowance of 25 per cent for steam systems and 35 per cent for hot water systems is preferable to ignoring entirely the load due to heat loss from the supply
441