In some units, in order to increase the humidifying capacity, and to utilize a greater portion of the spray water, the atomized spray is per mitted to impinge against a heated surface thereby forcing its evapora tion. While this is practical in some instances, there is danger of scale formation where hard water is employed. It should be pointed out that in any atomizing system if extremely hard water is used, the air will carry with it a- content of infinitely fine solids which should be removed by a filter before discharging into the conditioned space. If it is not so re moved, this may result in the formation of an apparent dust upon furni ture and exposed surfaces.
One of the simplest methods of humidification in winter is by means of' a direct steam spray. This is seldom used in unit conditioners for comfort applications due to the resulting odors. In industrial applications; how ever, it finds frequent use. The steam is usually introduced to the air through a perforated tube or through some type of porous material.
. If a small atomizing spray is not used in comfort conditioning units, the evaporative pan type of humidifier is usually employed. This consists of a container offering as much water surface as possible and equipped with means of heating the water. This heat may be applied either electrically, by steam, hot water, or by circulation of the water from a heated space through the evaporating pan. Since the humidification is accomplished by surface evaporation only, it is essential that the air stream be directed across the surface and that the evaporating surface be large. While this system eliminates the dusting hazard when hard water is used, with a spray system, hard water tends to scale the heating surface and results in loss of capacity and the need for frequent cleaning.
The rate of evaporation per unit surface exposed is low. Thus it frequently becomes difficult to provide sufficient surface for adequate capacity. The higher the temperature of the water, the lower the relative humidity of the air; the greater the velocity over the surface, the greater is the rateof humidification. The evaporative pan type of humidification limits the water wastage and is usually supplied with water through a float valve. Due to the collection of salts in this evaporating pan such humidifying systems require occasional drainage and cleaning.'
Other methods of humidification attempted in air conditioning units are through the use of wetted fabrics, porous earthenware plates, or other, capillary surfaces. These methods rely upon the capillary absorption of the moisture up from the liquid level into the portion exposed to the air. They have a tendency to lose their effectiveness due to the resulting deposit of mineral salts at the evaporating surfaces thereby clogging the pores and reducing the contact of the air with the water. Also they frequently become foul and often support bacterial growth.
The capacities of any of the above methods of humidification are affected by the temperature and relative humidity of the air passing through the humidifier. The higher the temperature, the lower the relative humidity, the greater will be the rate of humidification.
Cooling and Dehumidification
Those units that employ recirculated water sprays will undoubtedly use such sprays as their means of cooling and dehumidification by
Chapter 12--Unit Heaters, Ventilators, Coolers, and Air Conditioners.
furnishing refrigeration to the water in circulation. Occasionally where an adequate.source of cold well water is available, this may be used as a direct spray and run to waste.
Other methods of dehumidification accomplished by direct contact with the transfer medium are by means of the so-called adsorption and absorption systems. (See Chapter 2 on Refrigeration.) It must be
recognized that these methods of dehumidification.do not in themselves provide cooling. The substance removes the water vapor from the air thereby heating it. This highly dehumidified air may then be cooled either by partial rehumidification or by direct contact with a cooling
medium of cold water or direct expansion refrigerant. There are now on the market solid adsorbents such as silica gel, and activated alumina, and liquid adsorbents such as calcium chloride in solution and lithium chloride which is one of the most promising examples.
Finally the most common direct means of cooling and dehumidification
is through the use of ice. In such units the ice is brought into as intimate contact as possible with the air handled. Provision is made for the
removal of the moisture as rapidly as it is formed from the melting of the ice. One method employed is to mount the ice on metal grids and then
draw the air over the cold grids as well as over the projecting pieces of ice formed between the grids. Of course, ice is also used to cool water which is circulated through the sprays;
In conditioning units, the use of surface cooling is probably more common than direct spray or other direct transfer means. The type of surface employed may, of course, be cast or fabricated from tubes. In present-day practice finned tubes or plate fins through which tubes are passed form the most generally used cooling surface. The detailed fabri cation of this surface and the arrangement of the tubes will depend largely upon the type of refrigerant for which it is intended.
The simplest construction is where chilled water or brine is used as the
refrigerating medium. With direct expansion refrigerant it is usually
necessary to provide a special arrangement of headers so that proper
distribution of refrigerant through all the surface is obtained. In some
cases, ordinary brine coils can be used when operated as a flooded refri
gerant system. In some units a combination of a direct spray and a
refrigerant surface is used, the spray being directed against the surface.
Such systems claim the advantage of air washing together with the
maintenance of a clean and effective cooling coil.
. '
It should be noted that when surface coolers are used, adequate pro tection in the form of filters or at least lint screens are necessary to prevent fouling of the surface from the air borne dirt. Surface not so protected
frequently becomes completely matted with lint, grease,; and similar dirt.
The sources of refrigeration used with these surface type conditionir^V units are discussed in Chapter 2 on Refrigeration. However, they may be divided into the following groups: -'
______cA^-anoiuu icingerant in wmcn .
w*&v*.*****- tyajwiaicu
within the coils of the unit. The vapor from these coils may be recompressed in
centrifugal; rotary, or reciprocating type compressors, and the refrigerant again returned to the evaporator coil.