CHAPTER 31
1955 Guide
V, .= nominal velocity of discharge based on the core area, feet per minute.
Cd = coefficient of discharge (usually between 0.65'and 0.90).
fti. = ratio of free area to gross (core) area:
= distance from face of outlet, feet.
'' '
= proportionality constants, with K' = 1.13 K
-- effective or equivalent diameter of stream at discharge from open-end ,duct or at.a contracted section, feet,,,.
= A0 X Cd -X' Rt* -- effective area of stream at discharge from an openend duct or at a contracted section, square feet.
A. = measured gross (core) area of outlet, square feet,
Q discharge from outlet, cubic feet per minute.
Equation 1 is nondimensionai and requires only that consistent units be used, as in the above nomenclature. Values of K and K' are listed in Table
l.2-4
Table 1. Recommended Values of the Centerline Velocity Constant K or K' (See Equation 1)
' Ttpe' op Outlet
K
V, 500 to 1000
vt . : 2000 to 10,000
K
Vo = 500 to 1000. ,. 2000 to 10,000.
Free Openings
Round or Square
Rectangular, large as-
pect ratio (<40)
Annular slots axial or
radial"------....
,
Grilles and Grids
Free area 40% or more
Perforated Fanels *
Free area' 3' to 5%
Free area-10 to 20%:
5.0 4.3
' . . ...
4.1
2.7 3:5
6.2 5.7 5.3 4.9
3.9 .. . -
5.0 .
' 4.7
3.3 ' : 4.3
3.0 4.0 '
7.0 6.0
4.8
5.7
3.7 4.9
' For radial Biota U8e X/H instead of XZ(A)1!1. H is the height or width of the slot. Note: K and K' are indexes of Idea in axial.kinetic energy. Interpolate as required. Departures from maximum value indicate lossesIn first and 'second zones when compared with'the jet from a rounded-entrance, circular nozzle..
Low velocity test results, in the range Vx < 150 fpih, indicate that the normal values of K and if', should be reduced, about 20 percent for 7* = 50 fpm, as.used in later Equation 4b for throw. Fig. 2 gives the effective diameter -Do in inches for single openings and includes the coefficient of dis charge.6 Similar values for grilles are available in the literature or can be experimentally determined. Values of C<j and Ru are required for deter mining V0, Do and A0 for orifice-type and multiple-opening outlets, and should, therefore, be included in catalog data of these outlets.
In the case of multiple-opening outlets and annular-ring outlets (see diagram A of Fig. 1), the streams coalesce into a solid jet before actual jet expansion takes place. This coalescence affects the experimentally de termined proportionality constants K or K' and accounts for some of the divergence in reported values for similar outlets.
Centerline Velocities in Zones 1 and 2 , Experimental evidence indicates that in Zone 2
Vx _ ,./WHq
(3)
'`
` " Vo ~ %. X, /
.; ,
Air Distribution
697'
where
Ho -- width of jet at outlet or at vena contracta.
Approximately the same values of K! apply as for Zone 3 expansion from axial outlets.
In Zone 1, the ratio Vx/Vo is constant and equal to the ratio of the cen-
Fig. 2. Effective Diameters for Round and Rectangular Openings (Plenum Approach)
er velocity of the jet at start of expansion to the average velocity, ranging rom approximately 1.0 for rounded-entrance nozzles to about 1.2 for raight pipe discharge, but with much higher values for diverging-dis-: charge outlets.
Determining Centerline Velocities
perrPt correlation of data from all four zones, centerline velocity ras are plotted against distance from outlet in Fig. 3 in accordance with