CHAPTER 12
1956 Guide
Electric Motors and Machinery
Motors and the machinery which they drive, if both are located in the room, convert all of the electrical energy supplied into heat. This heat is retained in the room if the product manufactured is not removed until its temperature is the same as the room temperature.
. If power is transmitted to the machinery from the outside, then only the heat equivalent of the brake horsepower supplied is used. In some mills this is the chief source of heating, and it is frequently sufficient to overheat the building even in zero weather, thus requiring cooling by ventilation the year round. Table 7 shows the heat output equivalent
Table 7. Heat Equivalents of Various Sources*
Machinery (Motor in room) = Motor Hp/efficiency x 2544
Btu/hr.
Machinery (Motor outside room) = Motor Hp x 2544
Btu/hr.
Electric Lights
= Kilowatts x 3413
Btu/hr.
Gas (Producer = 150) (Manufactured = 535) (Natural = 1000) Btu/cu ft.
* Additional values are given in Chapter 13, Table 26.
of various sources of heat in a factory. For information concerning the heat supplied by persons, refer to data given in Chapter 6, and also Table 25, Chapter 13. For appliances see Table 26, Chapter 13.
INTERMITTENTLY HEATED BUILDINGS
In the case of intermittently heated buildings additional heat is required for raising the temperature of the air, the building materials and the ma terial contents of the building to the specified inside temperature. The rate at which this additional heat must be supplied depends upon the heat capacity of the structure and its material contents, and upon the time in which these are to be heated.15
This additional heat may be computed and allowed for as conditions re quire, but inasmuch as the heating system proportioned for taking care of the heat losses will usually have a capacity about 100 percent greater than that required for average winter weather, and inasmuch as most buildings may either be continuously heated or have more time allowed for heating up during the few minimum temperature days, no allowance usually is made, except in the size of boilers or furnaces. For churches, auditoriums and other intermittently heated buildings, additional capacity should be provided.
RESIDENCE HEAT LOSS PROBLEMS
The following Examples 6 and 7 will illustrate the procedure for calcu lating the heat loss of a residence, uninsulated and insulated, in accordance with the recommendations given in this chapter.
Example 6: Calculate the heat loss of the residence shown in Fig. 2 located in the vicinity of Chicago. From Table 1, design outdoor conditions are --10 F and 12 mpb wind velocity. Inside temperature from Table 2 is assumed to be 70 F.' The attic is unheated. Assume ground temperature to be 50 F (see Fig. 3, Chapter 35) under basement and garage floors and 32 F adjoining basement walls. Estimate infiltration losses by the air change method. No wall, ceiling or roof insulation is to be con sidered in this problem, but all first and second floor windows, except in the garage,
Heating Load
271
Bedroom A and Closet
Bedroom B and Closet
Bedroom C and Closet
Bedroom D and Closet
Bathroom 1
Bathroom 2
Part of Stbuctubb ob Infiltration Ajb Changes
VVaib Glass Ceiling ' Infiltration (H)g
Net Ark* ob Aib Volume
Walls Class Ceiling' Infiltration ($$)*
Wails Glass Ceiling Infiltration (H)8
156 sq ft
. 40 sq ft 170 sqjt
1020cfhb
Walls Glass Ceiling
Floor over garage Infiltration (H)*
Walls Glass 'Ceiling
Infiltration. (1 )*
Walls Glass
Ceiling
Floor over garage. Infiltration (1)*
Dining Room
Kitchen and Entrance to Garage
Livette and Vestibule
Walls ,,
Walls (adjoining gtfcage) Glass
Floor
`.
Infiltration WM)"
Wails Glass (doom) Glass (windows) Floor Infiltration
Walls Gh!^ (adjoining garage)
Door Floor Infiltration (1)4)*
Walls Glass ^at^'n`D garage)
Door Floor Infiltration {lV$)k
WalIs
Door Ceilingr
Infiltration^)'
Walls Glass Doors Infiltration (14) Floor
Gain adjoining rooms
Hoorn**
Walls Glass Floor Infiltration (1)*
D1E
COEFFI I Temp. CTENT Diff.*
0.28 0.45 0.69 0.018
0.28 0.45 0.69 0.018
SO 80 39.8* 80
80
80
39.8d 80
F1
Helat Loss (Btu per hour)
5330 1440 6910 2180
3490 1440
G Totals (Btu per hour)
15,860
1470 11.060 f