Document qkwzN36mnnBmGzBp3XJVZXwmq
American Society oj Heating and Ventilating Engineers Guide
distance between inlet openings below and outlet openings abov
D is the temperature difference.
e>
The total force or head is consumed in forcing the air in at inlet ings, through the building, and out at the outlet openings. The/
required to move the air through the building is usually negligjui that the total head may be considered as being consumed at inlet^
outlet openings. The part of the total head consumed in forcing th * to flow through the lower or inlet opening will be manifested as an ex of outside pressure over inside pressure at that level; while at the mL,
or outlet opening, the part of the total head consumed in forcing the
out will be manifested as a pressure inside, greater than outside. Tt the lower part of the building inside will be in a state of partial vacu/
. with respect to the outside, while the upper part will be in a state
pressure. At some point between the levels of the two openings th^E
pressure state is neutral, and no flow will take place through an openin'
at that level. This level is called the neutral zone?
1
Relation between Head and Flow
The relation between head or pressure difference on the two sides of at opening, and the velocity that will be created thereby, is given approxainl mately by equation (3).
K=4,(Mlj7
(3)|
where V = velocity in feet per minute through an opening, and p is the
pressure difference, in inches of water, existing at that opening from any
causes or combination of causes.
,
With V known, the flow, Q, at the opening can then be easily computed by the familiar relation.
Q = A VC
(4) i
where Q is the flow in cubic feet per minute; A is the area in square feet, and C is a coefficient.
For openings such as result from swinging or sliding windows and doors,* where the aperture is essentially an orifice, the value of C will beabout0.60.
It would be comparatively easy to calculate flow through an opening, if the pressure difference could be determined. However, so many factors participate in the general action that it is very difficult to evaluate a
pressure difference arising from a .given wind velocity and temperature.The difficulty is further augmented by the fact that the pressure difference is likely to have a different value for every different opening.or group of openings of a building.
NATURAL VENTILATION SYSTEMS The success of natural systems of ventilation depends on one or more of the following factors:
1. The availability of the natural force employed, whether it be the wind or tempera ture difference, or both.
*See The Neutral Zone in also p. 78. Chapter .
Ventilation, by J.
E.
Emswiler, A.S.H.V.E.
Transactions, Vol. 32, 1226;
422
Chapter 27--Ventilation Systems
ri, size and location of openings and of ducts, flues, dampers, louvres and other
ince.s- nf the regulation of the operative devices, which must function almost
of hand control.
C^avity .Sysgteymstsems obtain the necessary pressure difference by using vs which are called vent flues, and which become more and more
wSriveas the difference between the outside and inside temperatures *^ases As long as a temperature difference of not less than 40 deg. jgjSen indoors and outdoors exists, these systems can be depended upon ^"definite result. With slight temperature differences, the effective-
issof gravity systems decreases rapidly. Gravity ventilating systems usually must operate, except when the
rtioms are on the windward side of the building, at somewhat lower atmos^heric pressure than that out-of-doors. This is due to the necessity for pressure-difference to cause air to enter the rooms on the leeward side.
por (.fog first hour or so of school on a cold morning, a well-designed gravity ventilating system will function well. After that period and in comparatively mild weather, gravity ventilating systems cease to function since heat must be shut off from the radiator and the temperature dif ference which causes air movement must, without heat, decrease rapidly.
Gravity ventilating systems are not well adapted to the installation of hiimidifiers and air cleaners, and their control and upkeep with such
sysStteumdsieiss odfiffbicuuilldt.ings which operate with gravity ventilating systems indicate that the windward rooms usually may, with care, be provided with satisfactory air movement and temperature control, but that during this time the leeward rooms get too warm and usually cannot be made to receive any air supply except that which comes through the windward
rooms and the corridors.
Direct-Indirect Gravity Ventilating Systems ..Direct-indirect gravity ventilating systems have small openings through the outside walls below windows, with encasement of the super imposed radiator sections and are sometimes used in school building gravity ventilation. This system is very difficult to control, and becomes less and less effective as the temperature difference between indoors and outdoors decreases. The windward rooms may receive more air supply than can be warmed, while simultaneously, the leeward rooms are losing heated air due to reverse air currents through the direct-indirect heaters, due to the low pressure zone which always occurs in the lee of any obstruc
tion during a high wind.
Indirect Systems oj Gravity Ventilation : Indirect systems of gravity ventilation with convectors in the base-
m.ent may operate satisfactorily so long as their air supply comes from .windward and the temperature conditions inside and out permit the con-
' 1 4 -i-Via Viat is shut off from these
423
S