Document qarg5LOkqa35LVMpLVqdV1XzR

696 CHAPTER 31 1955 Guide V, .= nominal velocity of discharge based on the core area, feet per minute. Cd = coefficient of discharge (usually between 0.65'and 0.90). fti. = ratio of free area to gross (core) area: = distance from face of outlet, feet. '' ' = proportionality constants, with K' = 1.13 K -- effective or equivalent diameter of stream at discharge from open-end ,duct or at.a contracted section, feet,,,. = A0 X Cd -X' Rt* -- effective area of stream at discharge from an openend duct or at a contracted section, square feet. A. = measured gross (core) area of outlet, square feet, Q discharge from outlet, cubic feet per minute. Equation 1 is nondimensionai and requires only that consistent units be used, as in the above nomenclature. Values of K and K' are listed in Table l.2-4 Table 1. Recommended Values of the Centerline Velocity Constant K or K' (See Equation 1) ' Ttpe' op Outlet K V, 500 to 1000 vt . : 2000 to 10,000 K Vo = 500 to 1000. ,. 2000 to 10,000. Free Openings Round or Square Rectangular, large as- pect ratio (<40) Annular slots axial or radial"------.... , Grilles and Grids Free area 40% or more Perforated Fanels * Free area' 3' to 5% Free area-10 to 20%: 5.0 4.3 ' . . ... 4.1 2.7 3:5 6.2 5.7 5.3 4.9 3.9 .. . - 5.0 . ' 4.7 3.3 ' : 4.3 3.0 4.0 ' 7.0 6.0 4.8 5.7 3.7 4.9 ' For radial Biota U8e X/H instead of XZ(A)1!1. H is the height or width of the slot. Note: K and K' are indexes of Idea in axial.kinetic energy. Interpolate as required. Departures from maximum value indicate lossesIn first and 'second zones when compared with'the jet from a rounded-entrance, circular nozzle.. Low velocity test results, in the range Vx < 150 fpih, indicate that the normal values of K and if', should be reduced, about 20 percent for 7* = 50 fpm, as.used in later Equation 4b for throw. Fig. 2 gives the effective diameter -Do in inches for single openings and includes the coefficient of dis charge.6 Similar values for grilles are available in the literature or can be experimentally determined. Values of C<j and Ru are required for deter mining V0, Do and A0 for orifice-type and multiple-opening outlets, and should, therefore, be included in catalog data of these outlets. In the case of multiple-opening outlets and annular-ring outlets (see diagram A of Fig. 1), the streams coalesce into a solid jet before actual jet expansion takes place. This coalescence affects the experimentally de termined proportionality constants K or K' and accounts for some of the divergence in reported values for similar outlets. Centerline Velocities in Zones 1 and 2 , Experimental evidence indicates that in Zone 2 Vx _ ,./WHq (3) '` ` " Vo ~ %. X, / .; , Air Distribution 697' where Ho -- width of jet at outlet or at vena contracta. Approximately the same values of K! apply as for Zone 3 expansion from axial outlets. In Zone 1, the ratio Vx/Vo is constant and equal to the ratio of the cen- Fig. 2. Effective Diameters for Round and Rectangular Openings (Plenum Approach) er velocity of the jet at start of expansion to the average velocity, ranging rom approximately 1.0 for rounded-entrance nozzles to about 1.2 for raight pipe discharge, but with much higher values for diverging-dis-: charge outlets. Determining Centerline Velocities perrPt correlation of data from all four zones, centerline velocity ras are plotted against distance from outlet in Fig. 3 in accordance with