Document qkdrY2m4owbGnYM8MjyGqDrQG
Section I?
fitatun
Tabic of Contents
CO,,U.',
2.1 Introduction -- Askarel transformers and capacitors
P.1.1 2.1.2 P.1.3
Transformers Capacitors References
P.P "Ackarel-class" transformers
P.P.l 2.2.2 2.2.3 ?.2.li 2.2. 5
2.2.6
Description of the "askarel-class" of transformers Sources and consequences of transformer tank rupture Full-unit arc testing Alternatives to askarels in ''askarel-class" transformers Test techniques and standards used by manufacturersto evaluate fluid-filled transformers References
P.3 "Askarel-class" capacitors
P.3.1 2.3.P P.3.3 2.3.**
2.3.5
P.3.6
Description of the "askarel-class" of capacitors Probability and consequences of rupture Full capacitor arc testing Effect of alternative fluids on design and testing of the full capacitor unit Test techniques and standards used by manufacturers and users to evaluate fluid-filled capacitors and cables References
P.b Dielectric and insulating fluids
2.U.1 2.U.2
2.b.3 P.b.li ?.b.5 2.b,6
Available fluids Test techniques and standards by which fluid materialproperties are evaluated TeBt techniques by which fluid flammability is evaluated Tc-Bt 'techniques by which toxicity is evaluated Test techniques by which degradability is evaluated
References
2.5 The Bcope and influence of government regulations
?.51 P.5.P 2.5.3 2.5.^
Environmental regulations Poisonous ingredients in foods Occupational health Transportation
2.6 The scope and influence of insurance and fire-code requirements
Vnrr I1 I I . :
s . I : ];,
pt 25 PC py
30
3b
35 35 51
53 6? 6? 6?
66 66 66 69 72
76
MGNS 057496
2.1 Introduction - Askarel transformers and capacitors
2.1.1 Transformers Electrical transformers ere used to change voltage, current and impedance
levels In a wide variety of applications in electrical apparatus. These trans formers range from the very smallest types in solid-state electronic circuitry to very large (1000MVA) 60-Hz power transformers. This study is concerned with the following restricted but Important set of transformers:
1. "Network"-type distribution transformers, 500-2500 kVA, 12-3*4 kV, used In heavily concentrated urban and industrial load areas.
2. Precipitation transformers, high-voltage, for electrostatic precipi tators which remove particulate pollutants from furnace exhaust gases.
3. Transformers for multiple-unit type electric railroad cars; these are located under the flat-bed of the car.
These are all 1Iquld-Insulated and operate at the commercial power frequency. The liquid Insulant has two duties, electrical Insulation and cooling. Com
pared with air Insulation, the liquid allows much closer spacing (smaller size) for a given voltage, and compared with air or solid Insulation ("dry-type"), the circulating liquid coolant leads to a much smaller size for a given power rating. Mineral oil was traditionally used for this purpose and Is still used for most power transformer applications. Estimates are that as much as 93% of all llquldcoolcd power transformers use mineral oil, on an MVA or gallon-of-cooiant basis.
The particular set of applications described above have critical non flammability requirements, however, since they arc generally located In heavily populated areas or are used In high-temperature or high fire-risk conditions. "Askarel" transformer liquid was developed, using blends of the polychlorinated biphenyls (PCB's), In the early 1930*s to replace mineral oil In applications where non-flammabllIty was an Important requirement. The PCB's for these
HOMS 057A97
1
transformer askarels are manufactured by Monsanto Industrial Chemicals Company
C* and are Jii-efliSed by Monsanto under the trade name "Aroclor." Two grades are used
(showing percent chlorination and 197*1 domestic sales In thousands of pounds.)
Aroclor I2k2
(623;)
6207
Aroclor 125k
(5W
6185
Ten to twenty percent of this production goes into precipitator and railroad transformers; most of the remainder is used In the "network" transformers. Approximately 5000 askarel-f11 led transformers are manufactured per year in the U. S., at a value of about $k5 million.
While essentially all precipitator and railroad transformers are askarelfllled, only I0-I5 of network transformers are the askarel-type.
2.1.2 Capacitors As In the case of transformers, there Is also a wide range In types and
sizes of capacitors which are used In electrical apparatus. These are used for electric energy storage, tuning and power factor correction purposes. Their ratings can go from a few picofarads to many microfarads, with voltages from a few volts to over one-hundred kilovolts.
Although some high-frequency capacitors use air dielectric (air Insulation), most capacitors are made up of multiple, thin layers of metal and solid Insulation. To eliminate any weakening by the presence of air, these layer assemblies are then totally Immersed In a liquid dielectric; often paper Is used as one part of the solid Insulator, and this paper Is Impregnated by the liquid. In addition to being a good electrical Insulator, the liquid should have a high permlttlvity (dielectric constant,c). The PCB's possess both of these features, and so grades of capacitor askarels have been used In capacitors since the Introduction of the askarcls In the I930's. Whereas only a small percentage of transformers contain
HONS OS'J'*98
2
askarel, nearly one-hundred percent of capacitors use this type of liquid t
Insulont. Because of'the widespread use of PCB's in capacitors, Monsanto in 1971
Introduced a more environmentally compatible formulation, Aroclor 101$, especially for capacitors. In 197^ Monsanto sold 21,955 thousand pounds of this fluid; the capacitor market for PCB's is considerably greater than the transformer PCB demand. The market value for PCB-lnsulated capacitors is In excess of $100 ml11 ion per year.
Askarel capacitors are often divided into two categories, "power" and "Industrial." The power capacitors are high voltage units which generally contain several gallons of fluid. They are used for power factor correction, which increoscs the efficiency of the electric power system. Without this efficiency Improvement, approximately $1 billion In extra electric power plant and about I|0M KWH in extra electric energy per year would be required to serve existing demand.
"Industrial" capacitors are generally smaller units which serve a large number of purposes Including motor start and run, fluorescent light ballasts, arc welders, and power supply filters. The industrial class of capacitors is estimated to use one-half to two-thirds of the demand for capacitor askarel.
There Is an Important economic Interdependence between the capacitor and trans former fluids markets which should not be overlooked in deciding on alternatives to PCB's. The capacitor pnd transformer askarels have different percentage contents of various PCB's, but they are both formulated from the same basic stock. They, therefore, aid each other in achieving the cost advantages of large scale production. Any shift of either market away from askarel would Influence the price of the askarel to the other use. This factor should not be overlooked In evaluating the relative cost advantages of substitutes for PCB's.
MONS 057*99
3
2.1.3 References, Section 2.1
Much of the material In this section was obtained through personal con
versations with the manufacturers and users cited In the Introduction. In
addition to these personal communications, the following sources were found to
be helpful:
1. In Re: Proposed Toxic Pollutant Effluent Standards, (EPA); testimony on behalf of: a. General Electric Co., Mr. George B. Farnsworth, March U, 197^ b. Westlnghouse Electric Corp., Dr. James H. Wright, March 15, I97A
2. Statement of Electronics Industries Association, to EPA, concerning Proposed Toxic Pollutant Effluent Standards, In a letter to the Honorable Russell Train, Administrator, June 25, 1975.
3. R. H. Munch, "New Capacitor Impregnants," IEEE, New York, Jan. 30, 1975.
A. L. L. Jackson, "Industrial Organic Chemicals vs. Alternative Dielectric Fluids, IEEE Power Engineering Society, Winter Meeting, New York, Jan. 197*<, Paper No. C7^ 265~5-
5. "The Role of Polychlorinated Biphenyls in Electrical Equipment," General Electric Co., Schenectady, NY, Feb. A, 1972.
6. "Study of the potential impacts of the proposed Toxic Substances Control Act, as Illustrated by Senate Bill S. 776," for Manufacturing Chemists Association, Washington, DC, by Foster D. Snell, Inc., June 26, 1975.
7. National Conference on Polychlorinated Biphenyls, sponsored by Environmental Protection Agency, Chicago, IL, Nov. 19~21, 1975.
MGNS 057500
h
2.2 "Askarel-class" transformers
2.2.1 Description of the "askarel-class" of transformers The term "askarel" describes a broad class of fire-resistant,' Synthetic
chlorinated hydrocarbon Insulating liquids (polychlorinated biphenyls, "PCB's") which ere used in certain special transformers, reactors and accessory electrical equipment where fire resistance is an important requirement. The askarel desig nation Is used and defined more rigorously In the following standards and guidelines.
IEEE Std. 76-1971** IEEE Guide for Acceptance and Maintenance of Transformer Askarel in Equipment
ASTM 0-2283~73 Chlorinated Aromatic Hydrocarbons (Askarels) for Trans formers (also see D-2233"70)
National Electric Code, 1975; Art. 100 ("Definitions"), A50 (Transformers and Transformer Vaults), A60 (Capacitors).
Askarel Is a fluid which Is used both for insulation and for cooling. The transformer fluid must therefore exhibit proper electrical characteristics (particularly high breakdown strength^ and low electrical loss) and good thermal
qualities (adequate viscosity, specific heat, and thermal stability). The transformer windings are completely Immersed In the fluid, Inside a
tank which Is sealed to prevent the fluid from escaping.^ The tank must be
heavy walled to withstand the sudden pressure of a high current electrical fault
'"Fire resistant" materials are difficult to Ignite, and when Ignited burn at a slow rate. [2.2.1--see references at end of section]
* The high dielectric strength of the askarels In fact allowed a reduction
In the size of the transformer, compared with mineral oil. ^Thc amount of askarel fluid In such a transformer ranges from k0 to 500
gallons, depending on the size and rating of the transformer.
HONS 057501
5
within the tank. The lank Is generally finned for convective heat transfer to the surrounding air, and It often has a pressure relief valve to bleed off any small but steady rise of gas pressure within the tank (as from occasional lowlevel arcing or corona).
The fire-resistant character of this fluid, along with the high thermal stability and non-sludging qualities [2.2.2*], has made It an attractive trans
former Insulant since its Introduction In 1932. Its high cost relative to mineral oil has, however, restricted its use to a fairly well defined set of applications which we will call the Maskare1-class" of transformers. It Is for this set of uses, then, that alternative transformer fluids are being offered, and test methods and standards for these alternative fluids should therefore be responsive to these specific applications.
The most Important application of transformer askarel is In network transformers, which are essential components of the electric power distribution system In high load
density urban areas. These transformers deliver the electrical power directly to large commercial buildings and so must be located In close proximity to the building, within, on, under or directly adjacent to the building. This close proximity to expensive, heavily-populated structures has led to the need for fire resistant electrical equipment, and askarel transformers are therefore specifically identified In the National Electric Code and in many local fire codes and ordinances. The same type of fire-resistant transformer, of course, finds wide use also In non-urban applications such as Industrial plants, partmont buildings and shopping centers where the fire-resistant characteristic Is equaIly desIrable.
These transformers are generally In the 500 to 2000 KVA range, with primary voltages typically 12.8KV and secondary levels of 208V (three-phase, wyc-conncctcd). They are subject to high load and fault currents and so gener.il ly arc fuse protected on their low voltage side. A fault developing within the
^References, shown In brackets, are listed at the end of each section. MONS 057502
6
*\
transformer tank Itself will be cleared by the cIrcuit-breakers at the
substation.
Two other special uses for askarel transformers deserve mention. These
are In electric ra11 road and mass transit traction equipment, and in elcctrostatic
precipltat ion power supplies. The railroad application requires non-flammable
equipment to prevent fire damage In case of accidents, but at the same time the
electrical supply must be high-powered and compact, necessitating a liquid-cooled
and Insulated transformer.
Precipitators are used to remove particulate pollution from the flue gases
In fossil-fueled electrical generating plants and other industrial furnace-type
operations. The precipitator power supply and Its power transformer must there fore be In close proximity to the furnace and the hot flue gas, and so again for
fire protection purposes, askarel transformers are used. These two special uses
are growing as mass transportation and air pollution control programs expand,
and they now constitute ten to twenty percent of the askarel transformer demand.
It Is evident from the above discussion that the "askarel-class" of trans
formers can equally well be called the "fire-resistant class" of transformers.
Both external fires and fires from electric arcs Internal to the transformer tank
must be resisted. The askarels (polychlorinated biphenyls, PCB's) provide this resistance by generating hydrogen chloride which quenches any proximate flame.
Their flash and fire polntspare also very hlgl), making them difficult to Ignite.
These askarel flulds.-end the hydrogen chloride which they generate^***
v
* \ i .)' ^
''W* 1
. y /.o
highly corrosiv'e,
r4als, *Ad~sg extensive special designing and Installation
__ ..............
r .aV..f
;|
^ n ..
,
must.be obsery</d. ^fvly--partlculari--eorroslon-resistent winding and tank coating
i
\a> t*
> .X.'r -.yy- /> \
. .-(
M < *
{ * < f **>.
material's "Dan-fee-'used, "scavenger1* materials must- t>e VP^esent In the fi-uid -to -take
,i sf ' -s ' \ - ' ` *
' * t > / J, a'- ' t
up AOy..JLffl&JJ--amounts <kf-hydrogen'Chloride which are generated-Jo-normal-parat-i-om.
and in eddlUon*The transformer room or vault must be adequately ventilated to
prevent buildup of HCI vapor.
HONS 057503
7
Because of the toxicity and environmental problems of the PCB's, -drains
.M. ,>! 4.
< '.v
frwraskarei transformer Installations must a I so~T>e ^adequate^-rf-W^ered so that
small or large scale spilling of fluid, during filling, testing, operation or
catastrophic rupture, will be contained and not reach the ground water or navigable water systems.
These special requirements of existing askarel-transformcr designs and Installations are being identified In order to have a clearer picture of the
processes which will be involved In replacing the PCS fluid with an alternative.
Either the new fluid will have to be compatible with all of the characteristics
of the existing askarel installation, or new installations will have to be de
signed to accomodate the new fluid. These constraints wili shape the requirement
of testing procedures to evaluate and qualify new fluids and transformers fiUec
with new fluids.
2.2.2 Sources and consequences of transformer tank rupture If mineral oil or a new liquid Insulant such as silicone are to be used as
replacements for askarel In transformers, one can be sure that containment of this fluid will be a prime objective, for safety, environmental and economic reasons. In anticipation of requirements for containment tests and standards, It will be the purpose of this section to review the present state of standards, tests and understanding in the area of transformer fluid containment.
Although the fluid Is held in substantial drums or In the sealed transformer tank, loss of the fluid can still occasionally occur under several different circumstances t
a. During transport of the fluid or of the filled transformer, b. During processing and handling of the fluid by the manufacturer or user, c. During In-service operation of the transformer, and d. Upon disposal at the end of the unit's life.
HONS 057504
8
Instructions for proper transport of the fluid and of the transformer are included within the general procedures of the Department of Transportation (Reference 2.2.3; see also Section 2.5]. In addition, the follcv/lng are cited as examples of the types of guidelines and standards which could be developed to prevent leakage during acceptance, maintenance, handling and disposal of transformer and fluids:
a. "Guidelines for handling and disposal of capacitor and transformer grade askarels containing polychlorinated biphenyls," ANSI C107.I - I971*; American National Standards Institute, 1*130 Broadway, New York, NY 10018.
b, "IEEE guide for acceptance and maintenance of transformer askare! in equipment," IEEE Std 76 " 197**, Institute of Electrical, and Electronic Engineers, 3**5 E. **7 St., New York, NY 10017.
These standards are discussed more fully In Section 2.2.5. The oil spill regulations developed and enforced by the Environmental
Protection Agency (2.2.**) also can serve as a model for judging the restrictions on other fluids leaking into the environment. These are discussed In Section 2.5.
A very rugged design Is used for transformer tanks In order to maintain containment under most external or internal stresses. These tank designs are specified by industry standards published by ANSI (2.2.5). Tank dimensions, static pressure withstand capability and corrosion resistance are specified. These standards should be reviewed for applicability with new fluids.
Rupture of a transformer tank while in service Is most often due to arcing within the tank. This Is a very complicated phenomenon which has been studied for many years. The following facts describe the phenomenon, its effects, and possible controls as presented In three recent articles by Barkan et_. a_l_. (2.2.6), Goodman and Zupon [2.2.71, Nettleton [2.2.8], and Rlstuccla and Benton [2.2.91.
a. The arc most often starts as a low-current, hlgh-Impedance arc between adjacent turns somewhere within the transformer windings,
HONS 057505
9
b. A "high proportion" [2.2.7) of transformer failures result from the
gradual build up of pressure In the tank due to the gas evolved by the
lov/ current arc. The pressure-rellef valve present on most network
transformers would avoid this as a cause of rupture in this important
application of "askarel-class" transformers. Some users claim, however,
that the pressure relief valve Is more trouble than asset, and so avoid
Its use. A fuse should also be used to clear these low-level faults
[2.2.6).
c. The high Impedance arc will grow with time to a high current fault as
the arc eats away the insulation on more turns. Because the use of
pressure relief valves generally prevents
the type of tank
rupture described In part b. above, the high current arc may be the
most prevalent cause of tank failure In the network transformers. We
presume that the final growth of current Is rapid, so that a bubble of
high pressure gas forms within the fluid. The Barkan paper then shows
that this bubble, as It expands, drives a "piston" of oil against the
tank wall, momentarily overloading the .wall and causing rupture.
d. Techniques for calculating the peak tank wall pressure under arcing
faults are presented tn both the Nettleton [2.2.8) and the 8arkan [2.2.6)
articles, but both also point out the difficulty of this for actual tank
geometries. The static pressure relief valve is of no use here because
of the rapid rate of pressure rise (2.2.9), and gas-flame venting
techniques are also generally Inapplicable for the same reason (2.2.8).
There Is apparently a proposed revision to the ANSI transformer standard
(C57.12.20-1971) for a standard transformer arc test to determine the
necessary tank arc pressure withstand capability (2.2.9).
MONS 057506
10
e. Further complicating the pressure calculation are the effects of energy release by burning of the fluid and of fluid products. This energy will build up the pressure, and the pressure wave will have characteristics due to being flame - as well as arc-driven (2.2.8],
f. One should not rely purely on tank withstand strength to prevent tank rupture under arcing, but rather this should be coordinated with a properly specified current-limiting fuse [2.2.6, 2.2.9). The peculiar 2 Impedance characteristics of the arc prevent use of familiar I t types of fuse specifications; rather, the fuse manufacturers should recommend the proper fuse, based on the user's known voltage and fault-current levels.
Protection against the high current arc Is of great Importance, not only because It may be the most prevalent source of "askarel-class" transformer failures but also because the arc is a high-temperature source which can Ignite the fluid or the decomposition products due to the arc. Thus, protective tests and standards must coordinate the available temperature and energy (as for Instance determined by a current limiting fuse) with the Ignition temperature and energy of the fluid and of flammable components created by the arc. The "full unit arc testing" discussed in the next section (Section 2.2.3) will explore this type of testing in depth.
It Is worth noting at this point that an arc In an Insulation fluid can cause a wide range of decomposition products, depending on the chemical nature of the fluid, the availability of reactant gases such as oxygen and nitrogen, and the Intensity (temperature) of the arc. Products can be flammable, explosive corrosive and toxic. As examples, arcs (or low level discharges such as corona) can decompose mineral oil Into hydrogen and hydrocarbon gases (and probably water), while askarcls are said to break down to hydrogen carbon monoxide, carbon dioxide, and oxygen [2.2.10].
HONS 05750?
U
Not only can these products be directly harmful, but they can also weaken
the dielectric strength of the insulating fluid and thereby set the stage for subsequent high current flashover and tank rupture. One should, therefore,
seek standard procedures by which the fluid can be cleaned up at regular intervals,
or after known arcing, in order to avoid future equipment failure. As guides in
preparing such standards, we should note the following procedures which are now
regularly employed.
a. ''Scavenger1' substances are mlxedwlth askarels to take up the corrosive
hydrogen chloride which Is produced by occasional low level electrical
discharges within the fluid.
'
b. In spite of the presence of scavenger material, users are instructed
' to bubble nitrogen through the fluid immediately after known arcing In
order to pick up hydrogen chloride before It can do corrosion damage.
c. The IEEE standard 76-197^ suggests that moisture content and dielectric
strength of askarel be regularly checked If arcing Is known to be
occurlng. Because of the combination of preventive measures outlined above,
manufacturers and users report that present transformers of the network type experience about a .01 to ,02% yearly rate of tank rupturing failures. Tests,
standards, and guidelines must be prepared for new fluids In order that low
failure rates will also be obtained for new transformer fluids.
Even though a low rupture rate Is experienced with transformers, It Is
still Industry practice, generally backed by fire or environmental code en
forcements, to place fluid-insulation transformers In vaults. Mineral oil
units must be In fire-proof vaults [2.2.11]; askarel transformer vaults need not
be fire-proof but must have adequate ventilation and drainage facilities so that
spilled fluid Is contained and toxic vapors do not accumulate [2.2.12).
MQNS 057508
12
2.2.) Full"Unit Arc Testing In the early days of askarel usage a short-circuit test and an arcing test
were performed by Underwriters' Laboratories, Inc. on actual transformers filled with an oskarcl (General Electric "Pyranol"). Details of these tests are reported In the UlMH No. 2581 Report, dated September 29, 193**. More recently, catastrophic explosion (arc) tests with several Insulating fluids were performed by RTE Cor poration [2.2.13]
1. Underwriters1 Laboratories Tests
The transformers were rated 60 cycles, 5KVA, 2200-110 volts. One of these
was short-circuited externally. The other was subjected to an arcing test by
being connected to a 12,000 KVA generator so as to apply 7,500 volts between the
ungrounded 122-volt lead and ground. In both cases, pressure-tight covers were
provided with pressure-relief diaphragms designed to rupture at not less than
10-12 psIg.
'
The results of the two tests were rather similar: no appreciable change in
pressure was noted for approximately 2 minutes after current was supplied to
the transformer. Thereafter, the pressure increased rather rapidly until the
diaphragms ruptured, large volumes of gases were liberated during the tests, but the gases did not Ignite upon application of a test flame.
2. RTE Arc Tests Four Insulating fluids were tested: mineral oil, Silicone DC-200 (Dow Corning), RTEMP (RTE Corporation), and an askarel (Westinghouse Inerteen 70-30). Approximately four gallons of each fluid were used, preheated to I50C. The containers were sealed before the test, but the rupture pressure (pre sumably roughly the same In all four cases) was not specified. In each test the liquids were subjected to a massive arc discharge: **660 to **820 amps at
HONS 037509
13
*tdOO volt open circuit. All four samples showed a violent flash Initially, with rupture of the container lid and wide spraying of liquids, but only mineral oil continued to burn. It Is Important to note that mineral oils used In transformers have flash points in the vicinity of 150C (1*6*C minimum according to stardard specifIcattons) and fire points about I5C higher. Askarels, on the other hand, have no true flash point (so-called pseudo flash points do occur), and no Mre point up to the boiling point. Silicone oils have very high flash points 'about 3009C)--see the section on flammability tests. RTEMP, being a high hydrocarbon fraction, presumably also has a high flash point. Thus the tests were conducted with Initial fluid temperature near the flash and fire points of mineral oil, but substantially below flash points of other fluids.
3, Reaction from Industry and Insurance
The consensus appears to be that both sets of tests (UL and RTE) shov.
askarels to have very low flammability. The UL rating of 2-3 on the scale of
100 for flammable fluids reflects this consensus, furthermore, the Factory
Mutual representatives appear satisfied that the RTE tests show also the silicone
fluids and RTEMP to have flammabilities In the same, generally acceptable, range
as askarels. Ul representatIves have not commented bn the RTE tests.
On the other hand, the nature of the Initial flash In RTE tests and of the
observed pseudo flashes In flash point testing of askarels does not appear to be
understood, so some concern remains. Intense heating of the decomposition products
by the arc may lead to some reaction of these products with air. Contributors
have also suggested that In arc explosion tests of askarels the fluid Is elect
rically heated to decomposition temperatures, and that decomposition Itself Is
exothermic. As a result, several representatives from Industry and Insurance
business have commented that a carefully standardized arcing test should be
developed. Manufacturers, users, and testing laboratory personnel have indicated
a willingness to cooperate In developing such a test. MOWS 057510
Jl*
2,2.k Alternatives to oskarcls in "askarel-class" transformers; influence on total transformer tests and standards
We must emphasize again that the purpose of this study is not to evaluate alternatives to askarels but rather to survey the status of tests and standards by which such alternatives may be judged. The characteristics of the available alternatives must be explored, hov/ever, to the extent that unique characteristics will influence the definitions of tests and standards. This section will emphasize the effect of alternatives on the total unit, while the next section will look at standards for the fluids themselves. Many concepts originally brought up In Section 2.2.2 ("Sources and consequences of transformer tank rupture") will be revisited in terms of the goals of this section.
The characteristics of available alternative fluids are presented in detail In Section 2,l and so need not be repeated here. It is Important to note, how ever, that these represent a wide range of density, viscosity, operating temper ature, corrosiveness, volatility, hydrolytic stability, flammability, etc. Because of the divers!veness of these values, we will see that universal performance specifications will be difficult to write without taking into account the unique characteristics of each particular Insulant. This will be equally true in establishing universal performance standards for the total transformer assembly. The Important fluid characteristics which must be accounted for in any future transformer standards and specifications are listed below:
e. Haterial compatibility. The chemical activities of the available Insulation fluids differ In kind and degree. Tests must, therefore, be devised to measure adequacy of the materials used for protective coating on Inside of the tank walls, for insulation on the wire used for the transformer windings, and for miscellaneous other components such as disconnects and fuses which might be In contact with the fluid.
HONS
15
b. Temperature. If the particular Insulating fluid requires an unusuafly high operating temperature, all materials used to construct the trans former must be compatible with this temperature, and In addition the location of the operating transformer must be selected to be acceptable to this higher operating temperature. Existing standards such as: "General Principles for Temperature Limits In the Rating of Electric Equipment," IEEE Std 1-1969 are probably adequate for this purpose. Standard sampling techniques may also be desired to Insure the stability of the fluids at high operating temperatures.
c. Cooling. The fluid In a transformer Is used as both an insulating and cooling medium. An economically competitive transformer must have Its cooling system design closely matched to the characteristics of the coolant fluid, and so new fluids will undoubtedly require some redesign of the transformer. This may necessitate new standards on transformer tanks, cooling surfaces, circulating equipment, etc., and the user may demand more thorough cooling specifications on transformers with new coolant fluids.
d. HydroIytIc stab!11ty. Water Is generally a problem In transformer fluic, but the degree of difficulty will probably change from one fluid to another. Sealing against moisture entry, and processes for removal of water should, therefore, be specified for each new insulant.
e. Containment. The different fluids will have different densities and required volumes for any given kVA and kV class of transformer, so space and supporting structure specifications must be made up for each new fluid. The types of seals will also have to be correlated with
HONS 057512
16
eacH fluid, since difference fluids have difference leakage character istics. Since rigorous containment of any fluid may be the goal of future regulations, standards and tests for evaluating containment of each tank/fluid combination wl11 be of Increasing Importance.
Standards for external protection should be coordinated with the particular class of transformers, the fluid and the level of tank containment security. By external protection, we mean secondary protection provisions, beyond the tank -Itself. This Includes both vaults, for extra containment in case of tank failure and protective circuit elements (such as circuit breakers and fuses) to prevent tank rupturing arcs from occurring. Much as an electrical system has its various power and protective elements coordinated with one another, so also might the Industry consider more quantitative coordination of the levels of transformer containment. One might, for Instance, consider that Increased speed and redun dancy of circuit breaker and fuse protections could allow a less cumbersome and expansive vault structure. Extensive probability analyses of actual operating experience would be required before such a coordination plan could be acceptable for fire codes end Insurance purposes.
Although no new standards or tests may be required, we Include, for com pleteness, a mention of two other available alternatives, namely dry-type and gas-cooled transformers. These transformers depend on ambient air or special gas Insulation. The dry types are available now and are being used extensively In place of askarel transformers. Relative reliability and overload capability have been questioned by some users but are quite acceptable to others, which may mean that standardised tests on these characteristics should be available to clear up such disagreements.
Gas cooled transformers are not yet as readily available for substitution. Tests may be required to establish the harmlessness or the need for containing
HONS 057513
IT
products of arcing within the Insulation gas. Development of these tests should be guided by the extensive existing work on entire gas-Insula ted substations.
2.2.5 Test techniques and standards used by manufacturers and users to evaluate fluid filled transformers
The transformer manufacturer and user have the following standards documents available for guidance in selecting and handling the Insulating fluid.
1. ASTM D 2203-74 "Standard Specification for Chlorinated Aromatic Hydrocarbons (Askarels) for Transformers." This document gives detailed specifications of the physical, chemical and electrical properties of six askarels which have, or are being used In transformers and Identifies specific test methods.
2. ASTM D 3146-75 "Standard Specification for Oxidation - Inhibited Mineral Insulating Oil for Use In Transformers and Circuit Breakers." This document gives detailed specifications of the physical, chemical and electrical properties of the oil together with approved test methods.
3. ASTM D 1040-73 "Standard Specification for Uninhibited Mineral Insulating Oil for Use In Transformers and In Oil Circuit Breakers." This document gives detailed specifications of the physical, chemical and electrical properties of the oil together with approved test methods.
k, ANSI C 59.131*1971 "Guide for Acceptance and Maintenance of Insulating Oil In Equipment" [Also issued as IEEE (institute of Electrical and Electronics Engineers) Std. 64-1969.) The purpose of this Guide Is to assist In evaluating the serviceability of oil received In equipment; oil as received from the refiner for filling new equipment at the Installation site, and as processed Into such equipment. It also Is Intended to assist the operator In maintaining his oil In serviceable condition. The Guide recommends standard oil
HONS 057514
16
tests and evaluation procedures, methods of reconditioning and reclaiming, the levels at which these become necessary, and the routines for re storing oxidation resistance where required by the addition of inhibitors. 5. IEEE Std. 76-197** "Guide for Acceptance and Maintenance of Transformer Askarel In Equipment." This guide assists In evaluating askarel as received in transformers, reactors, and accessory equipment operated at power frequencies and in efforts to maintain askarel in serviceable condition. It recommends standardized tests and evaluation procedures. Methods are outlines for reconditioning and reclaiming askarel whenever necessary. 6. ANSI (American National Standards Institute) C 107.1-197**. "Guidelines for Handling and Disposal of Capacitor- and Transformer-Grade Askarels Containing Polychlorinated Biphenyls." This document gives typical physical, chemical and electrical properties of askarels used in insulating fluids In transformer construction, details methods of shipping and handling, spells out necessary safety precautions, recommends labeling practices and details approved dis posal techniques. It also lists organfzations having facilities for analysis and for disposal and details an analytical procedure for the determination of airborne PCB's. 7. IEEE Draft "Specification for New, Unused Transformer-type Askarels." This specification covers bulk shipment in tank cars and drums of new, synthetic, nonflammable electrical insulating liquids of the chlorinated aromatic type known as askarels which are used as Insulating and cooling media in liquid-filled transformers. While this specification Is Intended to cover the composition and characteristics of askarels for purchase only and does not apply to liquids In apparatus, a number of discontinued types are Included for purposes of Identification and historical significance.
057515 HONS
19
8. IEEE Std. 283-1968 "Guide for Installation of Oil-lmmcrscd Distribution Transformers." This document suggests procedures to be followed In filling with oil those large transformers which are customarily shipped to the point of installation without the oil.
9. A NEMA Standards Document titled "Proposal for American National Standards on Mineral Insulating Oil for Use in Electrical Apparatus" Is in the final stages of preparation. It is intended "to provide a functional industry standard that will assure a continuing supply of a single mineral insulating oil that adequately meets the needs of equip ment manufacturers and oil refiners." It sets functional limits for the essential physical, electrical, and chemical properties and specifies the ASTM test methods to be used. Presumably It will ultimately replace Items 7 and 3 above.
10. Federal Specification VV-l-530a "Insulating Oil, Electrical (For Trans formers, Switches and Circuit Breakers." This standard specifies the physical properties required, establishes quality assurance provisions, and gives Instructions for testing. It identifies several ASTM docu ments as forming a part of the specification.
11. Federal Specification W-1-1219 "Insulating Fluid, Electrical (Non combustible)" This standard applies to "liquid of the chlorinated aromatic hydrocarbon type (askarels) with coverage similar to that of VV-i~530a.
The following standards relate to the specification and performance of the transformer Itself:
1. ANSI C57.12.00-1973 (also IEEE **62) "General Requirements for Distri bution, Power, and Regulating Transformers."
HONS 05?5*6
?0
This standard specifics (1) service conditions; (2) preferred ratings; (3) Insulation classes end dielectric tests; (*t) tolerances on losses, Impedance, ratio, regulation and temperature rise; (5) tests; (6) such construction details as bushing class, marking of terminals, nameplate data, etc.; and (7) short circuit characteristics. 2. ANSI C57.12.90 (also IEEE #262) "Test Code for Distribution, Power, and Regulating Transformers.*' This standard prescribes methods for performing the tests specified in C57.12,00-1973 (above) and In the separate transformer standards of the C57.12 series. The test methods covered are: (1) resistance measurements (2) dielectric insulation; (3) losses and impedance; (M ratio and regulatlon; (5) temperature rise; (6) insulation power factor; (7) polarity and phase relation; and (8) short circuit calculations. C57.98, an Appendix to C57.12.90, covers impulse tests. 3. C57.12.90a-197^ (also IEEE #262A) (Draft Standard) "Distribution and Power Transformer Short-Circuit Test Code." This code defines a procedure by which the mechanical capability of a transformer to withstand short-circuit stresses may be demonstrated.
Other standards and guides In the ANSI C57 series (there arc about 30) Include such documents as:
057.12.20-197^ "Requirements for Overhead-Type Distribution Transformers 67,000 Volts and Below"
C57.12.21?1969 "Requirements for Pad-mounted Compartmental-Type Single-Phase Distribution Transformers"
C57.12.40-1967 "Secondary Network Transformers, Subway and Vault Type (Liquid Immersed)"
057.100-197^ "Thermal Evaluation of 011-lmmcrsed Distribution Transformers"
HONS 057517
21
C57.93 (also NEMA TR-5-1956) "Guide for the Installation and Maintenance of OM-lmmcrsed Transformers"
C57.92 "Guide for Loading 011 - Immersed Distribution and Power Transformers" I*. NEMA TRl-197^ "Transformers, Regulators and Reactors"
This document identifies the ANSI transformer standards which have been approved as NEMA standards and includes more detailed specifications regarding such characteristics as audible sound levels, external clearances between live parts, accessories, and some test procedures. 5. NEMA TRll-1967 "Small Power Transformers with 65C Average Winding Rise and Distribution Characteristics." This covers electrical characteristics and mechanical features of this class of transformers.
The above are representative of about ten NEMA standards dealing with various classes of transformers. .
6. UL (Underwriters Laboratories) 506 "Specialty Transformers"
This standard covers requirements for air-cooled transformers and
reactors for general use but does not cover oil-filled units.
7. AAR (Association of American Railroads) SM262 "Specifications for
Impulse Transformer for Coded Systems Control"
8. AAR SKI65 "Specifications for Transformer, 011-lmmersed, Self-Cooled"
9. FM (Factory Mutual) 5-27 "Fire Prevention Transformers"
10. FM 5-275 "Arc-Furnace Transformers"
.
11, FM IA-B "Inspection and Maintenance of Transformers"
(Note: Items 7-11 above are not In hand and thus no further description is
available.)
Section 2.1*.2 should be consulted for designation of the standards and
techniques used for specifying and measuring the various fluid material prop
erties Identified In the above transformer standards.
MQNS 057518
22
2.2.C References, Section 2.2
' Much of the material In this section was obtained through persona) con
versations with the manufacturers and users cited In the introduction. In add 11
the following articles are referenced In the text:
2.2.1 `'Transformer askarel inspection and maintenance guide," Monsanto Company Bulletin No. IC/FF-38R, revised March, 1975.
2.2.2 R. N. Sillars, Electrical Insulating Materials, IEE Monograph 14,
1973; Section 10.2.1 .
2.2.3 49CFR 100-199, revised October I, 1974.
2.2.4 "Oil Pollution Prevention," Environmental Protection Agency, 38FR 34164, December 11, 1973*
2.2.5 C57.12.40; American National Standards Institute.
2.2,6. P. Barkan, et. a 1., "Overpressure phenomena in distribution transformers with low impedance faults: experiment and theory," F 75 464-8, IEEE PES Summer Meeting, San Francisco, July 1975.
2.2.7 E. A. Goodman, L. Zupon, discussion to Barkan paper (F 75 464-8).
2.2.8 M. A. Nettleton, "Explosions due to faults In electrical equipment," Electrical Review, 25 July 1975, pp. 116*119*
2.2.9
0. J. Rfstuccla, R. E. Benton, "Ten most-asked questions on violent transformer failure." Transmission and Distribution, January, 1975,
PP* 30-31.
2.2.10 A. E. Knowlton, editor-in-chief, Standard Handbook for Electrical Enqlneers, Ninth Edition, McGraw-Hill Book Co., New York^ 1957, 1,-561. V-570.
2.2.11 National Electric Code, 1975; Sec. k50-2<t, "Oil-insulated Trans formers Installed Indoors," NFPA, Boston, (also see Ref. 2.2.8, Sections 15-102, <1-572, l<t-300).
2.2.12 National Electric Code, 1975; Sec. <150-23, "Askarel-lnsulated transformers installed Indoors," NFPA, Boston.
2.2.13 0. A. Duckett, "Catastrophic explosion tests In Insulating fluids," RTE Corporation, Wankcsha, Wl 53186, November 9, 197k.
HONS 057519
?3
2.3 "Askarel-class" capacitors
2.3.1 Description of the "askarel-class" of capacitors In Section 2.1.2, descriptions were given of the important uses of askarel-
Impregnated capacitors, namely "large" ones for power factor correction on elec tric power systems and "small" Industrial ones for fluorescent tube ballasts and for motor starting. These are generally constructed by winding alternate sheets of metal foil and paper and/or film dielectric in round or flattened rolls. One or more of these rolls are connected together Inside a closed metal housing which Is then filled with the askarel.
The paper dielectric material has a high permittivity (c^-S), but it is dried before assembly Into the capacitor, and It contains a large volume per centage of open air space. The askarel Impregnates the paper, filling the air space voids. Askarel Is uniquely suited to this dielectric application because Its high permittivity (--6) reasonably matches the paper, and therefore causes less nonuniformity In electrical stress. The net high permittivity and the high dielectric strength of askarel also allow for a smaller capacitor per KVA or Kilojoule rating.
This combination of high dielectric constant (permittivity) and high di electric strength would be sufficient to make askarel a favorable Impregnant for capacitors. Its stebl11ty and nonflammability are additional characteristics which capacitor users have come to accept and depend upon through the many years that askarel has been essentially the exclusive capacitor impregnant. The com ment Is occasionally made that capacitors, particularly the large power factor correction types, are generally out-of-doors or In vaults and so flammability Is not an Issue as with transformer fluids. But this Is definitely a minority view point, and the majority of manufacturers and users indicate that they depend on
MQNS 057520
2U
the nonflammability of askarel capacitors. More will be said about this flammoblllty issue in Section 2.3*3.
In considering test techniques for alternate capacitor fluids, then, we can at tills time identify the following factors: dielectric constant (permit tivity, c), dielectric strength, Impregnability, flammability, and stability. Toxicity, environmental degradability and compatibility with other capacitor materials will also be added to the list in subsequent sections.
2.3.2 Probability and consequences of rupture The rate at which the small Industrial capacitors experience a tank-
rupturing failure Is very low; and when one of these small capacitors fails, there is little loss of fluid. The total amount of fluid In all small Indus trial capacitors Is, however, large, as shown In Section 2.1.
In the case of the larger, power-type of capacitor, again failure rate Is low; the tank-rupturing type of failure Is estimated to occur to .1$ or less of the capacitors In service per year. Generally, a capacitor will fall by an Internal arc short-clrcuiting the unit. Each power capacitor Is generally Individually protected by a current-limiting fuse, and this fuse will blow when the capacitor falls, leaving the capacitor-fuse unit open-clrculted.
Often, power capacitors are used In parallei-serles connected groups, or banks, and upon failure of one capacitor in the bank, all parallel capacitors will try to discharge through the failed unit. The current-limlt1ng fuse limits this "In rush" current so that the other capacitors In the bank are not damaged.
NEMA standards exist for Identifying the proper fuse to use to protect any given capacitor. These are somewhat out of date, however, so a manufacturer
*ln a capacitor containing paper Insulation, 80$ of the fluid Is absorbed and so will not spill out even If the can does rupture.
*CP 1-1971, "Shunt Capacitors," National Electrical Manufacturers Associatl New York. See also ANSI C55.1-1968 (IEEE No. 18), "Shunt Power Capacitors."
HONS 057521
2
wl 1l. general ly provide the necessary Information for his capacitors. There Is need, therefore, for a newly-created set of- Industry-wide standards for pro tection of now capacitor designs with new types of impregnant dielectric fluids.
2.3.3 Full capacitor arc testing We have established In Section 2.2 that flammability Is an Important
characteristic of "askarel-class" transformers and that the insulating fluid has
been In the past and should continue to be qualified by full transformer arc
testing. We have also recognized the Importance of nonflammability of capacitors,
but It must be reported that there Is little documented experience or interest
In arc or flame testing of capacitors. The apparent Justifications for this lack of testing are the low rate of
capacitor failure and the small amount of fluid in any one capacitor. Fuse
protection as described In Section 2.3.2 also reduces concern for rupture and fire.
In evaluating the need for full unit flammability testing of capacitors,
one should also keep In mind the following factors:
a. New capacitor dielectric fluids generally are more flammable than
askarels.
b. The paper and film, which make up a lar.ge percentage of the bulk
material within a capacitor, are generally flammable.
c. Power factor correction capacitors are generally used not singly but
rather In large multiple-unit banks. The flame from a single unit
might be unconsequentlal, but it could lead to a dangerous, full-bank
fire. d. Use of many capacitors In large, closely spaced banks also has another
risk. Unless each capacitor Is properly fused, all parallel branches of a bank can discharge through a single unit which develops an Internal,
short-cIrcult fault. The sudden release of this large stored energy
might lead to significant damage and fire.
26
HONS 057522
I
* Manufacturers of fluids and capacitors, have privately run occasional arc tests on capacitors to study flammabiIity effects after a bank-rupturing fault. No definitely recommended format for such testing has been brought to our attention, however, and the Indication ts that considerable design and testing would be required before a quantitatively interpretable and repeatable test could be devised. Several parties Involved in the manufacture and use of capacitors did feel rather strongly that such a test should be developed, however particularly in light of the increased flammability of the new fluids.
2.3.4 Effect of alternative fluids on design and testing of the full capacitor unit.
The dielectric fluid must be compatible with al) other materials with which the fluid makes contact Inside the capacitor casing. As In the transformer situation, the Inside coating of the metal capacitor tank must be non-reactive with the fluid. Since the fluid permeates directly to the metal foil electrodes, either the metal and fluid must be compatible or the metal must be treated with a protective coating.
In capacitors, the most serious material coordination problem Is between the fluid and the Insulating sheets which separate the fol) electrodes. If this Is a paper, then the fluid must be able to completely Impregnate the paper, leaving no voids in which corona discharges can be Initiated. Although certain fluid characteristics such as molecular weight and viscosity will help to screen out obviously Improper fluids, adequacy of Impregnation is best evaluated finally by testing the Impregnant fluid In a true, ftIm-electrode capacitor geometry. One should be on the watch not only for Immediate corona from Inadequate impregnation but also for weakening of the dielectric strength of the fluid, which can result from the fluid dissolving impurities out of the solid Insulation material.
MGNS 057523
27
Incompatibility of a new fluid with the existing film and paper may be solved by going to new paper and film rather than by rejecting the new fluid. Thus, tests must be devised so that combinations of fluid and solid films can be evaluated on a controllable and comparative basis, and criteria for inter preting these tests must be devised so that new fluids are not rejected merely because of inadequacies In the paper or film. The best practical combinations of fluid and solid must be compared.
In the previous paragraph, we sought the best combination of Impregnant and paper from a materials compatibility standpoint. It is Important, however, to also coordinate dielectric characteristics. Severely mismatched dielectric constants will cause very uneven electric stress which can lead to corona and flashover In the more highly stressed member. Thus, askarel was a good fluid to use with paper since both have relatively high dielectric constants. The plastic films which are now In use in capacitors, such as polypropylene, have lower dielectric constants and so lower e fluids can be used.
Using lower dielectric constant materials means that the capacitance per unit area of electrode is less for a given electrode separation, larger area (larger capacitor size) Is needed for a given capacitance, and larger voltage or size are needed for the same energy storage. Regardless of what material Is selected, Its dielectric constant should be accurately known under actual Operating conditions, and so Its c should be measured with the material in the true operating electric field. This may suggest that an extension be made in the ASTM standard test for dielectric constant (092*0.
The size of the capacitor Is Influenced not only by the fluid dielectric constant, for a given capacitance, but also by the dielectric strength, for a given voltage. Decreased capacitance and energy storage because of decreased dielectric constant can potentially be regained by higher dielectric strength
HONS
28
nmlcrlols v/hlch allow higher fields and voltages. The design of the capacitor is, therefore, Influenced by the dielectric strength (breakdown strength) of the fluid. The breakdown strength of the fluid Itself may be measured by standard test procedures, as described in Section 2.I*.2. Final capacitor designs, and test capacitor geometries can be evaluated by methods outlined In Section 2.3.5.
The maximum operating voltage of a capacitor is generally set by Its corona Inception and extinction levels, rather than by the flashover voltage. The low current, but continuous corona discharge causes damage to solid and liquid dielectric material and therefore leads to short life and failure of capacitors even though the operating voltage may be well below the breakdown level. Detection and measurement of corona and particularly of its Inception extinction points are therefore extremely Important In order to specify the maximum safe voltage for long life. These corona levels are not characteristic of just the insulating fluid, Itself, however, but rather of the fluid In the actual electrode config uration, Including the electrode material, the microscopic surface conditions, and purity of the electrode/fluid interface. An absolute measure of corona inception for a pure, isolated fluid Is therefore of little value, and one must instead determine the inception level for the whole electrode/lnsulator config uration, assembled according to routines which would be followed In manufacture. Corona measurement techniques are sped fed In ASTM D 1868-73*
In addition to corona, losses In capacitors result from resistive and di electric properties of the fluid. These can generally be evaluated for the pure. Isolated liquid as described In Section 2.A.2. The measurement should duplicate operating conditions (frequency, temperature, electric field) as closely as possible. Generally, higher dielectric constant materials exhibit higher loss, because of the large and rapid molecular polarization changes required by high permittivity materials in a-c fields.
MQNS 057525
20
A final important characteristic of the capacitor dielectric fluid Is its stabl11ty. It must show little change in dielectric, chemical or physical characteristics under actual electrical and thermal operating conditions over the many years expected life time of the capacitors. Frequent comments from fluids manufacturers, capacitor manufacturers and users brought out (1) the Importance of this characteristic, (2) the difficulty In defining and measuring stability, and (3) the importance of the measurement being in as realistic an environment as possible, l.e., In a test capacitor configuration.
In conclusion, this section has shown that the particular dielectric fluid chosen for a capacitor has a major effect on the total capacitor design. Con sequently, and of more major Importance to this study, we can further conclude that alt aspects of new capacitor dielectric fluids finally need to be evaluated In the true, operational capacitor environment.
2.3.5 Test techniques and standards used by manufacturers and users to evaluate
fluid-filled capacitors and cables.
.'
The capacitor manufacturers and users have the following standards documents
available for guidance In selecting and handling the Insulating fluid.
1. ANSI C 59:11 (also American Society for- Testing Materials (ASTM)) D2233-71*
"Standard Specification for Chlorinated Aromatic Hydrocarbons (Askarels)
for Capacitors." This document gives detailed specifications of the physical, chemical
and electrical properties of four askarels which have been used as
capacitor Impregnants and details test methods.
2. ANSI C 59.123-1970 (also ASTM 02297) "Standard Specification for
Continuity of Quality of Electrical Insulating Mineral Oil for Capa
citors and Cable Accessories,"
This document provides detailed specifications of the physical,
chemical and electrical properties of the oil.
1 30 HOMS 057526
3. ANSI* C 59.122-1970 (also ASTH 02296) "Standard Specification for Continuity of Quality of Electrical Insulating Polybutene Oil for Capac)tors." This document provides detailed specifications of the physical, chemical and electrical properties of the oil and details test methods.
A. ANSI C 107.1*197^ "Guidelines for Handling and Disposal of Capacitorand Transformer-Grade Askarels Containing Polychlorinated Biphenyls." This document gives the typical physical, chemical and electrical properties of askarels used as capacitor Impregnatns, details methods of shipping and handling, spells out necessary safety precautions, recommends labeling practices and details approved disposal techniques. It also lists organizations having facilities for analysis and for disposal and details an analytical procedure for the determination of airborne PCB's.
5, IEEE Draft "Specification for New, Unused Transformer-type Askarels" This specification covers bulk shipment In tank cars and drums of new, synthetic, nonflammable electrical Insulating liquids of the chlorinated aromatic type known as askarels which are used as insulating and cooling media In liquid-filled transformers. While this specification Is in tended to cover the composition and characteristics of askarels for purchase only and docs not apply to liquids In apparatujfs, a number of discontinued types are included for purposes of Identification and historical significance.
The following standards relate to the specification and performance of the capacitor Itself:
MGNS 057527
31
1. ANSI C 55.1-1308 (IEEE No. 18) "Shunt Power Capacitors" Definition of terms, ratings, tolerance, operation, production and design testing, fusing. Such characteristics as stability, corona Start, radio Influence voltage, overvoltage, capacitance, leakage, loss and dielectric withstand are identified, but the specific detailed test technique is not described, nor are appropriate ASTM procedures cited. This standard is for shunt power capacitors without reference to the dielectric fluid; with non-askarel fluids, certain specified values and limits might possibly have to change, and specific test procedures may not be the same as have been traditionally used for askarel capacitors.
2. ANSI C 55.2-1973 "Series Capacitors for Transmission and Distribution line Compensation" This standard Includes requirements for safety, rating, and gap settings; functional requirements for protective equipment, alarm devices, servlcirc, type, and routine tests and a guide for operation.
3. NEMA CPI-1971 "Shunt Capacitors" This standard Is similar In coverage to ANSI C 55.1.
A. EIA RS-392 "Fixed Paper Dielectric Capacitors for Alternating Current Appl(cations." This standard covers the requirements for oil-paper dielectric capa citors hermetically sealed in metal cases for general purpose application on AC voltages. It specifies (1) standard designations, (2) standard test conditions, (3) marking, (A) quality assurance test programs, (5) tests, and (6) applications suggestions. Although the term "oil" Is used, this standard Is meant to apply to askaret-f11 led capacitors.
HOMS 057528
33
5. EIARS-392-1 (ANSI C83.67a-197*0 "Fixed Paper Dielectric Capacitors with Non-PCB Impregnant for Alternating Current Application" This standard applies to capacitors with paper dielectric impregnated with non-PCB fluid. Note that there is no existing EIA standard covering non-PCB capacitor fluids with plastic film dielectric.
6. EIA RS-40! "Paper, Paper/Film, Film Dielectric Capacitors for Po.ver Semiconductor Applications." The coverage of this standard is similar to RS-392 above.
7. UL (Underwriters Laboratories) 10 "Power Factor Correction Capacitors" (600V).
Cables AEIC (Association of Edison Illuminating Companies) 1-68
"Solid-Type Impregnated-Paper-lnsulated Lead-Covered Cable Speciflcatlo This standard specifies rated voltages, preferred sizes, construction, and assembly details and tests. AEIC 2-67 "Specifications for Impregnated-Paper-Insulated Cable, HichPressure Pipe-Type" The coverage of this standard is similar to 1-68 above. IPCEA (Insulated Power Cable Engineers Association) 5-67-^01 (also NEMA WC2-1967) "Metallic and Associated Coverings for Impregnate Paper-Insulated Cables" This covers materials, constructions, and requirements for metallic and associated coverings for normal use with oi1 - Impregnated, paperinsulated power cables. This Is the only IPCEA standard not related to solid Insulation. Note: There are also several ANSI Standards In this area.
MONS 057529
33
2.3.6 References, Section 2.3 Much of the material in this section was obtained through personal con
versations with the manufacturers and users cited In the introduction. In
addition to these personal communications, the following publications and
reports were found to be helpful:
1. R. H. Munch, "New Capacitor Impregnants," IEEE, New York. Jan. 30, 1975.
2. B. H. Goldy, W. 0. Solbert, "A New Liquid Dielectric for CapacItors." Insulation/circuits, Jan., 1975.
3. John Lapp, "Concepts In Systems Testing of Dielectrics In Capacitors," IEEE PES Summer Meeting, July, 1974, T 79 <450-3.
A. J. H. Wright, "Comments of Westlnghouse Electric Corporation," hearings regarding "Preposed Toxic Pollutant Effluent Standards ...," Mar. 15, 1979.
5. L. L. Jackson, "Industrial Organic Chemicals as Alternative Dielectric Fluids," IEEE PES Winter Meeting, New York, Jan.,
1979, C79 265-5.
.
MONS 057530
P.Ji.J Avu i J able- Kl u > i) r,
Iti t,)i n uvnli'su wc uhall. treat a few of the major materials used at the
tir.e in the elec trio power industry as tran^formor and capacitor riuida. The p'/w-.r industry in general has viewed with reluctance any change from the use of vr.Karn1*!i.
trunsformerj and capacitors not out of prej-dice or indifference
th- onv! ront*o*
or people's safety, but because the uckarel:: possessed outstanding electrical
ch%ructeristics. Furthermore, the askarels have low flammability, ar.d, while no*
inexpensive, their cost has been at a level the industry could manage. It must to
emphasized that there is no other fluid now available which has quite so broad a rav.rc
of application and usefulness in the electric power industry. If it is decided tnc*.
the ar.karels are not to be used in transformers and capacitors, then it will be fairly
certain that two classes of compounds, one for capacitors, the other for traftsfcrmrrt:.
will be required. In addition to the high versatility of the askarels, there is the fact that the
materials are cheap, although they cost more than mineral oils. The prime supplier
of askarels is a major chemical company of high productive capacity which has ke;t
the price of the material at a reasonable level. The general applicability, as well
as the relatively low cost will be lost in any switch away from askarels since virt-a.l
all proposed substitutes^will be more expensive. At least one of the promising substitute transformer fluids discussed belcw is at present being offered at a rebanc,
presumably in order to establish a market. It is not known whether this lover rebate
price could be maintained for any great length of time.
The materials discussed briefly below constitute by no means all of the existing
promising fluids proposed as substitutes for the askarels. Any such list would be
immensely long and would prove to be an encumbrance to this report which is designed to provide n view of the adequacy of present test methods rather than a view of all
possibilities. The major fluids proposed as substitutes for the askarels in power transformer
and capacitor application are for transformers: (a) silicone oils, (b) mineral oil::.
HGNS 057531
35
'(c)'Illl'hJy saturated paraffin oils. For cupneltorc, the riuids are (d) lone chain
csteri; oT phthnlic ueid and (e) dlaryl r,ul Tones of a variety of type:;. There arc other minor fluid:; which will he included at the clone of the discussion. However at the present time, these materials ore either not so desirable electrically an the shove five fluids or they ure an order of magnitude (or twol) more expensive.
Before proceeding to the consideration of the non-ar.karel riuids a few remarks on the askarels themselves may not be amiss.
HONS 057532
3 fi
The Ankar*:! n (pojyehlorobi pheny I :i)
The ur.V.'ir': Iore proprietary mixture:; of chlorinated biphenyl r: and chlorinated
benzene:;, the enpi r i'.-al formula:; of which are
H^q ^ Cl^ (where may run Vr\m
1 to 10)and
11^ Cl (where ni ma;/ run from 1 to 6) respectively. These ror.nomd-
no y be re presented by the structural formulas of a single example of each.
ci ___________ ^
/V-_- -_-/v_^/
>>
2, ?' *i, 141 - tetrachlorobiphenyl
1, 3* 5 - trichlorobenzc-r.*
The proprietary mixtures mentioned above usually are designated as havinr an effective percentage of chlorine and this percentage usually appears somewhere in th
trade numerical designation. The singly chlorinated biphenyls are light oils and ih
completely chlorinated (n * 10) biphenyls usually assume the character of a resin or
wax. Although first synthesized nearly a century ago (1], it was not until the third
and fourth decades of this century that they were produced in considerable quar.titie
It was during these decades that the superior electrical properties of these r.ateric
became apparent. Within a few years, large scale manufacture of the polychlorcclphe:.
was undertaken (3). Besides the excellent electrical properties and the low flannat
of the pelychlorobiphenyls it was observed that with the somewhat higher dielectric
constant over, say, transformer oils, the capacitor size could be reduced [M-
The askftrel fluids have been suggested as being suitable in a wide variety of
applications outside the electric power industry, mostly as heat transfer fluids,
additives to petroleum oils, in textile coatings and in surface coatings and paints
Applications to scaling compounds, printing inks and papers, and casting waxes are a
well attested (5).
The variety and successfulness of application of the askarel mixtures has led l
widespread unc and unfortunately to their widespread occurrence in the environment.
MGNS 057533
37
Mtyjt, of the urea;; where Uie |H>]ychJorubi[>hcnylr. occur in the environment ura, ol' our ir?;;ociuted with eminently intonnc industrial activity. However, the high chemical stability of the u;;karcl:; insurer. their persistence wherever they are transport'. :. The result is that they are found at some polluting level in a great, many i/.uecr: around the world. The pol yehlorobi phenyl o hve heer: documented :r. ey'r.t.i-,; in v.rrd and South America in both marine and freshwater environments (6-10], A detailed
4 direusBion of these findings may be found in Kimbrough's comprehensive review pe-.er '
There would seem to be little point expatiating upon the toxicity of tne polychlorobiphenyls in this brief resume since this report concerns the adequacy of tests of prospective replacements for these very fluids. Suffice it to say, in sururi up, that the polychlorobiphenyls accumulate, persist, and are destructive to anir.al tissues. Evidence for their prospective condemnation unfortunately mounts *12-lf]. Kimbrough's review {11] provides details on toxic effects in animals er.d human beings of polychlorobiphenyls and should be consulted by the interested reader.
MONS 057534
38
Cl J ieonc Oil:> , Probably the foremost contenders among the silicone oils; id a substitute for t lr
aak'arcl u are mixture:; of the dimethyl eiluxo.no polymers. Those mixtures evri bo nn<n` up in n variety of viscosities. One of the most important properties of the dimethylsj 1 icono oils is their low temperature coefficient of viscosity [ lr ]. are also mechanically resistant to high shear rates [l8, 19]. These conpo ;n<l3 *-..-e generally inert and are resistive to oxidative and thermal degradation (2C, 21].
The dimethyl si 1 icone oils may be compounded to have viscosities running from 3 to well beyond 30,000 centistokes. The dielectric constants for ail such mixtures remain in the neighborhood of 2.7 over many orders of magnitude ir. frerjenc,and over a broad range of voltages [25]. The flammability of the various rixtures exhibiting this viscosity range may be gauged by the range of the open cup flash poi: : of about 37 C for a 1-centistoke fluid to about 320 C for a 200-centisto/.e fluid
The solid-liquid transitions for the methylsiloxane oils that interest us here, occur for the most part in the neighborhood of -80 to -1*0 C (22]. The dielectric strength of these fluids is in the neighborhood of 1*0 kV/0.1 in. [22]. The dissipati'n factor is about 0.0003 at 100 Hz. All in all, these fluids are nearly ideal as power transformer fluids. They do not sludge or oxidize easily and with proper deslgr. one obtains good heat transfer. They offer good resistance to acid and alkaline contaminants in a transformer. Offsetting these virtues somewhat is the fact that wh=: these fluids are subjected to arcs their dielectric strength may be reduced by the formation of solid SiO^ filamentary bridging. In addition there seems to be a possibility of silicon carbide, SIC, being formed at an arc in these oils. Silicon carbide is conductive, and refractory, and provides another impediment to the self healing of the dielectric liquid (21*]*
These drawbacks are much more detrimental to applications in capacitors than in transformers and explain why the oils are proposed mostly for transformer use.
39
HONS 057535
Einco the breakdown product:*. of Uv.* ulLiconoo rnnemMe the products From which they are r.ynthe:;ized, u few word:; should be* udOed here about the chemistry of r.lJieoir. oil::. Whot is i von below is not meant to represent current proprietary melho js of silicone oil production but to give elementary background material for discur::.! ons el nowhere I n the report.
Early expectations that silicon would form an organic chemistry analopour. *.o carbon organic chemistry were never fulfilled. Saturated silicon chains anal'../in:*- t . the paraffins can indeed be formed but the silicon-silicon bond is relatively weak. At the beginning of the century Alfred Stock prepared the first few members of the silicon hydride series by dropping [see 26] acid on magnesium silicide:
Mg2SI * H Cl - SiH^ + Si2 H6 + Si3HQ + . . . + MgClg .
He found that the hydrides were unstable and he was not able to prepare tr.y cor.;: and in pure state higher than Si^H^ [see 26]. The modern silicon compounds which arec: interest here do not rely on the Si-Si bond which is subject to oxidation but upont.. stable Si-O-Si bond. From this bond true polymers may be constructed as was evidence by the thorough investigation of compounds of this class by Kipping in the first half of the century [see for instance, 27]. We might pursue one possible path to synthesi of a dimethyl silicone. If ve treat sand (SiO^) at about 1000 C with chlorine gas and a reducing agent (carbon) an important product would be silicon tetrachloride, a corrosive liquid at room temperature (SiCl^). Use of a methyl Grignard reagent (CIl^MgCl) will allow attachment of methyl groups to the silicon atom:
' SiCl^ + 2 CH.^MgCl - (CH^ SiClg + 2 MgCl2 .
The dimethyl silicon dichloride is most useful because we simply allow it to react with wnter:
HONS 057536
hO
TM" pr-i-hr.-1. jcnl 1 <vl dimethyl dir,Hanoi anil will undergo n dchydriilivo curi.k'r.rat. i.u thus::
ch3
ch3
ch3
ch3
HO C - Oil 110 SI -OH * HO - SI - 0 - Si - Oil + llgO
ch3 cii3
ch3 ch3
giving us a primitive dimethyl silicon. A glance at the equation will suggest to the reader that longer chains and cyclic compounds can be built up from our simple silicc and such is the case. The last reaction may be reversed under altered circumstances, i.e., may yield silanols from silicones, a point of interest in avoidance of dumping toxic materials onto the land and into waterways of this country.
These compounds are non-flammable in the sense that they have no true ccr.bustir points. The hent supplied to the compound must be sufficient to cause depolyr.erizati if the combustion is to be sustained; only the short chain polymers really burr. (c5,
HONS 057537
MJnoruJ Oil:;
#
/-tost of the oilz u:;cO uc transformer fluids are complex mixtures of paraffinic
compounds or mineral origin. Mnny of these paraffinic compounds are both sat
1
and cyclic. Such compounds are designated hz "naphthenic" by the petroleum irviun-.ry.
The oils are nearly always the result of a process where the refining method Is
tailored to the final use of the product. The aromatic content of the oil r.-jst to
controlled iri order to prevent sludging or oxidation of the paraffin corponerts; tit
some aromatics are added as oxidation inhibitors. A typical additive which -3 ccrpoun . j
with the oil as an antioxidant is ditertiary butyl paracresol (DTBP) which frequently
is added at the 0.2/t level (2&J. Such antioxidants are largely confined to distribut i
transformer applications. The use of such compounds is largely avoided in power
transformers where the fluid is hermetically sealed into the transformer under a
blanket of nitrogen gas. The addition of aromatic compounds is also designed to inhibit
gassing in an oil under the operating conditions of a transformer. However such
additions may prove a two-edged sword since one and the same class of compounds c?.n
caure sludging and oxidation of the paraffin oil.
The low cost and self-healing properties of mineral oils coupled with their
PM i ^factory electrical properties have contributed to their widespread use. The~e oil.'
have a dielectric constant of about 2. The dissipation factor is about 0.CC1
at 60 lla. The dielectric strength of mineral oils is generally greater than 30 kV/0.?f cm, 12
md 10 Item isa typical value for the resistivity of a fresh oil. The toxicity of oils
composed entirely of saturated paraffins is very low. Highly saturated oils find
perennial use in cosmetic products. Some of the highly refined oils are pharmaccpoeu].
The proeence or addition of aromatic inhibitors increases the toxicity of the oils.
The degradation of a pure oil in a normal atmosphere probably follows the course
of oxidation of alkanes to, ultimately, carbon dioxide and water. Such a process
would require high-energy radiation (ultraviolet) for initiation of the reaction.
HONS 057538
h2
T)i'-* rat,chwii:;m of tjii:; proe::;r, k; n<t, yet elcorly ori'lorntood because or the paucity or knowledge oT slow reactions [ ',1 ]. All purufl'inr, are to some slight extent soluble in valor arid cun therefore in time react with compounds present in natural v/tlo-e;. Furthermore, volatile fraction.-. of an oil may cr.enpc into the atmosphere whore it they are excited by energetic radiation they may form free radicals win eh reo. Illy react with atmospheric components. Whatever the details of the case, it is believed that the degradation products whether produced by physical or biological meats are nr highly damaging, to the environment.
The flammability of the mineral oils is considered high since they are hydrocarbons with no quenching atoms (such as halides). If the oil is to be sui*.cbl<? for transformer use it must be both insulating and non-viscous at operating temperatur since it will be used as a convective heat transfer fluid. However in a rough ar.-j re = way of speaking,the less viscous an oil, the closer it is to its flash point so that a compromise between hazard of fire and efficiency as a heat exchanger is required. Th* considerations have lead power companies to the use of oil in transformers and capacitors almost exclusively in exterior installations, and even there a firewall may be required (as near a wooded area, for example) or advisable.
Jf a transformer can be made to operate at a temperature remote from its flash point the hazard from fire would seen to be more remote than in the usual situation. There Is some advocacy (see for example Duckett RTE Corp., [30}) of using high-purity high-flash-point paraffin oils in inside installations, much as askarels are used at present. The test used to suggest the suitability of such oils is discussed in the next section.
HONS 057539
l.
Hydrogenated Paraffin Oils One? suggested fluid for transformer use is a product which the RTL
Corporation of Waukesha, Wisconsin is offering as a substitute for asknrcls in transformers in locations proximate to or Inside buildings. The firm maintains that the high flash point and consequent low flammability of this oil so much reduces hazard from fire in proximate installations that that fluid should qualify for service in such Installations.
This fluid is not produced by the RTE Corporation itself. The supplier is a large oil company [29] and the fluid was designed, or expected to be used, In high-temperature transformers. The product is marketed as RTemp. The composition does not appear to be anything unusual in the way of petroleum oils. It is a high-viscosity 800 cs (25C), high-flash-point (296*C) oil with a dielectric strength of about 37 kV/0.25 cm, (ASTM D877) , and high resistivity, 1013 ohm-cm. The oil is a petroleum product twice subjected to a hydrogenation process, thereby acquiring its saturated paraffinic properties. RTemp is therefore a highly stable mineral oil which is claimed to be of food grade [30]. It is presumed that the environmental characteristics of this highly saturated oil would be similar to the pharmacopoeal mineral oils [30]. That is, they form "safe" combustion and degradation products. RTemp oil is being tested by power companies In the Chicago area as noted elsewhere in this report [29]. The general physical and electrical properties of this oil resemble the ordinary transformer oils. The flammability properties of R Temp transformer oil are better than most transformer oils as would be indicated by its high flash point. The expected lower flammability Is confirmed in a general way by the surge-cell tests conducted at RTE Corporation by Duckett ct^ al [30). The surge of electric energy into the oil caused
MOWS 057540
Mi
vaporization of the oil and dispersal of the oil outside the test apparatus. No fire resulted, however, because the temperature of the liquid oil was well below the combustion point. This behavior was In marked contrast to an ordinary transformer oil subjected to the same test which ignited Immediate 1 and did not extinguish possibly because oil was Initially closer to Its flash point than the RTemp and considerable less energy was required to bring the transformer oil to combustion temperature.
Oils of the highly saturated type are used in cable and underground applications. The high viscosity of such oils makes them acceptable at the common operating temperatures of transformers In temperate or even moderately cold weather. But In the severest cold these oils require the protection of enclosure or burial to maintain their fluidity. Although the RTE surge testa show, and the combustion data predict that these highly saturated oils are probably safer than ordinary transformer oils, the National Electrical Code Committee will need Independent testing before explicit acceptance of this fluid.
HONS 057541
1*5
Mixtures Containing DiaryJ Sulfone These compounds are proposed by one of the major chemical companies
of the country as substitutes for the askarels. The basic chemical structure is:
where the R le an alkyl group with probably 1-8 carbon atoms, n runs from 1 to 3 and Ar is a phenyl, naphthyl or indan group. All these compounds are halogen free [3SJ. The actual product-is presumably a proprietary mixture of such compounds and other Ingredients such as non-chlorinated biphenyls. Cited as example in German and U.S. Patent disclosures [35] Is a mixture of tolyl xylyl sulfone, isopropylbiphenyl and minor Ingredients. It is presumed that in use further ingredients will be added to these compounds as antioxidants.
The mixtures as proposed have a dielectric constant of about 6. No dielectric strength figures are available at present, but life-tests of capacitors are continually being run by the manufacturer of the fluid [36]. The fluid 1s tested in ballast-capacitor use at 1000 volts at 90C working temperature. The flash point of the mixtures now advocated by the manufacturer Is about 150C, combustion is sustained at about 165eC and the fluid will auto-ignlte in the region of 450C. No pour-point figure is available but the capacitors function well at -50C [36]. Some toxicity studies have been conducted by the manufacturer. These studies indicate that irritation can be Induced by Intense or prolonged contact of the mixture with eye or skin of rodents. The manufacturer recommends that normal
MQNS 057542
1*6
industrial hygienic precautions be taken (attainable, in the main, with soap and water) In order to assure safe handling.
These materials when fed to rodents seem to break down into cxcretable metabolites according to studies conducted by, or on order of, the manufacturer. Polychlorobiphenyls fed under similar conditions persist in the animal body after the sulfone mixtures in the tissue have become undetectable.
HCNS 057543
Ii7
The Phthalate Esters The phthe.lates can be offered immediately as a product for use in the
high voltage capacitor Industry because they are already supplied by the petroleum industry as plasticizers for polyvinyl chloride plastics in tonnage quantities. In 1972, about 1 billion pounds of some 20 different phthalatc esters were manufactured [32].
The superior electrical characteristics of the esters of phthalic acid make them natural candidates as substitutes for the askarels in powercapacitor use should the substitution become necessary.
The phthalic anhydride typically is manufactured from naphthalene which is oxidized in the presence of vanadium oxide to phthalic anhydride
or alternatively from o-xylene by a similar oxidation process to the same
The phthalate esters supplied as high voltage insulating liquids are mostly dllsononyl phthalate (DINP) and dioctyl phthalate (DOP) [33]. One major manufacturer prefers DINP over DOP because of the expected resistance to hydrolysis bestowed by sterlc hindrance.
The chemical and petroleum companies use various methods for producing the alcohols from which DOP and D10P are formed, all of which start from petroleum refinery products. They may be typified by the one reaction for
MOMS 057544
IjO
turn by aldol condensation yields a CoQ aldehyde. hydrogenated to 2 ethyl-hexanol.
The CoD aldehyde Is
co2, h
aldol
Jo------------------ C*. aldehyde -c--o--n- jd--e--n--s--a--t:--ion+ C.8 aldehy1de
2 ethylhexanol.
The 2-cthylhcxnnol then estorifies the phthalic acid
O Q:i> -
^
1- ^
VR
producing the well-know plasticiser 2 ethylhexanol. The octanols and lsononanol used In the manufacture of Insulating fluids will use the same or similar reactions in their preparation.
The aromatic dibasic phthalate esters typified by dllsononyl and dloctyl 12
phthalate have specific resistances In the neighborhood of 10 ohm-cm. In applications as capacitor fluids they offer a dielectric constant of about 5 which la considerably higher than that offered by the askarele, and should therefore allow for more compact design of capacitors than the askarels. The voltage breakdown point occurs at around 30 kv/.25 cm. The boiling point at reduced pressure (5 mm Hg) is about 250C and yet the pour point Is in the neighborhood of -50C. The flash point as determined by the Cleveland Open Cup Hethod for those fluids is in the neighborhood of 220C and the same determinations show that combustion Is sustained at 250*C or thereabout [34).
HONS 057545
1*9
The dibasic phthalatc esters are available on the market, apparently in any quantity desired and are marketed by at least two major chemical companies. At least one high voltage equipment manufacturer has modified the design of his power capacitors to accomodate the phthalates as capacitor fluids (33]. Alkyalatcd Chlorodiphenyl Oxides
(This section is still in preparation - - will be forwarded to reviewers at a later date.)
MOMS 057546
50
2*\y2 Tost techniques and standards by v/hlch fluid material
properties are evaluated
Insulating fluids for transformers and capacitors are commonly tested and evaluated in accord with one of the following:
1. ANSI C 59.2 (also ASTM D117) "Standard Methods of Testing Electrira) Insulating Oils"
2. ANSI C 59-6? (also ASTM D9D1) "Standard Methods of Testing Askarels" 3. ANSI C 59.118 (also ASTM D2225) "Standard Methods of Testing Silicone Fluid for Electrical Insulation" The teat procedures called out in these documents are tabulated below.
Acidity, Approximate Acidity, Approximate, and
Polar Contamination Coefficient of Thermal Expan
sion Color Chlorides, Inorganic
Chlorine Compounds, Hydro]ytable
Dielectric Constant Dielectric Strength Using
Meta] Disk Electrodes Dielectric Strength Using
VPE Electrodes 2,6 Pitertiary-Butyl Para-
Cresol Content Examination, Visual
Flash Point Fire Point Cas Content Gas Content (Nonncidic) Inorganic Chlorides and
SulfntOB Interracial Tension Neutralization Value
(Neutralization Number) Oxidation Stability Peroxide Number Pour Point
ASKARELS (D901) D97*< D1903
, D2129 D1821
D1820, D2Ml D92>i D877
D92
D971), D66L
D97
ELECT. INS. OILS
(D117)
D153lt D1902
D1903
D1500 D878
D877
DI816
D1673
D152>) D92
D83I D1827 D878
D971 d66*j , D97>t
DPiihO* D1563
D97
. '
MCNS 057547
SILICONE FLUIDS (D22C5)
D2129 D921*
D92
D97h D97
51
ELECT. IMS.
SILICCri;
ASKAREI.:;
on.s
FUJI IV
Power Factor Refractive Index (and Specific
Opticul dispersion) Kecistivity
Sa-.pl i nr. Saponification Nunbcr Scavenger Content Sediment and Soluble Sludge Sludge Specific Gravity Specific Resistance Sulfur > Corrosive Thermal Stability Viscosity Visual Examination Volume of Oil Water Content
D92t D1807
D1169 D923
D1703
D1810
D1936 D88, Dlt5
D1702 D1808 D1533
D9?U D1807
D1169 D923 D9^
DI698 D1313, D131*<
D1298
D1275
. D88, DUI15, D2161
D92t l:8ot
Dl?95 Dll 6? DU It 5, D2H_
D1315, D1533
D2112 also deals with oxidation stability and is called out in D31^*6, "Standard
Specification for Oxidation-inhibited Mineral Oil for Use in Transformers ani
Circuit Breakers"
The following ASTM Standards have recently appeared:
D3.300 "Standard Method of Test for Dielectric Breakdown Voltage of Insulating Oils of Petrolium Origin Under Impulse Conditions"
D3303 "Standard Method for Rapid Gas Chromatographic Estimation of Higher Boiling Homologues of Chlorinated Biphenyls for Capacitor Askarels"
D330k "Standard Method for Analysis of Environmental Materials for Polychlorinated Biphenyls" (This document is a modified version of Appendix B of ANSI C107.1 -197).
HONS 057548
5? I
2.4.3 Test techniques by which fluid flammability Is evaluated. Most would agree that the concepts of combustion and flammability of a mater
ial ore qualitatively clear and easily understood. The quantitative definitions of flammability of the material, that is, whether it will ignite and then continue to burn under specified temperature, pressure and ambient atmosphere conditions Is not, however, as easily achieved. What is required is a flammability test in which all relevant parameters are rigorously controlled and In which the results are unequivocally Interpretable, and this has been difficult to develop to every one's satisfaction. The various tests which are recognized and in common use are described below, along with comments on their applicability and shortcomings:
a. flash and fire points The only test specified by the standard-setting agencies (ASTM, ANSI, NFPA, IEEE) for Insulating fluids, mineral oils and askarels, fs the Cleveland Open Cup test for flash and fire points (ASTM D-92). The specifications are: Mineral oil: flash point of 146C (In some areas 130C); Askarel: no fire point up to boiling point. Beside the D-92 test, ASTM recognizes several other variants for deter mining the flash point, which, however, are not prescribed for insulat ing fluids: the Tag Open Cup tester (D-1310), the Tag Closed Tester (0-56)1 and the Pensky-Martens Closed Tester (D-93). In all experimental arrangements the flash point is determined by slowly Increasing the temperature of the cup containing the liquid sample. An ignition source, placed above the surface of the liquid, is actuated at specified Inter vals. The flash point, by definition, is the lowest temperature of the cup at which the vapors above the liquid surface flash. The flashes are transient, because only the vapor phase burns, not the liquid. In
MONS 057549
53
addition to the determination of the flash point, the D-92 test specifics the procedure of increasing the temperature beyond the flash point up to the temperature at which transient application of the ignition source causes continued burning of the liquid. The lowest temperature at which this happens is the fire point. Determinations of flash and fire points give valuable indications of flammability hazards, and should continue to be used. However, It must be recognized that developments In recent years have prog ressed significantly beyond the stage at which the standards for Insulating fluids were set, and also beyond the state-of-the-art prescribed by officially adopted ASTM standards. The following items should be considered before flash and fire point standards are recommended for replacement fluids:
(1) There has been a general trend toward closed-cup methods (e.g. 0-93). In particular. Underwriters' laboratories have favored closed-cup tests for some time now. These generally give lower flash points than the open-cup variants. For example, the flash points of the Dow Corning 50CS (silicone) fluid are 30^C and 277C as determined by 0-92 and D-93 tests respectively.
(2) The ASTM Flash Point Committee Is moving toward recommending International adoption of an Mequllibrium'' method. Equilib rium methods specify Flash-No Flash determination at a series of constant (rather than continually Increasing) temperatures. Since In equilibrium methods the entire system, sample and
. container, Is at the same temperature, complications assoc iated with heat transfer between the sample and the container are eliminated. Therefore sample size Is arbitrary and much
MOMS 057550
'^
' smaller samples can be used. In addition, these methods do not depend on viscosity because convective currents within the sample arc also eliminated,
(3) Scientific analyses of fire-point determination are poorly developed. Therefore, the significance of the test Is not clearly understood. This point will be further discussed in connection with the Oxygen Index test.
b. The Oxygen Index Test In the Oxygen Index (01) test the test sample is placed inside a tube containing a mixture of oxygen and nitrogen gases. The gas mixture, normally at room temperature, flows gently upward. The sample is Ignited and the percentage of oxygen In the gas mixture Is decreased. 01, by definition, Is the percentage of oxygen in the oxygen/nitrogen mixture at which extinction occurs.
The specified ASTM 01 technique applies to solid samples only (D-2863). Various laboratories have made their own modifications of the test to apply It also to liquids, and have reported the resulting data, but there Is no uniformity of procedure.
Sharply divided opinions exist as to the value of the 01 test toward a definition of flammability. For example, a limited polling of the Industrial opinions In this survey shows that some manufacturers use the test for practical purposes, while others consider It "worthless." The reasons for this division are not difficult to see. On one hand, It Is recognized that the burning of a small laboratory sample (grams) In room-temperature environments In no way simulates the behavior of large amounts of combustible materials In a welI-developed fire. On the
HONS 057551
55
other hand, there are reasons why the 01 test should not be discounted In the context of this survey. Fundamentally, the test is the proto type of extinction of a diffusion flame, and It bears roughly the same relationship to practical fire-point determfnations that the fundamental flamroabi11ty-1imit data do to practical flash-point determinations. As was discussed earlier, both flash and fire points are specified standard for definition of flammability of Insulating fluids. The problem is, however, that fundamentally meaningful fire-point, or 01, tests are more difficult to design than the meaningful flash-point tests.
To obtain consistent extinction data one would have to develop an OS test for liquids and a fire-point tester in such a way that an 01 value of 21 (l.e., air) Is obtained at the experimental fire point. Recent work at the NBS Center for Fire Research shows that such development would require very careful design of the test geometry. Therefore, an 01 test for Insulating fluids should be recommended only after some additional study, allowing specifications of the testing arrangement.
Spray Flammability Tests The ASTM Mist Spray Flammability of Hydraulic Fluids test (0-3119-72T) could be applied also to electric Insulating fluids, but we have no evidence that anyone has done that. The test Is a very severe one, entailing the spraying of a preheated atomized mist into an open flame. Underwriters' Laboratories consider It too severe and use one of their own variants In Its stead (UL File MH 011)66, p. Tl-6). The Ul test consists of applying drops of the liquid to the surface of a heated steel plate, end observing the "behavior."
MOHS 051552
56
Factory Mutual Research Corporation has its own spray flammability test, akin to D-3119. It Is also a very severe one. Most hydraulic fluids do not pass It.
Inasmuch as our survey of actual or potential accidents (admittedly a very limited one so far) has revealed no practical circumstances which would be simulated by any of these droplet-combustion tests, there is no reason why they should be recommended for replacement fluids. Further survey of accidents may give ground for a firmer recommendation.
d. Autolgnitlon Temperature (AIT) Several techniques exist for theheating of liquids In air until they Ignite. ASTM D-2155 Is a specified procedure for liquid petroleum products. Underwriters' Laboratories use a similar test of their own.
As one should expect, autoignltion temperatures of electric insulating fluids are quite high. Some reported values are: 332*C for a mineral oil and 393"C for Dow Corning 50CS fluid, both by the D-2155 test; 662-670C for askarels by the UL test.
As In the case of the spray flammability tests, operational conditions, normal or abnormal, are unlikely to give rise to these temperatures in the case of Insulating fluids. The AIT test, therefore, does not appear particularly pertinent. (At this point, It should be mentioned that Underwriters' Laboratories do not evaluate liquids only on the basis of tests which simulate some aspects of actual operations, but also on the basis of the total information about stability and flammability of the liquid. If this philosophy is adopted, then of course the AIT test and any other reproducible test which can be tied to some property of the liquid, becomes pertinent. In fact, UL did use the AIT test among others, to arrive at a numerical flammability rating of askarels).
HONS 057553
57
, e. Energy-Release Tests Hazards tests designed to evaluate the amount of explosive energy released In an accident apparently have not been used In connection with Insulating fluids, but there are good reasons why they should be. Such tests almost invariably give a measure of energy release by the effect on the surroundings: damage to a target, displacement of a target, or generation of a blast wave in air. Since the hazard of an erc-inltiated fire In a transformer or capacitor tank may be due to the blastwave damage as well as the subsequent fire, a measure of the explosive energy release capability of an Insulating fluid would appear to be useful. Such a test would be particularly important if It could be shown to be a useful screening mechanism before going to the more expensive, full-unit tests suggested in Sections 2.2.3 and 2.3.3. Direct measurement of the blastwave Intensity may be the most valid energy release test, as described more fully In Section 3.
The accompanying Table summarizes presently accepted flammability data on
several Insulating fluids.
-
HONS 057554
50
FI.AM.MAllITY DATA (I)
Info. Source
ASTX Stand. Jtu Mine
Dow Corning 1974 1EM
Liquid Description
Flush (*f;)
Mineral Oil
Min. Oil, paraffinic (deep waxed)
Transformer Oil (ASl'M D92) " D2155 " D2863 (Mod)
146 (130) 196
150
Fire Cc) -
221
165
ASTM Stand. UL (closed cup) Uu Mine
Dow Corning 1973 Doble
Askarel
No fire pt. up to b.p.
Aroclor 1016
174 -
AroeJor 1242
(Trichlorodiphenyl)
Aroclor 1254
(Totra-
)
177 193
Askarels "have no true flash point. "
334 None
Dow Corning 1974 IEEE UL
Dow Corning 1973 Doble
Bu Mine
Silicone/?
50 CS (Polydimclhyl)
Dow C 50CS closed cup XF-1-4701
Phenylmctbyl (Si) Dimethyl (hi vise.)
" (low vise.)
Methyl phenyl Polymethyl (low vise.)
304
277
304 319 138 271 124
360 445
138
AIT 01 37)
-- 332
15.1 670
393
HONS 057555
59
KIAMNAI; 11.1TY DATA (II)
1. Ub ClassiJied Prod. Index also gives info, on combustibility in air.
bow Corning 50CS: Moderate in air 257C
XI'- 1-6 701:
" " " 256C
Compare flash-open: 304C, closed: 277<,C
Aroclor 1016: Moderate in air 164C
2. Uow Corning, 1976 1C1CK Paper
Transf. Oil
50CS
Burning rate (gm/sec) Mist Spray (D3119)
0.0267 Violent
0.0060 Spasmedir
MOWS 057556
6o
fluid flammability measurement, by whatever test procedure Is adopted, should be carried out under conditions as closely approaching operation as reasonably possible, tn particular, pressure and temperature conditons are known and should be duplicated. Thus, power transformers of the "askarel class" have a temperature increase of about 65*C undar full load, so that bulk fluid temperatures will probably not exceed IOOC even on hot days. Local temperatures near the transformer winding may be ten to twenty degrees higher. Most utilities operate their transformers with a pressure relief valve as pre scribed by the National Electrical Code (Section **50-23); the relief pressure
yip Is usually only a few psi.
Power capacitor tanks rupture at low {a few psI) pressures but small Industrial type capacitors generally are sealed to **0-50 psi. The fluid temperatures within capacitors would not be much above the ambient, which itself might vary widely depending on location.
For a new fluid, with different loss and heat transfer characteristics, these typical values may have to be revised.
HONS 05755?
6i
?,h.h Tosh techniques by which toxicity in oval uutod (This section istill in preparation--will be forwarded to reviewers at b labor date).
Test toon:; i quo:; by which dof'riidab i 1 i by is evaluated (This section is still in preparation--will be forwarded to reviewers tt a later date).
HONS 051*58
62
2.4.6 References for Section 2.4
2.4.1 Schmidt, !(., and Schultze, G. (Mebig's) Annalen, 1881, 207, 238.
2.4.2 running, C. IJ., Ind. Eng. Chem. 1930, 22, 1180.
2.4.3 Clark, F. M. , Ind. Eng. Chem. 1937, 29, 698.
2.4.4 Clark, F. M,, Trans. Electrochem. Soc. 1934, 63, 59.
2.4.5 Broadhurst, M. G., Environ. Health. Perspect. 1972, 2, 81.
2.4.6 Holden, A. V., Nature, 1970, 228, 1220.
2.4.7 Koeman, J. H., Ten Noever De Brauw, M. C., and Devos, R. H., Nature,
1969, 221., 1126.
2.4.8 Jensen, S., Johnels, A. G., Olsson, M., and Otterlind, G., Nature,
2.4.9
1969, 226, 247. Zitko, V,, Bull. Environ. Contain. Toxicol. 1970, _6, 464.
2.4.10 Veith, G. D,, Environ. Health Perspect. 1972, lt 50.
2.4.11 Kimbrough, R., CRC Reviews of Toxicology 1974, Jan., 448, Chemical
Rubber Company, Cleveland.
2.4.12 Stallings, D. L., and Mayer, F. 1.., Environ. Health Perspect. 1972,
1, 159. 2.4. 13 Hansen, D. J. ,, Parrish, P. R., Lowe, J. J., Wilson, A. J., Jr. , and
Wilson, P. D. ,, Bull. Environ. Contain. Toxicol. 1971, j6, 113. 2.4. 14 Vos, J. G., and Koeman, J. H., Toxicol. Appl. Pharmacol. 1970, 17. 656. 2.4. 15 Peakall , D. B.., Bull. Environ. Contam. Toxicol. 1971, 6, 100. 2.4. 16 Troon, J. F, , Cleveland, F. P. , Cappel, S. W., and Atchley, R. W. ,
Am, Ind. Hyg. Qu. 1956, ,17, 204.
2.4.17 Dauppi, T. A., and Currie, C. C., Product Engineering, 1949, 22* 108.
2.4.18 Currie, C. C. and Smith, B. F., Ind. Eng. Chem. 1950, ^2, 2457.
HGNS 057559
63
2. 4. 19 Fitzsimmons, V. C., Pickett, D. L. # Mllltz, R, 0., and Zlsmun, V.'. A., Trans. A.S.M.E. (1946), .68, 365.
2.4.20 Scott, D. W., J. Am. Chem. Soc. 1946, 68, 356. 2.4.21 Patnode, W., and Wllcock, D. F., Ibid., 358. 2.4.22 Fordhnm, S., The Silicones. The Philosophical Library, New York, 1961
(See also Industrial literature such as Bulletin 22-053 Dow Corning Company, Midland, Michigan, 1972, and
2.4.23 ASTM Standard Method D92-4, Annual Book of Standard Methods Part 40 American Society of Testing Materials, Philadelphia, Pa., 1975.
2.4.24 1975 Insulating/Circuits Desk Manual, J21, No. 7, 1975, Lake Publishing Company, Llbertyville, Illinois.
2*4.25 See for example "Dielectric Properties of Dow Corning Silicone Liquids", issued by Dow Corning Corporation, Midland, Michigan.
2.4.26 Stock, A., and Somieskl, C., Ber. 1916, 49, 111. 2.4.27 Kipping, F. S., Proc. Roy. Soc. 1937, 159A, 131. 2.4.28 McGregor, R. R., Silicones and Their Uses, McGraw-Hill Book Co.,
New York, 1954. 2.4.29 Link, E., RTE Corporation -- personal communication. 2.4.30 Duckett, D. A., Paper before the General Meeting of the Edison Electrl
Institute, Transmission and Distribution Committee, Minneapolis, Minnesota, May 8, 1975. 2.4.31 Morrison, R. T., and Boyd, R. N., Organic Chemistry, Allyn & Bacon, New York, 1966.
MOMS 057560
ft,
<)ruh:uti,, I'.T:Kriv I ron . IlcuJth J'errspoct ., 197 J,
3*
<?.*. 33 Forster*, K. 0., pcrr.oriH.1 common i eat,ion. ?,lj. ?,h !:jlkow: .ki, A. J., anl Forster, K. 0., presented fit American Power Society (li:il.)
Winter Power Meeting, New York, 1975, also Troc. VII Int. Conf*. on Fieri. r i r-al
InsuU*.in/; Materials, Jnrt. Elec. Kng. Tokyo, Japan, 197^
HONS 057561
^5
2.5 The Scope and Influence of Government Regulations
The purpose of this section Is to identify the several government agencies which have potential regulatory power over new insulating fluids, to describe the particular area of concern over which each exercises regulatory power, end to define what criteria and procedures arc used to determine whether a new fluid falls within the purview of each particular agency or regulation. The emphasis will, therefore, be on the regulations themselves; criteria and testing procedures which support or are cited in
these regulations will be briefly Identified in Section 2.It.2, these test
techniques are more thoroughly explored.
2.5,1 Environmental Regulations
Environmental protection regulations are developed and enforced by the Environmental Protection Agency (EPA) and by the various state depart ments of natural resources. The state agencies generally follow the Federal regulations, and they may In fact have operational responsibility for enforcing the Federal environmental regulations. Being more closely in touch with the local Issues and being under less complex operating constraints, the states can often act more rapidly than the Federal enforcement agencies. It is Important, therefore, that the state and Federal environment regulatory bodies act under rigorous, quantitatively definable criteria In establishing and enforcing their regulations. We will review the existing and pending Federal regulations, recognizing that these will also probably be reflected in any state acts.
Insulating and dielectric fluids are typically very stable compounds which have low vapor pressures and which, therefore, do not represent a
HONS 057562
66
significant air pollution problem. The primary environmental effect is
In water, and so the primary source of environmental regulation of such
fluids is; Public Law 92-500 (86 Stat. 8l6) "Federal Water Pollution Control Act Amendments of 1972"
Three sections in this act are of particular importance for evaluating the Impact of regulations:
1. Sec. 307a "Toxic effluents" A proposed list and a final list of toxic substances were published by EPA In the Federal Register on 7/6/73 (38FR180W* and on 9/7/73 (38FR243^2) *
respectively. Criteria for selecting these substances were Included, thereby Indicating the standards by which new substances can be evaluated. The toxic substance list Is not enfor ceable, however, until standards for allowable levels of these toxic substances are finally promulgated. Although standards were proposed on 9/7/73, these have not yet reached final legal status.
2. Sec. 311 "Oil and Hazardous Substance Liability" (Spills, leakage, pouring hazardous substances Into navigable waters of the U.S.) On 9/22/7h, proposed rules were issued: "De signation and determination of removability of hazardous sub stances from water" (39FR30A66). A list of hazardous sub stances and selection criteria were included. This never reached the final promulgation stage and Is In fact now being rewritten. The existing oil spills regulation (38FR3M610 may serve as a guide for the new proposal.
See Section 2.5.3, "Occupational health," for air quality criteria In the working place.
Federal Register (FR), vol. 38, page fllfloMi, July 6, 1973.
MGNS 057563
67
3. Sec. *<02 "Pollution discharge permits"
This section
empowers the regional offices of EPA to issue permits limiting
the allowable levels of pollutants in effluent discharges. Limitations on polychlormated biphenyls have already been
Included in several permits. "PollutantV is defined (in Sec.
302) as effluents which "would interfere with the attainment or
maintenance of that water quality In a specific portion of the
navigable waters which shall assure protection of public water
supplies, agricultural and industrial uses, and the protection
and propagations of a balanced population of shellfish, fish and
wildlife, and allow recreational activities In and on the
water,..
In addition to the existing legislation cited above. Congress Is in the process of working on a Toxic Substances Control Act, which would give EPA more direct control on production and use of Identified toxic substances.
2.5.2 Poisonous Ingredients In Foods
The Food and Drug Administration (FDA),'an agency of the Federal Department of Health, Education and Welfare, has the responsibility for administering the consumer protection standards established by the Federal Food, Drug, and Cosmetics Act of 1938 with amendments (FFDCA) (IL & Code, Title 21). The various state departments of public health cooperate In maintaining proper food standards, under authority of state public health legislation. Whereas FDA enforcement authority concerns only foods involved In Interstate commerce (Sec. 703 and 70^ of FFDCA), the state may, of course, take local action.
*o**s
68
''Poisonous substances" include all substances documented to be harmful to human health. Thus, they may be specifically Identified in FDA regulations (as in the case of PCB's; see 38FR18096, July 6, 1973) or known to be poisonous from other reliable sources such as "The Toxic Substances List1' published by the National Institute for Occupational Safety and Health (see Sections 2.5.3 below). Likewise, tolerance levels are not specifically Identified by FDA for each known poison, but rather this is judged on a cese-by-case basis, as specified in Sec. 406 of FFDCA.
Any new insulating or dielectric fluid which ts identified by any Federal agency to be poisonous would thus come within FDA jurisdiction. In relation to this, it should be noted that the FDA regulations on PCB's (38FR18096) specifically exempts PCB transformers and capacitors; being In sealed containers was an influential factor In this decision.
In enforcing its regulations, FDA can request a manufacturer to recall an adulterated product, under threat of prosecution. It can, under court authority, seize a shipment of adulterated food. And It can legally prosecute manufacturers of Illegally adulterated foods. Actions are reported In:
"FDA Weekly report of seizures, prosecutions, injunctions, field corrections and recalls," published weekly by the FDA Press Office, Rockville, HD 20652.
2.5.3 Occupational Health
The Occupational Safety and Health Administration (OSHA), a part of the Department of Labor, has the responsibility "to assure so far as possible every working man and woman in the Nation safe and healthful working conditions, as stIpulatcd in:
HONS 057565
69
* Public law 91*596 (8A Stat. 1590) "Occupational Safety and Health Act of 1970"
Dielectric and Insulating fluids could come within the scope of OSHA regulations In two ways:
1. During processing of the material by the capacitor and trans former manufacturers
2. By use of the capacitors and transformers in or closely adjacent to work areas.
In the Act cited above, the following responsibilities are defined: 1. The Secretary of Labor (i.e., OSHA) is to promulgate standards
for toxic substances (Sec. 6). 2. The Secretary of Labor (OSHA) also Is empowered to inspect
working places (Sec. 8) and to enforce the standards (Sec. 10, 17). 3. The Secretary of Health, Education and Welfare, through its agency,
The National Institute of Occupational Safety and Health (NI OSH) Is to carry out research, develop criteria, end carry on training concerning health and safety In the working place (Sec. 20, 21, 22). Thus, NIOSH has the job of establishing standards, while OSHA prom ulgates and enforces these standards. The following publications and standards have resulted regarding toxic substances: 'The Toxic Substance Llst--197^ Edition" NIOSH, Rockville, MD 20852 June 197^. In this publication, a large number of toxic substances are listed, along with toxic dose levels, and the reference sources for these toxic doses. Four PCB's arc Included. A new Issue of this Is now in preparation.
HONS 057566
70
"Occupational Safety and Health Standards," 33FR23502, June 27, 197^. Sec. 1916.33 (CFR.Title 29 - Labor) Tabic Gl lists contaminants, Including chlorodiphenyI (62?; Cl); skin 8-hour time weighted average exposure not to exceed 1.0 mg/m\ and chlordiphenyl (56?,), 8-hour time weighted average skin exposure not to exceed 0.5 mg/m^.
The source of these standards Is 61 CFR 50-206.50 which cites: "Threshold Limit Values of Airborne Contaminants for 1908," Amer. Conf. of Govn. Industr. Hygienists.
The National Electrical Code (NEC) - 1971 (ANSI Cl-1971) has been Incorporated within 0SHA regulations (29CFR 1910.308; see 39FR23502, June 27, 1976). Dielectric fluids for transformers and capacitors therefore fall within 0SHA regulations Insofar as these fluids are effected by the NEC. (See Section 2.6 of this report for further discussion of the NEC.)
MONS 057967
71
2.5.1* Transportation The Department of Transportation (DOT) Is Involved In both the use and the
control of insulating fluids In these two ways: 1. Use. High speed mass transit systems employ electric traction. The
electric transformer Is, therefore, a rather key Item. It must be small because of the size limitations on the transit cars and fireproof In the event of an accident. Askarel transformers are, therefore,
a
universally used in present ground electric transit systems. DOT may, therefore, be a significant participant In the move toward
both safe and reliable techniques for continued use of PCB's and for
substitutional use of new Insulating fluids.
There Is little documentation which has yet come to our attention on
work by DOT on Improved transformers.
2. Control. The transportation of hazardous materials falls within DOT'S regulatory power, as Identified In: A9CFR Parts 100-199 Transportation; revised as of October 1, 1975. The following sections are particularly pertinent to the Insulating
fluids question: l. List of Hazardous Materials; sec. 172.5 a. None of the PCB's, by any of their chemical or trades names, Is on the list. b. Any substance which qualifies for the list under definitions given In other sections must be treated - as If on the 11st.
The Japanese retained askarel In their electric rail cars even after their otherwise complete ban on PCB's; they apparently are now experimenting with a si 1 leone substitute.
o*i*fa8
Ti
2. Dielectric and insulating fluids would be Identified as Class U poisons Tf they were Found to be toxic. (See Sec. 173.363) "
J. Class B polson ("less dangerous") sec. 173.3^3 liquid or solid substance "known to be so toxic to man as to afford a hazard to health during transport, or which, in the absence of data on human toxicity...fa 11 within any one of the following categories:
1) Oral Toxicity: produce death within 68 hours in half or more of a group of 10 or more white lab* oratory rots weighing 200 to 300 grams at a single dose of 50 milligrams or less per kilogram of body weight when administered orally.
2) Toxicity on inhalation: those which produce death within 68 hours in half or more than half of a group of 10 or more white laboratory rats weighing 200 to 300 grams, when Inhaled continuously for a period of one hour or less at a concentration of 2 milligrams or less per liter of vapor, mist, or dust, provided such concentration Is likely to be encountered by man when the chemical product is used In any reason able foreseeable manner.
3) Toxicity by skin absorption: those which produce death within 68 hours In half or more than half of a group of 10 or more rabbits tested at a dosage of 200 milligrams or less per kilogram body weight, when administered by continuous contact with the bare skin for 2k hours or less.
The foregoing categories shall not apply If the physical characteristics of the probable hazards to humans as shown`by experience indicate that the substances will not cause serious sickness or death. Neither the display of danger or warning labels pertaining to use nor the toxicity tests set forth above shall prejudice or prohibit the exemption of any substances from the provisions of Parts 170-189 of this chapter. (29 FR 18753, Dec. 29, 1968, as amended by Arndt. 173-3, 33 FR 16922, Oct. 6, 1968; 33 FR 19823, Dec. 27, 1968.)
HONS 057569
7'-
4. Effect of list Proper procedures for the transport of hazard ous materials are stated in the following sections:
Pt. 173 Shippers 173.3^ Packing for class 0 poisons, liquid
a) Closing and cushioning. All containers must be tightly and securely closed. Inside containers must be cushioned as prescribed, or in any case when necessary to prevent breakage or leakage.
b) Outage. Outage for containers of liquid poison for transportation by carriers by rail freight, rail express, highway, or water must be as follows:
1) Containers must not be entirely filled. Sufficient Interior space must be left vacant to prevent leakage or distortion of containers due to the expansion of the contents from Increase of temp erature during transit.
2) The proper vacant space (outage) In a tank car or other shipping container depends on the co efficient of expansion of the liquid and the maximum Increase of temperature to which It will be subjected In transit. Outage must be cal culated to the total capacity of the container.
3) Liquid poison must not be loaded Into domes of tank cars.
4) (n tank cars, outage must be calculated to percentage of the total capacity of the tank, t.e.t shell and dome capacity combined. If the dome of the tank car. does not provide sufficient outage, then vacant space must be left for the shell to make up the required outage.
5) The outage for tank cars must not be less than I percent.
6) No cargo tank or compartment thereof used for the transportation of any liquid poison shall be coro
. pfetely filled; sufficient space shall be left vacant In every case to prevent leakage from or distortion of any such cargo tank by expansion of the contents due to rise In temperature in transit, and such free space (outage) shall be sufficient in every case so that such cargo tank shall not become entirely filled with the liquid at 130'F.
057570 HONS
7I4
173-3^*5 Exemptions for poisonous liquids, Class B,
a) Poisonous liquids, class B, as defined in 173 3*3 except those for which no exemptions are provided as indicated by the "No exemption" statement in 172.5 of this chapter, or as provided for in 173.359(c), In tightly closed inside container^, securely cushioned when necessary to prevent breakage and packed as follows, are exempt from specification packaging, marking, and labeling requirements, except that marking name of contents on outside container is required for shipments via carrier by water. Shipments for transportation oy highway carriers are exempt also from Part 177 of this chapter, except 177.817, and Part 397 of this title.
1) In glass or earthenware containers not over 1 quar: capacity each, or in metal containers or poly ethylene bottles not over 1 gallon capacity each, packed in strong outside wooden boxes or barrels.
2) In glass or earthenware containers not over l pint capacity each, or In metal or polyethylene containers not over 1 quart capacity each, packed in strong outside flberboard boxes.
173,klk Poisons material labels
Pt. 174 17^.532 17*.538
17*1.586
Rail Freight Loading other hazardous materials Rail freight; loading and storage chart of
hazardous material Handling hazardous materials, by carriers by
rail
frelcit.
Pt. 175 _ Carriers by Rail Express
Pt. 176
Rati Carriers In Daggage Service
176.702 Hazardous materials
Pt. 177
177.821
177.861
177.868
177.860
Public highway carriers Hazardous materials forbidden or limited for transportation Loading; poisons Loading and storage chart of hazardous materials Accidents or leakage; poisons
Pt. 178
Shipping container specifications
Pt. 179
Specifications for Tank Cars
HONS 057571
75
2.6 The sco^e and Influence of Insurance and fire code requirements.
tn addition to the various federal and state governmental regulations which might restrict the use of fluids in electrical equipment, one must also make sure that such equipment does not conflict with Insurance and fire code regulations. The two arc closely related and therefore can be most easily discussed together.
The National Electrical Code (NEC) is one part (volume 6, 1975) of the National fire Codes, Issued by the National Fire Protection Association (NFPA). This code Is developed and continually updated by a set of committees which is sponsored by NFPA and is composed of representatives from manufacturers, users, fire Insurance companies, Independent testing laboratories, and municipal and state fire safety and regulatory agencies. As such, it is an author!tative work universally recognized as a standard statement of safe electrical fire practice.
Although the NEC Is not In Itself law, it is usually adopted with various levels of modification as the legal electrical building code. Equipment to be legally Installed within the jurisdiction of such a code must therefore conform to NEC.
As presently written, the NEC specifically recognizes mineral oil and askarel as Insulating fluids. Since no more general descriptions or definitions are given, one Is led to Infer that other fluids are excluded unless specifically identified In future editions. To get a new material listed in the NEC, the manufacturer must propose the desired Inclusion to the Electrical Coordinating Committee of NEC, along with evidence substantiating the fire safety of the material. Before approval, however, the committee would probably require testing and safety verification by an Independent laboratory such as Underwriters laboratory (Ul) or Factory Mutual Engineering and Research (FMER).
MONS 057572
76
UL Is an Independent not-for-profit testing laboratory which carries out tests on products for manufacturers and makes "listing" or ''classIfIcatIon" judgement based on these tests:
`Misting" The product Is deemed to meet the requirements of the NEC.
"classification" A material wi11 be given a flammability classIflcatlon, based on a scale between 0 (water) and 100 (diethyl ether); the procedure Is outlined in: "Tests for comparative flammability of liquids," UL Standard No. 3**0.
Whereas NEC Is an Installation guide, local ordinances will often look to the UL listing to verify that the product meets NEC standards and therefore can be Installed as directed by the code.
FMER Is a service arm of the Factory Mutual System of insurance companies. It carries out testing of equipment and Issues "approvals" or "acceptances" based on these tests:
"approval" The product Is deemed to be safe and suitable for general applications.
"acceptance" A particular Installation of equipment and materials meets fire safety standards.
Such a safety test could be Initiated upon request by a manufacturer or by one of the FM Insurance companies.
An Installation of electrical equipment must not only meet fire ordinances but also must be covered by fire Insurance. The Insurance rates are generally set by the State Insurance Commission, but an Insurance company must have veri fication of the safety of the Installation before agreeing to write Insurance coverage. The Insurance Inspector will therefore generally look to UL or FM
HONS 057573
77
acceptance, or to some other indication that the installation meets NEC requirements. The Inspector might also base his decisions on his company's rating of the requesting company and possibly on the users or manufacturer's own tests.
An experimental unit with a new insulating fluid might for instance be accepted for further field testing under thfs latter situation, if one unit within a larger installation docs not meet standards, temporary approval may be granted with the understanding that the substandard unit be upgraded to an accept able level within a specified period.1
It should be noted that utilities are often self Insured and are granted exclusion from the local codes based on NEC. It is the general practice of utilities to comply with NEC, however, and they often work closely with local fire protection people to make electrical Installations safe. When utility owned equipment Is installed In users buildings, often the local code or Insurance requirements would necessitate that NEC practice be followed.
A further note on the NEC Is that It has been adopted in toto by OSHA ("Occupational Safety and Health Standards," 29CFR 1910.308 - See 39FR23502, June 27 197*0 and It therefore has a very broad legal importance in industrial facilities. OSHA regulations are discussed more extensively In Section 2.5.3.
HONS 057571*
78